Numerical Analysis of Key Parameters Influencing the Performance of a PV/T System with Surface-Augmented Forced Air and Nanofluids ()
1. Introduction
The growing global demand for energy, driven by population increase and industrialization, has intensified interest in renewable and sustainable energy solutions. Among these, solar energy is particularly attractive due to its abundance and environmental benefits [1] [2]. Photovoltaic/Thermal (PV/T) systems have gained attention as hybrid technologies capable of producing both electrical and thermal energy from solar radiation, thereby improving overall system efficiency [3] [4]. A key challenge in PV/T systems is the elevated temperature of photovoltaic (PV) cells, which can exceed 50˚C under high irradiance. This leads to reduced electrical efficiency and may cause permanent damage to the cell structure [5]. To mitigate this, various cooling strategies have been proposed, ranging from conventional fluids to advanced nanofluids [6] [7]. Nano fluids, suspensions of nanoparticles in base fluids, have demonstrated significant potential in enhancing heat transfer. Several studies have reported improved thermal and exergy performance of PV/T systems with nanofluid use. For example, Sardarabadi et al. observed a notable increase in both energy and exergy efficiency using SiO2-water nanofluids [8]. Similarly, Hamoudah and Etaig [9] reported lower PV cell temperatures and enhanced thermal performance with Al2O3-water mixtures. Recent works also explored advanced geometries and hybrid nanofluids. Samylingam et al. applied CFD and response surface methodology (RSM) to optimize system parameters using MXene-based nanofluids, achieving over 80% energy efficiency [10]. Abdelgaied et al. emphasized the role of fin configurations in dual-fluid systems, showing efficiency gains through optimized designs [11].
However, limited research has integrated CFD simulations, nanofluid cooling, surface-enhanced designs, and statistical optimization into a unified analysis. This study addresses this gap by evaluating a PV/T system equipped with forced air flow and serpentine copper tubes—both finned and unfinned—cooled by water, graphene-water, and MWCNT-water nanofluids. The concentration of nanofluids used in the analysis is 0.5%. The thermo-physical properties of MWCNT/water nanofluid are given as follows: density 1600 kg/m3, thermal conductivity 3000 W/(m∙K), and specific heat 0.796 kJ/(kg∙K). Similarly, the thermophysical properties of Graphene nanofluid are given as follows: density 2100 kg/m3, thermal conductivity 5000 W/(m∙K), and specific heat 0.710 kJ/(kg∙K). In the analysis, these properties for water were taken as density 997 kg/m3, thermal conductivity 0.607 W/(m∙K), and specific heat 4.180 kJ/(kg∙K), respectively [3]. Simulations were conducted using ANSYS Fluent, and results were optimized using Taguchi and regression analyses to determine ideal operating conditions.
2. Computational Fluid Dynamics (CFD) Analysis in PV/T
Systems
Computational Fluid Dynamics (CFD) is a highly precise analytical technique that simulates fluid flow phenomena using numerical methods and databases. When modeling PV/T (Photovoltaic/Thermal) systems with CFD, the Navier-Stokes conservation equations are employed to accurately resolve flow dynamics in accordance with the system’s geometry. The three-dimensional Navier-Stokes equations used in the analysis are summarized below [12] [13]:
Mass Conservation Equation:
(1)
Momentum Conservation Equation:
1) in the x-direction
(2)
2) in the y-direction
(3)
3) in the z-direction
(4)
These conservation equations are solved numerically using finite volume-based codes in CFD. The CFD workflow involves:
1) Defining the PV/T system geometry.
2) Generating a mesh structure.
3) Simulating flow dynamics within the system.
4) Assigning fluid properties and boundary conditions to the geometry.
To account for turbulence effects, the Reynolds-Averaged Navier-Stokes (RANS) equations were employed. Among the various turbulence models available in commercial CFD software, the SST k-omega model was selected for this study. This model combines the strengths of the k-epsilon (k-ε) and omega (ω) models, providing more accurate predictions of turbulent flow behavior [14] [15]. The SST k-omega model accurately captures viscous friction effects, particularly in the viscous sublayer of turbulence. It also performs well in the free-stream region and can provide more accurate results in flows with reverse pressure gradients. When performing CFD analysis with the coil cooling system added to PV/T systems, an appropriate mathematical model must be created, and this mathematical model must also include fluid dynamics equations, energy equations, and turbulence models. The SST-k omega model preferred in the analysis contains equations that comprehensively address the physical behaviour of the system [13].
2.1. System Specifications
The PV/T system under investigation has the following dimensions:
Overall dimensions: 675 mm × 380 mm × 17.3 mm.
Absorber plate: 675 mm × 380 mm × 0.7 mm (thickness).
Serpentine pipe material: Copper.
Pipe dimensions: Outer diameter: 10 mm; Inner diameter: 8 mm; Total length: 280 cm.
The serpentine pipe is positioned within the air duct beneath the PV/T panel. Figures 1-5 illustrate the serpentine design, including cross-sectional and isometric views of both finned and finless configurations.
2.2. Mesh Structure
Different mesh types were applied to accommodate the system’s layered structure:
Tetrahedral mesh: Used for solid structures and the working fluid.
Hexahedral mesh: Applied to the forced air region.
As shown in Figures 2-5, the mesh resolution was as follows:
Finless serpentine: 1,507,318 cells.
Finned serpentine: 2,194,180 cells.
Figure 1. Serpentine and fins.
Figure 2. Cross-sectional view of fin.
Figure 3. Isometric view of the finned serpentine.
Figure 4. Isometric view of the finless serpentine.
Figure 5. Network structure in the modeled system.
3. Energy and Exergy Analysis
The total energy output of a PV/T panel is the sum of the thermal energy emitted, the electrical energy generated, and the power loss associated with the process. Mathematically, this can be expressed as:
(5)
where:
: Represents the power dissipated from the PV/T panel to the environment due to the temperature difference between the panel and its surroundings.
: Denotes the useful thermal power absorbed by the working fluid from the panel’s bottom surface.
3.1. Useful Thermal Power (
)
The thermal power can be calculated using:
(6)
where:
= Mass flow rate of the working fluid;
= Specific heat at constant pressure;
and
= Inlet and outlet temperatures of the fluid, respectively.
3.2. Electrical Power Output (
)
The electrical energy generated by the PV/T panel is given by:
(7)
where:
= Open circuit voltage;
= Short circuit current;
= Fill factor, representing the panel’s maximum power conversion efficiency.
(8)
where,
is the maximum electrical output power, calculated as:
(9)
Here,
and
are the voltage and current at the maximum power point (MPP). Thus, the electrical power can also be expressed as:
(10)
Energy input (
):
The energy input to the PV/T panel is determined by the total solar irradiance
incident on the panel’s surface area
:
(11)
3.3. Energy Efficiency (
)
The overall energy efficiency of the PV/T system is the ratio of useful output energy to the total input energy:
(12)
The overall energy efficiency of the PV/T system is the ratio of useful output energy to the total input energy:
(13)
where:
r = Packing factor (ratio of the PV cell area
to the panel area
);
r = 0: No PV cells in the panel;
r = 1: Entire panel area covered by PV cells.
The packing factor is calculated as:
(14)
For the PV/T system in this study, which includes an air flow duct and a serpentine coil for fluid circulation, the thermal efficiency is:
(15)
3.4. Exergy Analysis
Exergy efficiency reflects the quality of energy conversion from solar energy and is defined as:
(16)
where the total exergy output (
) includes electrical exergy and thermal exergy:
(17)
Expanding this for the working fluid and air:
(18)
where:
and
= Outlet pressures of the fluid and air;
and
= Inlet pressures;
and
= Gas constants for the fluid and air.
The exergy input to the system is derived from solar radiation:
(19)
where:
= Ambient temperature;
= Sun’s surface temperature (5777 K in exergy analysis).
Using Jeter’s equation [3] [16] [17], the solar exergy input simplifies to:
(20)
4. Results
4.1. CFD Analysis Results
4.1.1. PV/T Contours without Flow
This section presents the temperature contours of the PV/T panel under no-flow conditions for solar radiation levels of 200, 400, 600, and 1000 [W∙m−2]. Figure 6 and Figure 7 illustrate that the panel’s surface temperature increases with higher solar irradiance, as expected due to greater thermal energy absorption.
Figure 6. PV-T panel temperature distribution without flow for 200 [W∙m−2].
Figure 7. PV-T panel temperature distribution without flow for 1000 [W∙m−2].
The temperature gradient is more pronounced at higher irradiance, highlighting the need for effective cooling mechanisms in high-sunlight conditions.
4.1.2. PV/T Panels with Flow and Finless Serpentine
Temperature contours for the PV/T system with a finless serpentine and forced flow are analyzed for nanofluid, which achieves the best cooling, attributed to its superior thermal conductivity (Figures 8-18).
Cooling Performance: MWCNT/water under varying solar irradiance and with working fluids (water, graphene nano platelets, and MWCNT/water).
Figure 8. PV-T panel with flow and finless serpentine temperature contour obtained at air velocities of 1 [m∙s−1] for the working fluid water and 200 [W∙m−2].
Figure 9. PV-T panel with flow and finless serpentine temperature contour obtained at air velocities of 1 [m∙s−1] for the working fluid graphene nano platelet and 200 [W∙m−2].
Figure 10. PV/T panel with flow and finless serpentine temperature contour obtained at air velocities of 1 [m∙s−1] for the working fluid MWCNT-water and 200 [W∙m−2].
Figure 11. PV-T panel with flow and finless serpentine temperature contour obtained at air velocities of 5 [m∙s−1] for the working fluid water and 200 [W∙m−2].
Figure 12. PV-T panel with flow and finless serpentine temperature contour obtained at air velocities of 5 [m∙s−1] for the working fluid graphene nano platelet and 200 [W∙m−2].
Figure 13. PV-T panel with flow and finless serpentine temperature contour obtained at air velocities of 5 [m∙s−1] for the working fluid MWCNT-water and 200 [W∙m−2].
Figure 14. PV-T panel with flow and finless serpentine temperature contour obtained at air velocities of 1 [m∙s−1] for the working fluid water 1000 [W∙m−2].
Figure 15. PV-T panel with flow and finless serpentine temperature contour obtained at air velocities of 1 [m∙s−1] for the working fluid graphene nano platelet 1000 [W∙m−2].
Figure 16. PV/T panel with flow and finless serpentine temperature contour obtained at air velocities of 1 [m∙s−1] for the working fluid MWCNT/water 1000 [W∙m−2].
Figure 17. PV-T panel with flow and finless serpentine temperature contour obtained at air velocities of 5 [m∙s−1] for the working fluid water 1000 [W∙m−2].
Figure 18. PV-T panel with flow and finned serpentine temperature contour obtained at air velocities of 5 [m∙s−1] for the working fluid graphene nano platelet and 1000 [W∙m−2].
Air Velocity Impact: Higher air velocity [5 m∙s−1] further reduces panel temperatures compared to [1 m∙s−1]. The MWCNT/water nanofluid again outperforms other fluids, though temperatures remain higher than at 200 [W∙m−2] due to increased solar input. Nanofluids enhance cooling efficiency, with MWCNT/water being the most effective. Higher air velocities amplify this effect.
4.1.3. PV/T Panels with Flow and Finned Serpentine
The finned serpentine design is evaluated under the same conditions as Figures 19-30.
Figure 19. PV-T panel with flow and finned serpentine temperature contour obtained at air velocities of 5 [m∙s−1] for the working fluid MWCNT/water and 1000 [W∙m−2].
Figure 20. PV-T panel with flow and finned serpentine temperature contour obtained at air velocities of 1 [m∙s−1] for the working fluid water and 200 [W∙m−2].
Figure 21. PV-T panel with flow and finned serpentine temperature contour obtained at air velocities of 1 [m∙s−1] for the working fluid graphene nano platelet and 200 [W∙m−2].
Figure 22. PV-T panel with flow and finned serpentine temperature contour obtained at air velocities of 1 [m∙s−1] for the working fluid MWCNT/water 200 [W∙m−2].
Figure 23. PV-T panel with flow and finned serpentine temperature contour obtained at air velocities of 5 [m∙s−1] for the working fluid water and 200 [W∙m−2].
Figure 24. PV-T panel with flow and finned serpentine temperature contour obtained at air velocities of 5 [m∙s−1] for the working fluid graphene nano platelet and 200 [W∙m−2].
Figure 25. PV-T panel with flow and finned serpentine temperature contour obtained at air velocities of 5 [m∙s−1] for the working fluid MWCNT/water and 200 [W∙m−2].
Figure 26. PV-T panel with flow and finned serpentine temperature contour obtained at air velocities of 1 [m∙s−1] for the working fluid water 1000 [W∙m−2].
Figure 27. PV-T panel with flow and finned serpentine temperature contour obtained at air velocities of 1 [m∙s−1] for the working fluid graphene nano platelet 1000 [W∙m−2].
Figure 28. PV-T panel with flow and finned serpentine temperature contour obtained at air velocities of 1 [m∙s−1] for the working fluid MWCNT-water 1000 [W∙m−2].
Figure 29. PV-T panel with flow and finned serpentine temperature contour obtained at air velocities of 5 [m∙s−1] for the working fluid water 1000 [W∙m−2].
Figure 30. PV-T panel with flow and finned serpentine temperature contour obtained at air velocities of 5 [m∙s−1] for the working fluid graphene nano platelet 1000 [W∙m−2].
Despite higher baseline temperatures, the finned design with MWCNT/water mitigates temperature spikes effectively. Fins improve heat dissipation, with MWCNT/water maintaining the best performance.
Key Takeaway: Finned configurations consistently outperform finless ones, especially at high irradiance, due to increased surface area for heat transfer.
4.2. Energy and Exergy Analysis Results
Graphical results (Figures 31-42) compare system efficiencies across configurations. The energy and exergy analysis results obtained for the PV/T system are shown in the graphs below. In these graphs, the changes in the total energy and exergy efficiencies of the system for each different configuration condition can be easily observed.
Figure 31. Changes in the total energy efficiency of the system for each fluid flow in the finless serpentine at 5 [m∙s−1] air velocity and different solar radiation powers.
Figure 32. Comparison of the changes in the total energy efficiency of the system for inlet conditions without any flow and flow conditions in the finless serpentine for solar radiation power of 200 [W∙m−2].
Figure 33. Comparison of the changes in the total energy efficiency of the system for inlet conditions without any flow and flow conditions in the finless serpentine for solar radiation power of 1000 [W∙m−2].
Figure 34. Changes in the total energy efficiency of the system for each fluid flow in the finned serpentine at 5 [m∙s−1] air velocity and different solar radiation powers.
Figure 35. Comparison of the changes in the total energy efficiency of the system for inlet conditions without any flow and flow conditions in the finned serpentine for solar radiation power of 200 [W∙m−2].
Figure 36. Comparison of the changes in the total energy efficiency of the system for inlet conditions without any flow and flow conditions in the finned serpentine for solar radiation power of 1000 [W∙m−2].
Finned vs. Finless: Finned serpentines improve energy efficiency by ~10% on average.
Figure 37. Changes in the total exergy efficiency of the system for each fluid flow in the finless serpentine at 5 [m∙s−1] air velocity and different solar radiation powers.
Figure 38. Comparison of the changes in the total exergy efficiency of the system for inlet conditions without any flow and flow conditions in the finless serpentine for solar radiation power of 200 [W∙m−2].
Figure 39. Comparison of the changes in the total exergy efficiency of the system for inlet conditions without any flow and flow conditions in the finless serpentine for solar radiation power of 1000 [W∙m−2].
Figure 40. Changes in the total exergy efficiency of the system for each fluid flow in the finned serpentine at 5 [m∙s−1] air velocity and different solar radiation powers.
Figure 41. Comparison of the changes in the total exergy efficiency of the system for inlet conditions without any flow and flow conditions in the finned serpentine for solar radiation power of 200 [W∙m−2].
Figure 42. Comparison of the changes in the total exergy efficiency of the system for inlet conditions without any flow and flow conditions in the finned serpentine for solar radiation power of 1000 [W∙m−2].
Finned Systems: Show a 0.5% average increase in exergy efficiency.
Nanofluids: MWCNT/water maximizes exergy output, aligning with energy efficiency trends. As a conclusion, combining finned designs with MWCNT/water nanofluid and high air velocity optimizes both energy and exergy performance.
4.3. Comparative Analysis with Literature
Table 1 shows a comparison of the results regarding system effectiveness obtained in this study with similar studies previously conducted in the literature. When this table is examined, there is a good agreement between the results obtained from the analysis where system efficiency was calculated and those in the literature. In general, it is understood that the efficiency of the finned serpentine system using nanofluids is higher than that of other configurations. It is possible to achieve different performance improvements depending on basic parameters such as nanofluid type, finned or finless serpentine design, and solar cell structure. In order to increase the efficiency of PV/T systems, there is a need for future studies on low-cost nanofluids with good thermal properties.
Finned Systems: Achieve higher thermal efficiency (14.73%) than finless designs (10.04%).
Nanofluids: Outperform water-based systems, with MWCNT/water leading.
Agreement with Literature: Results align with studies using similar nanofluids and configurations. Future research should focus on cost-effective nanofluids and advanced fin geometries to further boost efficiency.
Table 1. Comparison of this study with different studies in terms of system effectiveness.
Studies |
Inputs |
Work Fluids |
Comparison of the Performance of Classical PV Systems and PV/T Systems according to Reference Systems with Different Configurations |
ηth, finless (%) |
ηth, finned (%) |
εfinless (%) |
εfinned (%) |
Alous, S., Kayfeci, M., and Uysal, A. [3] |
0.5 L∙min−1, Imax = 940 W∙m−2 |
MCWNT/Water |
13.6 |
- |
- |
|
Fayaz, H., Nasrin, R., Rahim, N.A., et al. [22] |
120 L∙min−1, Imax = 1000 W∙m−2 |
MCWNT/Water |
12.25 |
- |
- |
- |
Nasrin, R., Rahim, N.A., Fayaz, H., et al. [23] |
0.5 L∙min−1, Imax = 1000 W∙m−2 |
MCWNT/Water |
9.2 |
- |
- |
- |
Hemmat Esfe, M., Kamyab, M.H., Valadkhani, M. [4] |
3.73 kg∙s−1, Imax = 810.54 W∙m−2 |
Water |
13.8 |
- |
- |
- |
Farzanehnia, A. and Sardarabadi, M. [24] |
Imax= 1000 - 1150 W∙m−2 |
CWWs |
- |
8.3 |
|
7.8 |
Farzanehnia, A. and Sardarabadi, M. [24] |
Imax= 1000 - 1150 W∙m−2 |
RAFs |
- |
5.1 |
|
4 |
Lee, J.H., Hwang, S.G. and Lee, G.H. [25] |
3 - 4 L∙min−1, Imax = 958.22 W∙m−2 |
CuO/Water |
21.30 |
- |
- |
- |
Lee, J.H., Hwang, S.G.
and Lee, G.H. [25] |
3 - 4 L∙min−1, Imax = 958.22 W∙m−2 |
Al2O3/Water |
15.14 |
- |
- |
- |
Prasetyo, S.D., Prabowo, A.R.
and Arifin, Z. [26] |
0.01 kg∙s−1 |
SiO2 |
14.31 |
- |
- |
- |
Gundala, S., Basha, M.M., Madhurima, V., et al. [27] |
0.5 - 1 L∙min−1, Imax = 1017.1 W∙m−2 |
Water, Graphene/Water |
26.3 |
- |
- |
- |
Abdallah, S.R.,
Saidani-Scott, H. and Abdellatif, O.E. [19] |
1.2 L∙min−1, Imax = 1000 W∙m−2 |
MCWNT/Water |
26.4 |
- |
- |
- |
Özakin, A.N. and Kaya, F. [18] |
0.065 kg∙s−1, Imax = 1000 W∙m−2 |
Air |
- |
- |
25 |
30 |
Sardarabadi, M., Passandideh-Fard, M., et al. [8] |
40 L∙h−1, Imax = 921 W∙m−2 |
SiO2 (Silica)/Water |
12.8 |
- |
24.31 |
- |
Al-Shamani, A.N., Sopian, K., Mat, S., et al. [28] |
0.17 kg∙s−1, Imax = 1000 W∙m−2 |
SiC/Water |
12.857 |
- |
- |
- |
Al-Waeli, A.H.A., Chaichan, M.T., et al. [29] |
0.17 kg∙s−1, Imax = 1000 W∙m−2 |
SiC/Water |
- |
13.7 |
- |
- |
Ebaid, M.S.Y., Ghrair, A.M. and Al-Busoul, M. [30] |
5 L∙min−1, Imax = 830 W∙m−2 |
TiO2/Al2/O3/Water |
- |
7.67 |
- |
- |
Hosseinzadeh, M., Salari, A.,
et al. [21] |
9 kg∙s−1, Imax = 830 W∙m−2 |
ZnO/Water, Pure Water |
- |
16.21 |
|
- |
Chow, T.T. [1] |
M/Ac = 75 kg∙m−2, Imax = 600 W∙m−2 |
Water |
- |
- |
12.1 |
- |
Present Study |
5 m∙s−1, Imax = 1000 W∙m−2 |
MCWNT/Water, Graphene/Water |
10.04 |
14.73 |
4.5 |
4.5 |
5. Optimization
5.1. Challenges and Objectives
PV/T systems operating without active cooling experience elevated temperature limits, leading to performance degradation and reduced operational lifespan. Non-uniform temperature distribution and thermal stress further exacerbate these issues. As demonstrated by the contours and graphs, configurations utilizing nanofluids and finned serpentines significantly improve temperature regulation, ensuring the system operates within optimal thermal ranges. The finned serpentine design enhances convective heat transfer by increasing the surface area for heat exchange between the coolant and the PV/T surface, thereby accelerating heat dissipation and lowering module temperatures. Among the tested configurations, the finned serpentine with MWCNT/water nanofluid emerges as the most effective, achieving the highest system performance.
5.2. Methodology: Taguchi and Regression Analysis
To optimize system performance, the Taguchi method was employed to identify the most efficient operating parameters. This statistical approach was complemented by a regression-based sensitivity analysis, which quantified the impact of key variables—such as flow rate, solar irradiance, and serpentine configuration—on system efficiency. In the Taguchi analysis performed using a suitable statistical program, 27 different designs were planned for each configuration, each with a level design of 4 and a number of factors of 3. Here, solar radiation values of 200, 400, 600, 800, 1000 W/m2 were taken as design levels, respectively, while air flow rate, energy, and exergy efficiencies were selected as factor numbers (Table 2). The analysis revealed correlations between inputs (e.g., air velocity, solar radiation) and outputs (e.g., exergy efficiency), enabling the derivation of optimal operating conditions. Key steps are included below:
1) Model Validation: Regression equations were generated for each flow configuration to predict exergy efficiency (ε).
2) Sensitivity Analysis: Determined the relative influence of each parameter (e.g., air velocity had a stronger effect than solar radiation in finned designs).
3) Error Assessment: Achieved high reliability with coefficients of determination (R2 > 95%) and minimal error rates (0.28% - 1.69%).
Table 2. Summary table of regression equations and performance metrics for each configuration.
Fluid |
εfinless (%) |
εfinned (%) |
Vair (m∙s−1) |
I (W∙m−2) |
R (%) |
Error (%) |
Multiply Regression Equation for εfinned (%) |
No Flow |
9.89 |
9.94 |
4.36 |
200 |
96.53 |
1.69 |
|
11.66 |
11.67 |
400 |
13.15 |
13.17 |
600 |
14.39 |
14.41 |
800 |
15.39 |
15.37 |
1000 |
Water |
11.29 |
11.31 |
5 |
200 |
98.64 |
0.95 |
|
13.08 |
13.15 |
400 |
14.69 |
14.83 |
600 |
16.14 |
16.34 |
800 |
17.44 |
17.67 |
1000 |
Graphene Nano Platelet/Water |
11.31 |
11.41 |
5 |
200 |
98.8 |
0.28 |
|
13.17 |
13.24 |
400 |
14.89 |
14.96 |
600 |
16.45 |
16.58 |
800 |
17.87 |
18.09 |
1000 |
MCWNT/Water |
11.33 |
11.35 |
5 |
200 |
96.74 |
0.69 |
|
13.27 |
13.34 |
400 |
15.05 |
15.18 |
600 |
16.68 |
16.87 |
800 |
18.15 |
18.4 |
1000 |
6. Discussion
6.1. Optimization Results
Optimization provides additional contributions to the precise determination of the optimum operating conditions for PV/T systems, the validation of CFD and thermodynamics analysis results. The statistical study also minimizes the complexity of the mathematical model by reducing the number of variables in the optimization process.
The temperature limits of the PVT system operating without any cooling increase, which leads to potential performance loss. Technically, the non-uniform temperature distribution, together with thermal stress, negatively affects the performance and operational life of the system. The temperature of the modules plays an important role in determining the module efficiency. Looking at the contours and graphs, it is clear that the nanofluid and finned serpentine configurations provide better results in reducing PVT system temperatures to ideal temperatures. The finned serpentine used improves the convective heat transfer rate by increasing the heat exchange surface area between the coolant and the PVT surface. This improvement enables faster heat removal from the PVT modules and ensures lower operating temperatures. Generally, it is understood that the PVT system with fins and MNCWNT nanofluid has the most effective system performance. As can be seen from the figures, when the solar radiation increases from 200 [W∙m−2] to 1000 [W∙m−2], the cooling fluid temperatures also increase.
Finned vs. Finless: Finned serpentines consistently outperformed finless designs, with exergy efficiency improvements of up to 18.4% for MWCNT/water at 1000 W/m2 and 5 m∙s−1 air velocity.
Nanofluid Superiority: MWCNT/water nanofluid yielded the highest efficiency due to its superior thermal conductivity, followed by graphene nano platelets and water.
Key Parameters:
Air velocity (Vair): Higher velocities (5 m∙s−1) enhanced cooling but required balancing against pumping power costs.
Solar radiation (I): Efficiency scaled with irradiance, though temperature management became critical at 1000 [W∙m−2].
Sample Regression Equation for MWCNT/Water (Finned):
6.2. Practical Implications
6.2.1. Design Recommendations
Prioritize finned serpentines with MWCNT/water nanofluid for maximal efficiency.
Optimize air velocity to [5 m∙s−1] for high-irradiance conditions (≥800 W∙m−2).
6.2.2. Future Work
Explore low-cost nanofluids with comparable thermal properties.
Investigate hybrid cooling systems (e.g., nanofluids + phase-change materials).
6.3. Key Findings and Performance Improvements
As the performance of PV/T systems increases by around 30% at ideal cell temperatures, the addition of a suitable cooling system and the selection of the working fluid are important design criteria for such systems. Through computational fluid dynamics (CFD) and thermodynamic analyses, conducted using Ansys Fluent. This study evaluated designs to enhance PV/T system efficiency. Key results include:
Finned Serpentine Superiority: Achieved a 10% increase in total energy efficiency and a 0.5% rise in exergy efficiency compared to finless designs.
Nanofluid Performance: The MWCNT/water mixture delivered the highest performance, outperforming graphene nano-pellet/water and pure water by 5% in energy efficiency and 0.4% in exergy efficiency.
Airflow Impact: Higher air velocities consistently improved both energy and exergy efficiencies across all configurations.
6.4. Proposed Design Enhancements
To further optimize PV/T systems, the following steps are recommended.
6.4.1. Advanced Serpentine and Fin Designs
Develop more compact and aerodynamically efficient serpentine geometries to maximize heat transfer surface area.
Explore multi-fin arrangements or graded fin densities to address localized hot spots.
6.4.2. Nanofluid Innovation
To improve the efficiency of PV/T systems, a PV/T system with and without fins and a serpentine type heat exchanger was analyzed, and the use of nanofluids at a concentration of 0.5%, water, and air circulation at different velocities from the external surface was also considered.
Experiment with hybrid nanofluids (e.g., MWCNT + graphene) to synergize thermal properties.
Investigate cost-effective alternatives (e.g., oxide-based nanofluids) without compromising performance.
6.4.3. Experimental Validation
Validate CFD results with real-world prototypes to bridge the gap between simulation and practical performance. Conduct long-term durability tests to assess nanofluid stability and system degradation.
7. Conclusions
This study investigated the thermal and exergetic performance of a PV/T system enhanced with internal fins and nanofluids under varying air velocities and solar irradiance. CFD simulations combined with Taguchi optimization and regression analysis provided valuable insights into how different configurations influence energy conversion efficiency.
Finned serpentine channels significantly improved both energy and exergy efficiencies compared to finless designs—by up to 10% and 0.5%, respectively—due to increased heat transfer surface area [18].
Among the tested fluids, MWCNT/water nanofluid achieved the highest overall performance, with up to 18.4% exergy efficiency at 1000 [W∙m−2] and 5 [m∙s−1] air velocity. This aligns with previous studies highlighting the superior thermal conductivity of MWCNTs [3] [19].
Higher air velocities consistently improved cooling effectiveness and system output, though practical limitations such as fan power and noise must be considered [20].
The integration of CFD analysis, surface modification, and advanced fluids has proven effective in optimizing PV/T system performance. The proposed finned configuration with MWCNT/water nanofluid under high air velocity is recommended for future PV/T designs. These findings are consistent with prior research emphasizing the importance of fluid selection and heat exchanger design in enhancing PV/T system efficiency [18] [21].
One of the fundamental criteria in the design of the air-source, finned serpentine heat exchanger used in the PV/T system is ensuring minimum fan power and pressure drop values. The optimal design of this type of heat exchangers is based on a certain number of geometrical and operational parameters. As is known, an optimization design starts by selecting criteria to minimize or maximize, which is called an objective function. In an optimization design, the requirements of a particular design, such as required heat transfer, allowable pressure drop, and fan power, are calculated accordingly, along with other constraints. Therefore, to overcome these requirements, advanced optimization algorithms such as the genetic algorithm are developed, which are gradient-free.
This study focuses on the cooling system and working fluids that improve the thermal performance of PVT systems for operation under ideal conditions; however, the fan power providing the secondary fluid air flow and the pressure drop in the flow medium have not been calculated. In more comprehensive analyses, the role of these two parameters in the operation of the system, especially under economic conditions, should be investigated.
Even if the pressure drop and fan power requirements for the secondary fluid air in the analyzed system are quite low, they can become quite significant for PV/T power plants, leading to a significant increase in energy consumption and a reduction in overall performance. In the literature, optimization studies of excessive pressure drop across serpentine can aim for air flow without excessive power use. Similarly, minimizing fan power and pressure drop have shown improvements; these must be carefully designed to provide optimal size and capacity. To balance this capacity/size ratio, fan systems can be geometrically reduced in size by approximately 4% to 10% [31] [32].
Future work should focus on cost-effective nanofluid alternatives, hybrid cooling methods (e.g., nanofluids with PCMs), and experimental validation under real environmental conditions. Researchers working on PV/T systems, a renewable energy source, should focus on analyses aimed at developing well-designed cooling heat exchangers and working nanofluids, and bring high-efficiency systems to industry through advanced analysis techniques and algorithms.