<?xml version="1.0" encoding="UTF-8"?><!DOCTYPE article  PUBLIC "-//NLM//DTD Journal Publishing DTD v3.0 20080202//EN" "http://dtd.nlm.nih.gov/publishing/3.0/journalpublishing3.dtd"><article xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink" dtd-version="3.0" xml:lang="en" article-type="research article"><front><journal-meta><journal-id journal-id-type="publisher-id">JPEE</journal-id><journal-title-group><journal-title>Journal of Power and Energy Engineering</journal-title></journal-title-group><issn pub-type="epub">2327-588X</issn><publisher><publisher-name>Scientific Research Publishing</publisher-name></publisher></journal-meta><article-meta><article-id pub-id-type="doi">10.4236/jpee.2020.84002</article-id><article-id pub-id-type="publisher-id">JPEE-99637</article-id><article-categories><subj-group subj-group-type="heading"><subject>Articles</subject></subj-group><subj-group subj-group-type="Discipline-v2"><subject>Engineering</subject></subj-group></article-categories><title-group><article-title>
 
 
  Frequency Control of Power System with Renewable Power Sources by HVDC Interconnection Line and Battery Considering Energy Balancing
 
</article-title></title-group><contrib-group><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Shoyu</surname><given-names>Onuka</given-names></name><xref ref-type="aff" rid="aff1"><sup>1</sup></xref><xref ref-type="corresp" rid="cor1"><sup>*</sup></xref></contrib><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Atsushi</surname><given-names>Umemura</given-names></name><xref ref-type="aff" rid="aff1"><sup>1</sup></xref></contrib><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Rion</surname><given-names>Takahashi</given-names></name><xref ref-type="aff" rid="aff1"><sup>1</sup></xref></contrib><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Junji</surname><given-names>Tamura</given-names></name><xref ref-type="aff" rid="aff1"><sup>1</sup></xref></contrib><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Atsushi</surname><given-names>Sakahara</given-names></name><xref ref-type="aff" rid="aff2"><sup>2</sup></xref></contrib><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Ryosuke</surname><given-names>Nakamoto</given-names></name><xref ref-type="aff" rid="aff2"><sup>2</sup></xref></contrib><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Fumihito</surname><given-names>Tosaka</given-names></name><xref ref-type="aff" rid="aff2"><sup>2</sup></xref></contrib></contrib-group><aff id="aff2"><addr-line>Hokkaido Electric Power Co., Inc., Sapporo, Japan</addr-line></aff><aff id="aff1"><addr-line>Department of Electrical and Electronic Engineering, Kitami Institute of Technology, Kitami, Japan</addr-line></aff><pub-date pub-type="epub"><day>20</day><month>04</month><year>2020</year></pub-date><volume>08</volume><issue>04</issue><fpage>11</fpage><lpage>24</lpage><history><date date-type="received"><day>19,</day>	<month>March</month>	<year>2020</year></date><date date-type="rev-recd"><day>18,</day>	<month>April</month>	<year>2020</year>	</date><date date-type="accepted"><day>21,</day>	<month>April</month>	<year>2020</year></date></history><permissions><copyright-statement>&#169; Copyright  2014 by authors and Scientific Research Publishing Inc. </copyright-statement><copyright-year>2014</copyright-year><license><license-p>This work is licensed under the Creative Commons Attribution International License (CC BY). http://creativecommons.org/licenses/by/4.0/</license-p></license></permissions><abstract><p>
 
 
  Recently, introduction of renewable energy sources like wind power generation and photovoltaic power generation has been increasing from the viewpoint of environmental problems. However, renewable energy power supplies have unstable output due to the influence of weather conditions such as wind speed variations, which may cause fluctuations of voltage and frequency in the power system. This paper proposes fuzzy PD based virtual inertia control system to decrease frequency fluctuations in power system caused by fluctuating output of renewable energy sources. The proposed new method is based on the coordinated control of HVDC interconnection line and battery, and energy balancing control is also incorporated in it. Finally, it is concluded that the proposed system is very effective for suppressing the frequency fluctuations of the power system due to the large-scale wind power generation and solar power generation and also for keeping the energy balancing in the HVDC transmission line.
 
</p></abstract><kwd-group><kwd>High Voltage Direct Current (HVDC) Transmission</kwd><kwd> Power System  Frequency Control</kwd><kwd> Coordinated Control</kwd><kwd> Battery</kwd><kwd> Renewable Power</kwd><kwd> Energy Balancing</kwd></kwd-group></article-meta></front><body><sec id="s1"><title>1. Introduction</title><p>Many studies have been reported so far about renewable energy systems like wind power generation and photovoltaic power generation [<xref ref-type="bibr" rid="scirp.99637-ref1">1</xref>] [<xref ref-type="bibr" rid="scirp.99637-ref2">2</xref>]. The advantage of wind power generation is that the power generation cost is comparatively lower and the energy conversion efficiency is higher than other renewable energy power generations. In addition, there is the advantage in photovoltaic power generation that no noise is appeared in power generation process and the power generation efficiency is about constant regardless of the installed system size. However, the output of these renewable energy power generations may fluctuate due to intermittent characteristics like fluctuations of wind speed and solar radiation intensity. This can cause power system frequency and voltage fluctuations. Therefore, various methods for controlling frequency fluctuations have been investigated [<xref ref-type="bibr" rid="scirp.99637-ref3">3</xref>] [<xref ref-type="bibr" rid="scirp.99637-ref4">4</xref>] [<xref ref-type="bibr" rid="scirp.99637-ref5">5</xref>] [<xref ref-type="bibr" rid="scirp.99637-ref6">6</xref>]. Among them, control method using HVDC interconnection line can be thought to be strong and effective method [<xref ref-type="bibr" rid="scirp.99637-ref7">7</xref>]. This is because the power ratings of actual HVDC interconnection lines are relatively large in most cases and active power flow on the HVDC transmission line can be controlled, in general, easily and quickly based on the AC/DC converter control. This paper proposes fuzzy PD based virtual inertia control system to restrain system frequency fluctuation caused by fluctuating output of renewable energy power supply, which is based on the coordinated control of HVDC interconnection line and battery. In addition, we also propose energy balancing control which is incorporated in the coordinated control system to keep the transmitted energy (MWh) of HVDC transmission line constant at the end of every specified period. Though there have been some reports so far in which power system frequency fluctuations caused by fluctuating output of renewable power sources are controlled by using HVDC interconnection line and battery as stated above, there is almost no one which achieves also the energy balancing control as far as the authors know. Simulation analyses are performed by using PSCAD/EMTDC software to verify the effectiveness of the proposed method.</p></sec><sec id="s2"><title>2. Model System</title><sec id="s2_1"><title>2.1. Power System Model</title><p>The power system model used in this study and its parameters are shown in <xref ref-type="fig" rid="fig1">Figure 1</xref>. It is a modified version of the IEEE standard model with 9 buses [<xref ref-type="bibr" rid="scirp.99637-ref8">8</xref>] which is composed of 3 synchronous generators (SG1, SG2, and SG3). SG1 and SG2 are thermal power plants (SG1: 200 MVA, SG2: 200 MVA), and SG3 is a hydraulic power plant (200 MVA). Moreover, a fixed speed wind turbine squirrel cage induction generator (SCIG) based wind farm (WF, 60 MVA), a PV station (60 MVA), HVDC interconnection line (60 MVA), battery (10 MVA), and three loads (Loads A, B, and C) are connected to the main system [<xref ref-type="bibr" rid="scirp.99637-ref9">9</xref>]. Their conditions are shown in <xref ref-type="table" rid="table1">Table 1</xref>. The HVDC transmission line is connecting the main modified 9-bus power system (System A) and another large power system (System B, expressed by an infinite bus) and the positive direction of the power flow is from System A to System B. Positive direction of battery power corresponds to charging.</p><table-wrap id="table1" ><label><xref ref-type="table" rid="table1">Table 1</xref></label><caption><title> Conditions of each generator</title></caption><table><tbody><thead><tr><th align="center" valign="middle" ></th><th align="center" valign="middle" >Generator</th><th align="center" valign="middle" >Rated MVA</th><th align="center" valign="middle" >Frequency Control</th></tr></thead><tr><td align="center" valign="middle" >SG1</td><td align="center" valign="middle" >Thermal</td><td align="center" valign="middle" >200 MVA</td><td align="center" valign="middle" >LFC<sup>*1 </sup></td></tr><tr><td align="center" valign="middle" >SG2</td><td align="center" valign="middle" >Thermal</td><td align="center" valign="middle" >200 MVA</td><td align="center" valign="middle" >GF<sup>*2 </sup></td></tr><tr><td align="center" valign="middle" >SG3</td><td align="center" valign="middle" >Hydro</td><td align="center" valign="middle" >200 MVA</td><td align="center" valign="middle" >LFC<sup>*1 </sup></td></tr><tr><td align="center" valign="middle" >SCIG</td><td align="center" valign="middle" >Wind Farm</td><td align="center" valign="middle" >60 MVA</td><td align="center" valign="middle" ></td></tr><tr><td align="center" valign="middle" >PV</td><td align="center" valign="middle" >Solar</td><td align="center" valign="middle" >60 MVA</td><td align="center" valign="middle" ></td></tr><tr><td align="center" valign="middle" >Total Load</td><td align="center" valign="middle" ></td><td align="center" valign="middle" >425 MW</td><td align="center" valign="middle" ></td></tr></tbody></table></table-wrap><p><sup>*1</sup>LFC: Load Frequency Control, <sup>*2</sup>GF: Governor Free.</p></sec><sec id="s2_2"><title>2.2. Governor Model [<xref ref-type="bibr" rid="scirp.99637-ref10">10</xref>]</title><p>In this study, SG1 and SG3 are operating under load frequency control (LFC) and SG2 is under governor free (GF) operation. <xref ref-type="fig" rid="fig2">Figure 2</xref> and <xref ref-type="fig" rid="fig3">Figure 3</xref> show the thermal governor model used for the thermal power plants (SG1 and SG2) and the hydro governor model used for the hydro power plant (SG3) respectively. The LFC system model is shown in <xref ref-type="fig" rid="fig4">Figure 4</xref>, where</p><p>Sg: Rotation speed deviation</p><p>65M: Load setting (Output reference value)</p><p>77M: Load limit (65M + rated output &#215; PLM [%])</p><p>PLM: Governor operating margin [%]</p><p>(A percentage of the rated output)</p><p>Pm: Turbine output</p><p>Input values of 65M and 77M are shown in <xref ref-type="table" rid="table2">Table 2</xref>. LFC system supplies output command signal to the LFC power plants according to the system frequency deviation. The LFC signal is input to 65M, and then, the output of each LFC power plant is changed. The governor models used in this paper is based on the standard models of the Institute of Electrical Engineers of Japan.</p><table-wrap id="table2" ><label><xref ref-type="table" rid="table2">Table 2</xref></label><caption><title> 65M and 77M of each generator</title></caption><table><tbody><thead><tr><th align="center" valign="middle" ></th><th align="center" valign="middle" >65M (Load setting)</th><th align="center" valign="middle" >77M (Load limit)</th></tr></thead><tr><td align="center" valign="middle" >SG1</td><td align="center" valign="middle" >Thermal LFC Signal</td><td align="center" valign="middle" >1.0</td></tr><tr><td align="center" valign="middle" >SG2</td><td align="center" valign="middle" >0.8</td><td align="center" valign="middle" >0.84</td></tr><tr><td align="center" valign="middle" >SG3</td><td align="center" valign="middle" >Hydro LFC Signal</td><td align="center" valign="middle" >1.0</td></tr></tbody></table></table-wrap></sec><sec id="s2_3"><title>2.3. Wind Turbine Model [<xref ref-type="bibr" rid="scirp.99637-ref11">11</xref>]</title><p>Wind turbine model used in this paper is shown in Equations (1)-(5).</p><p>P ω t b = ( 1 / 2 ) ρ C p ( λ , β ) π R 2 V w 3 (1)</p><p>C p ( λ , β ) = ( 1 / 2 ) ( Г − 0.022 β 2 − 5.6 ) e − 0.17 Г (2)</p><p>λ = ( ω W t b R ) / V w (3)</p><p>Г = ( R / λ ) ( 3600 / 1609 ) , C t ( λ ) = C p ( λ ) / λ (4)</p><p>τ M = 1 / 2 ρ C t ( λ ) π R 3 V w 2 (5)</p><p>where, P<sub>ωtb</sub>: wind turbine output [W], λ: tip speed ratio, R: wind turbine radius [m], ω<sub>Wtb</sub>: wind turbine angular speed [rad/s], β: pitch angle [deg], V<sub>w</sub>: wind speed [m/s], ρ: air density [kg/m<sup>3</sup>], C<sub>p</sub>: power coefficient, C<sub>t</sub>: torque coefficient, τ<sub>M</sub>: wind turbine torque [Nm].</p></sec><sec id="s2_4"><title>2.4. PV Model [<xref ref-type="bibr" rid="scirp.99637-ref3">3</xref>] [<xref ref-type="bibr" rid="scirp.99637-ref7">7</xref>]</title><p><xref ref-type="fig" rid="fig5">Figure 5</xref> shows PV model used in this paper. In this study, the PV model is expressed by a simple model using current sources, in which kilowatts data, P<sub>PV</sub> [kW], is used. Therefore, PV current (I<sub>PV</sub>) is calculated from P<sub>PV</sub> [kW] and PV voltage, V<sub>PV</sub> [kV], and the obtained current (I<sub>PV</sub>) is entered to the current sources.</p></sec><sec id="s2_5"><title>2.5. HVDC Model [<xref ref-type="bibr" rid="scirp.99637-ref4">4</xref>] [<xref ref-type="bibr" rid="scirp.99637-ref7">7</xref>] [<xref ref-type="bibr" rid="scirp.99637-ref12">12</xref>]</title><p><xref ref-type="fig" rid="fig6">Figure 6</xref> shows the Voltage Source Converter (VSC) based HVDC system model used in this study. In this paper, in order to shorten the calculation time of the simulation, VSC-HVDC simple model [<xref ref-type="bibr" rid="scirp.99637-ref9">9</xref>] is used which is expressed by controlled voltage sources instead of IGBT based inverter and rectifier. Reference 8 describes details of this simple model, where comparative analysis is performed between the VSC-HVDC simple model and the detailed VSC-HVDC model using IGBT switching circuits, and finally it is concluded that the accuracy of the VSC-HVDC simple model is high.</p><p><xref ref-type="fig" rid="fig7">Figure 7</xref> shows control system model of System A side converter that converts from three-phase AC to DC voltage. Also <xref ref-type="fig" rid="fig8">Figure 8</xref> shows control system model of System B side inverter that converts the DC voltage to the three-phase AC. The parameters of PI controllers used in <xref ref-type="fig" rid="fig7">Figure 7</xref> and <xref ref-type="fig" rid="fig8">Figure 8</xref> are shown in <xref ref-type="table" rid="table3">Table 3</xref>.</p><table-wrap id="table3" ><label><xref ref-type="table" rid="table3">Table 3</xref></label><caption><title> Parameter of PI controlers</title></caption><table><tbody><thead><tr><th align="center" valign="middle" ></th><th align="center" valign="middle" >PI1</th><th align="center" valign="middle" >PI2</th><th align="center" valign="middle" >PI3</th><th align="center" valign="middle" >PI4</th><th align="center" valign="middle" >PI5</th><th align="center" valign="middle" >PI6</th></tr></thead><tr><td align="center" valign="middle" >Proportional gain</td><td align="center" valign="middle" >0.1</td><td align="center" valign="middle" >0.1</td><td align="center" valign="middle" >1.0</td><td align="center" valign="middle" >0.1</td><td align="center" valign="middle" >0.1</td><td align="center" valign="middle" >0.1</td></tr><tr><td align="center" valign="middle" >Integral Time Constant</td><td align="center" valign="middle" >0.01</td><td align="center" valign="middle" >0.2</td><td align="center" valign="middle" >0.1</td><td align="center" valign="middle" >1.0</td><td align="center" valign="middle" >0.02</td><td align="center" valign="middle" >0.2</td></tr></tbody></table></table-wrap></sec><sec id="s2_6"><title>2.6. DC Link Model [<xref ref-type="bibr" rid="scirp.99637-ref4">4</xref>] [<xref ref-type="bibr" rid="scirp.99637-ref7">7</xref>] [<xref ref-type="bibr" rid="scirp.99637-ref12">12</xref>]</title><p>DC-link voltage in the DC-Link circuit of the HVDC model shown in <xref ref-type="fig" rid="fig6">Figure 6</xref> is expressed by Equation (6).</p><p>d V d c d t = 1 V d c C d c ( P r − P q ) (6)</p><p>where, V<sub>dc</sub>: DC voltage, C<sub>dc</sub>: capacitance of smoothing capacitor in the DC link (50,000 μF), P<sub>r</sub>: active power of the converter, P<sub>q</sub>: active power of the inverter, V<sub>dcn</sub>: rated voltage of the HVDC line (250 kV).</p></sec><sec id="s2_7"><title>2.7. Battery Model</title><p><xref ref-type="fig" rid="fig9">Figure 9</xref> shows battery model used in this paper. The battery model is expressed by a simple model using voltage sources. Q<sub>ref_Battery</sub> is fixed at zero. <xref ref-type="fig" rid="fig1">Figure 1</xref>0 shows the control model of battery converter that converts from three-phase AC to DC voltage. The parameters of PI controllers used in <xref ref-type="fig" rid="fig1">Figure 1</xref>0 are shown in <xref ref-type="table" rid="table3">Table 3</xref>.</p></sec></sec><sec id="s3"><title>3. Proposed Method</title><sec id="s3_1"><title>3.1. Fuzzy PD Control</title><p><xref ref-type="fig" rid="fig1">Figure 1</xref>1 and <xref ref-type="fig" rid="fig1">Figure 1</xref>2 show the fuzzy PD based virtual inertia control systems for the HVDC interconnection line and the battery proposed in this paper. The controller for the HVDC line shown in <xref ref-type="fig" rid="fig1">Figure 1</xref>1 is composed of PD controller in which D controller is based on FLC (Fuzzy Logic Controller). As differential value of the system frequency is used in the FLC, it can generate virtual inertia output component, and thus, it makes it possible to respond quickly to sudden frequency fluctuations. <xref ref-type="fig" rid="fig1">Figure 1</xref>3 and <xref ref-type="table" rid="table4">Table 4</xref> show the membership functions and fuzzy rule base designed for the FLC.</p><table-wrap id="table4" ><label><xref ref-type="table" rid="table4">Table 4</xref></label><caption><title> Fuzzy rule base</title></caption><table><tbody><thead><tr><th align="center" valign="middle"  colspan="2"   rowspan="2"  >FLC Signal</th><th align="center" valign="middle"  colspan="5"  >d(Δf)/dt</th></tr></thead><tr><td align="center" valign="middle" >PM</td><td align="center" valign="middle" >PS</td><td align="center" valign="middle" >ZR</td><td align="center" valign="middle" >NS</td><td align="center" valign="middle" >NM</td></tr><tr><td align="center" valign="middle"  rowspan="5"  >Δf</td><td align="center" valign="middle" >PM</td><td align="center" valign="middle" >PM</td><td align="center" valign="middle" >PM</td><td align="center" valign="middle" >PS</td><td align="center" valign="middle" >PS</td><td align="center" valign="middle" >ZR</td></tr><tr><td align="center" valign="middle" >PS</td><td align="center" valign="middle" >PM</td><td align="center" valign="middle" >PS</td><td align="center" valign="middle" >PS</td><td align="center" valign="middle" >ZR</td><td align="center" valign="middle" >ZR</td></tr><tr><td align="center" valign="middle" >ZR</td><td align="center" valign="middle" >PS</td><td align="center" valign="middle" >ZR</td><td align="center" valign="middle" >ZR</td><td align="center" valign="middle" >ZR</td><td align="center" valign="middle" >NS</td></tr><tr><td align="center" valign="middle" >NS</td><td align="center" valign="middle" >ZR</td><td align="center" valign="middle" >ZR</td><td align="center" valign="middle" >NS</td><td align="center" valign="middle" >NS</td><td align="center" valign="middle" >NM</td></tr><tr><td align="center" valign="middle" >NM</td><td align="center" valign="middle" >ZR</td><td align="center" valign="middle" >NS</td><td align="center" valign="middle" >NS</td><td align="center" valign="middle" >NM</td><td align="center" valign="middle" >NM</td></tr></tbody></table></table-wrap></sec><sec id="s3_2"><title>3.2. Coordinated Control</title><p>There is a permissible control range in the transmission power on HVDC interconnection line. This is &#177;10% of the rated capacity around the steady state transmission power in Japan under normal situation. Therefore, if the system frequency fluctuation is large so that the reference power of the HVDC line is over the permissible range, the HVDC line cannot control the frequency fluctuation. This paper proposes the coordinated control of HVDC interconnection line and battery. <xref ref-type="fig" rid="fig1">Figure 1</xref>2 shows the control systems for the battery, where the amount of power exceeding the permissible control range of the HVDC line is calculated, and then, sent to the battery as an output reference value.</p></sec><sec id="s3_3"><title>3.3. Energy Balancing Control [<xref ref-type="bibr" rid="scirp.99637-ref13">13</xref>]</title><p><xref ref-type="fig" rid="fig1">Figure 1</xref>4 and <xref ref-type="fig" rid="fig1">Figure 1</xref>5 show the control blocks used for energy balancing control of the HVDC system. The HVDC transmission MWh deviation, ΔMWs, from System A to System B is calculated by Equation (7).</p><p>Δ MWs = ∫ t t + τ ( PDC − PDC 0 ) d t (7)</p><p>where, P<sub>DC0</sub> is the reference value for HVDC transmission power, and P<sub>DC</sub> is the actual transmission power of the HVDC interconnection line. An auxiliary power signal P<sub>EB</sub> for the balancing control is generated by multiplying ΔMWs by a gain as shown in <xref ref-type="fig" rid="fig1">Figure 1</xref>4, and subtracted from the sum of PD control references as shown in <xref ref-type="fig" rid="fig1">Figure 1</xref>1 and <xref ref-type="fig" rid="fig1">Figure 1</xref>2. In the control block shown in <xref ref-type="fig" rid="fig1">Figure 1</xref>5, ΔMWs is passed through a Variable Dead Band (VDB), and then the auxiliary power signal P<sub>EB</sub> is obtained. As shown in <xref ref-type="fig" rid="fig1">Figure 1</xref>1 and <xref ref-type="fig" rid="fig1">Figure 1</xref>2, energy balancing control is performed by subtracting the auxiliary power signal P<sub>EB</sub> from the frequency control compensation power signals in the HVDC interconnection line and the storage battery. As described later, two types of gains that increase with time from a certain time t to t + τ in Equation (7) are used in the control block shown in <xref ref-type="fig" rid="fig1">Figure 1</xref>4.</p></sec></sec><sec id="s4"><title>4. Simulation Conditions</title><p>Simulation analyses have been performed in the 6 cases shown in <xref ref-type="table" rid="table5">Table 5</xref> to confirm the effectiveness of the proposed method. <xref ref-type="fig" rid="fig1">Figure 1</xref>6 shows the wind speed data and <xref ref-type="fig" rid="fig1">Figure 1</xref>7 shows the resulting output of WF used in the simulation analyses. <xref ref-type="fig" rid="fig1">Figure 1</xref>8 shows the PV data used in the simulation analyses. <xref ref-type="fig" rid="fig1">Figure 1</xref>9 shows the total output of WF and PV station. The data used in <xref ref-type="fig" rid="fig1">Figure 1</xref>6 and <xref ref-type="fig" rid="fig1">Figure 1</xref>8 were real data measured in Hokkaido, Japan. The simulation time was 1200 seconds and PSCAD/EMTDC software was used for the simulation analyses.</p><table-wrap id="table5" ><label><xref ref-type="table" rid="table5">Table 5</xref></label><caption><title> Study cases</title></caption><table><tbody><thead><tr><th align="center" valign="middle"  rowspan="2"  ></th><th align="center" valign="middle"  colspan="2"  >Control Method</th></tr></thead><tr><td align="center" valign="middle" >HVDC Interconnection Line</td><td align="center" valign="middle" >Battery</td></tr><tr><td align="center" valign="middle" >Case 1</td><td align="center" valign="middle" >Constant power transmission (fixed at 30 MW)</td><td align="center" valign="middle" >Stand-by (No control)</td></tr><tr><td align="center" valign="middle" >Case 2</td><td align="center" valign="middle" >Dead Band control</td><td align="center" valign="middle" >Stand-by (No control)</td></tr><tr><td align="center" valign="middle" >Case 3</td><td align="center" valign="middle" >Fuzzy PD control</td><td align="center" valign="middle" >Coordinated control</td></tr><tr><td align="center" valign="middle" >Case 4</td><td align="center" valign="middle" >Fuzzy PD control with energy balancing control (using gain I)</td><td align="center" valign="middle" >Coordinated control with energy balancing control (using gain I)</td></tr><tr><td align="center" valign="middle" >Case 5</td><td align="center" valign="middle" >Fuzzy PD control with energy balancing control (using gain II)</td><td align="center" valign="middle" >Coordinated control with energy balancing control (using gain II)</td></tr><tr><td align="center" valign="middle" >Case 6</td><td align="center" valign="middle" >Fuzzy PD control with energy balancing control (using Variable Dead Band)</td><td align="center" valign="middle" >Coordinated control with energy balancing control (using Variable Dead Band)</td></tr></tbody></table></table-wrap><p>In order to confirm the effectiveness of the proposed method, the energy balancing control for 10 minutes is performed twice in the simulation for 1200 seconds, i.e., 0 to 600 seconds and 600 to 1200 seconds. As shown in <xref ref-type="fig" rid="fig2">Figure 2</xref>0, two types of gains are used in the control block shown in <xref ref-type="fig" rid="fig1">Figure 1</xref>4, where gain I increases linearly from 0 at t = 300 seconds to 1.0 at t = 600 seconds and gain II increases linearly from 0 at t = 550 seconds to 1.0 at t = 600 seconds. On the other hand, Variable Dead Band is used in the control block shown in <xref ref-type="fig" rid="fig1">Figure 1</xref>5, of which threshold value becomes gradually narrower from &#177;6 [MWs] at 0 seconds to 0 [MWs] at 600 seconds as shown in <xref ref-type="fig" rid="fig2">Figure 2</xref>1. In <xref ref-type="fig" rid="fig2">Figure 2</xref>1, the white area is dead zone, and if ΔMWs exceeds the pink line, which is the threshold line, the energy balancing control is activated. Interval of the integration of Equation (7) for ΔMWs is set to [0, 600].</p></sec><sec id="s5"><title>5. Simulation Results</title><p>The simulation results are shown in Figures 22-25 and <xref ref-type="table" rid="table6">Table 6</xref>. <xref ref-type="fig" rid="fig2">Figure 2</xref>2 shows the frequency responses of System A in the 6 cases. <xref ref-type="fig" rid="fig2">Figure 2</xref>3 shows the HVDC transmission line power. <xref ref-type="fig" rid="fig2">Figure 2</xref>4 shows the battery power (positive value corresponds to charging). <xref ref-type="fig" rid="fig2">Figure 2</xref>5 shows the transmitted energy deviation, ΔMWs, obtained from Equation (7). <xref ref-type="table" rid="table6">Table 6</xref> shows the maximum deviation and the standard deviation of the frequency fluctuation of System A.</p><p>Comparing Cases 1 to 6 in <xref ref-type="fig" rid="fig2">Figure 2</xref>2 and <xref ref-type="table" rid="table6">Table 6</xref>, it is seen that the maximum frequency deviation in Case 1 exceeds the permissible range, &#177;0.2 Hz, which is the standard permissible range of power system frequency fluctuations in Japan. This is because the frequency control is not performed in Case 1. The frequency deviation is largest in this case. Next, the dead band control is performed in Case 2. However, since only the control by the HVDC interconnection line is performed in this case, the frequency fluctuation is also large and the</p><table-wrap id="table6" ><label><xref ref-type="table" rid="table6">Table 6</xref></label><caption><title> Maximum and standard deviation of system frequency</title></caption><table><tbody><thead><tr><th align="center" valign="middle" ></th><th align="center" valign="middle" >Case 1</th><th align="center" valign="middle" >Case 2</th><th align="center" valign="middle" >Case 3</th><th align="center" valign="middle" >Case 4</th><th align="center" valign="middle" >Case 5</th><th align="center" valign="middle" >Case 6</th></tr></thead><tr><td align="center" valign="middle" >Maximum Frequency Deviation +∆f [Hz]</td><td align="center" valign="middle" >0.4575</td><td align="center" valign="middle" >0.2974</td><td align="center" valign="middle" >0.1949</td><td align="center" valign="middle" >0.2010</td><td align="center" valign="middle" >0.1949</td><td align="center" valign="middle" >0.1976</td></tr><tr><td align="center" valign="middle" >Maximum Frequency Deviation −∆f [Hz]</td><td align="center" valign="middle" >−0.5514</td><td align="center" valign="middle" >−0.1906</td><td align="center" valign="middle" >−0.1484</td><td align="center" valign="middle" >−0.1886</td><td align="center" valign="middle" >−0.1484</td><td align="center" valign="middle" >−0.1534</td></tr><tr><td align="center" valign="middle" >Standard Deviation [Hz]</td><td align="center" valign="middle" >0.09696</td><td align="center" valign="middle" >0.05606</td><td align="center" valign="middle" >0.05316</td><td align="center" valign="middle" >0.05576</td><td align="center" valign="middle" >0.05377</td><td align="center" valign="middle" >0.05377</td></tr></tbody></table></table-wrap><p>fluctuation in the positive side exceeds 0.2 Hz. This is because the variations of HVDC transmission line power for controlling the system frequency fluctuations reach the permissible control range in the transmission power on HVDC interconnection line. The best results are obtained in Case 3 for both the maximum and standard deviations of the system frequency, because the coordinated control of HVDC interconnection line and battery is performed in this case. However, it is seen from <xref ref-type="fig" rid="fig2">Figure 2</xref>5 that the transmitted energy deviation, ΔMWs, does not become 0 at 600 and 1200 seconds, because the energy balancing control for 10 minutes is not performed in this case. On the other hand, ΔMWs becomes 0 at 600 and 1200 seconds in Cases 4, 5, and 6 as can be seen from <xref ref-type="fig" rid="fig2">Figure 2</xref>5, because the energy balancing control is performed in these cases. This confirms that the proposed energy balancing control is very effective for keeping the transmitted energy balance. In addition, it is also seen from <xref ref-type="table" rid="table6">Table 6</xref> that the performances about the system frequency deviations in these 3 cases are worse than that in Case 3. This is because the energy balancing control is also performed in Cases 4, 5 and 6. However the performances in Cases 5 and 6 are almost the same level as that in Case 3, and the best results are obtained in Case 5 where gain II shown in <xref ref-type="fig" rid="fig2">Figure 2</xref>0 is used in the energy balancing control block shown in <xref ref-type="fig" rid="fig1">Figure 1</xref>4.</p><p>As a result, it can be concluded that the coordinated control of HVDC interconnection line and battery in Case 5 is the most effective method for achieving both the system frequency control and the energy balancing control in the HVDC transmission line. As the proposed coordinated system (Case 5) can control well power system frequency fluctuations caused by fluctuating output of renewable power sources as well as can achieve the energy balancing in the HVDC interconnection line, it has original and significant values from a point of view of stabilization of power systems with renewable power sources installed.</p></sec><sec id="s6"><title>6. Conclusions</title><p>In this paper, a coordinated control method of HVDC interconnection line and battery is proposed in order to suppress the frequency fluctuations of the power system where wind farm and solar power station are installed, in which the control system is designed based on the fuzzy PD based virtual inertia controller and the energy balancing control in the HVDC transmission line is also considered.</p><p>Simulation analyses show the effectiveness of the proposed method. As a result, it is concluded that the system proposed in this paper is very effective for suppressing the frequency fluctuations of the power system caused by the large-scale introduction of wind power generation and solar power generation and also for keeping the energy balancing in the HVDC transmission line.</p></sec><sec id="s7"><title>Conflicts of Interest</title><p>The authors declare no conflicts of interest regarding the publication of this paper.</p></sec><sec id="s8"><title>Cite this paper</title><p>Onuka, S., Umemura, A., Takahashi, R., Tamura, J., Sakahara, A., Tosaka, F. and Nakamoto, R. (2020) Frequency Control of Power System with Renewable Power Sources by HVDC Interconnection Line and Battery Considering Energy Balancing. Journal of Power and Energy Engineering, 8, 11-24. https://doi.org/10.4236/jpee.2020.84002</p></sec></body><back><ref-list><title>References</title><ref id="scirp.99637-ref1"><label>1</label><mixed-citation publication-type="other" xlink:type="simple">Rahman, M.L., Oka, S. and Shirai, Y. (2010) Hybrid Power Generation System Using Offshore-Wind Turbine and Tidal Turbine for Power Fluctuation Compensation (HOT-PC). IEEE Transactions on Sustainable Energy, 1, 92-98.  
https://doi.org/10.1109/TSTE.2010.2050347</mixed-citation></ref><ref id="scirp.99637-ref2"><label>2</label><mixed-citation publication-type="other" xlink:type="simple">Lin, F., Lu, K., Ke, T., Yang, B. and Chang, Y. (2015) Reactive Power Control of Three-Phase Grid-Connected PV System During Grid Faults Using Takagi-Sugeno-Kang Probabilistic Fuzzy Neural Network Control. IEEE Transactions on Industrial Electronics, 62, 5516-5528. https://doi.org/10.1109/TIE.2015.2407851</mixed-citation></ref><ref id="scirp.99637-ref3"><label>3</label><mixed-citation publication-type="other" xlink:type="simple">Tada, K., Umemura, A., Takahashi, R., Tamura, J., Matsumura, Y., Yamaguchi, D., Kudo, H., Niiyama, M. and Taki, Y. (2017) Frequency Control of Power System with Solar and Wind Power Stations Installed by Flow Control of HVDC Interconnection Line. International Conference on Electrical Machines and Systems, ID621.  
https://doi.org/10.1109/ICEMS.2017.8056355</mixed-citation></ref><ref id="scirp.99637-ref4"><label>4</label><mixed-citation publication-type="other" xlink:type="simple">Sato, T., Umemura, A., Takahashi, R. and Tamura, J. (2017) Frequency Control of Power System with Large Scale Wind Farm Installed by Using HVDC Transmission System. IEEE PES PowerTech, Manchester, United Kingdom, 2017.  
https://doi.org/10.1109/PTC.2017.7979749</mixed-citation></ref><ref id="scirp.99637-ref5"><label>5</label><mixed-citation publication-type="other" xlink:type="simple">Ono, T. and Arai, J. (2012) Frequency Control with Dead Band Characteristic of Battery Energy Storage System for Power System Including Large Amount of Wind Power Generation. IEEJ Transaction on Power and Energy, 132, 709-717. (In Japanese) https://doi.org/10.1541/ieejpes.132.709</mixed-citation></ref><ref id="scirp.99637-ref6"><label>6</label><mixed-citation publication-type="other" xlink:type="simple">Wu, Z., Gao, D.W., Zhang, H., Yan, S. and Wang, X. (2017) Coordinated Control Strategy of Battery Energy Storage System and PMSG-WTG to Enhance System Frequency Regulation Capability. IEEE Transactions on Sustainable Energy, 8, 1330-1343. https://doi.org/10.1109/TSTE.2017.2679716</mixed-citation></ref><ref id="scirp.99637-ref7"><label>7</label><mixed-citation publication-type="other" xlink:type="simple">Tada, K., Sato, T., Umemura, A., Takahashi, R., Tamura, J., Matsumura, Y., Taguchi, T. and Yamada, A. (2018) Frequency Control of Power System with Solar and Wind Power Stations by Using Frequency Band Control and Deadband Control of HVDC Interconnection Line. Journal of Power and Energy Engineering, 6, 48-63.  
https://doi.org/10.4236/jpee.2018.69007</mixed-citation></ref><ref id="scirp.99637-ref8"><label>8</label><mixed-citation publication-type="other" xlink:type="simple">Anderson, P.M. and Found, A.A. (1994) Power System Control and Stability. IEEE Press, New York.</mixed-citation></ref><ref id="scirp.99637-ref9"><label>9</label><mixed-citation publication-type="other" xlink:type="simple">Rosyadi, M., Umemura, A., Takahashi, R., Tamura, J., Uchiyama, N. and Ide, K. (2015) Simplified Model of Variable Speed Wind Turbine Generator for Dynamic Simulation Analysis. IEEJ Transactions on Power System Power and Energy, 135, 538-549. https://doi.org/10.1541/ieejpes.135.538</mixed-citation></ref><ref id="scirp.99637-ref10"><label>10</label><mixed-citation publication-type="other" xlink:type="simple">Liu, J., Rosyadi, M., Umemura, A., Takahashi, R. and Tamura, J. (2014) A Control Method of Permanent Magnet Wind Generators in Grid Connected Wind Farm to Damp Load Frequency Oscillation. IEEJ Transactions on Power and Energy, 134, 393-398. https://doi.org/10.1541/ieejpes.134.393</mixed-citation></ref><ref id="scirp.99637-ref11"><label>11</label><mixed-citation publication-type="other" xlink:type="simple">Wasynczuk, O., Man, D.T. and Sullivan, J.P. (1981) Dynamic Behavior of a Class of Wind Turbine Generators during Randon Wind Fluctuations. IEEE Transactions on Power Apparatus and System, PAS-100, 2837-2845.  
https://doi.org/10.1109/TPAS.1981.316400</mixed-citation></ref><ref id="scirp.99637-ref12"><label>12</label><mixed-citation publication-type="other" xlink:type="simple">Jahan, E., Hazari, M.R., Rosyadi, M., Umemura, A., Takahashi, R. and Tamura, J. (2017) Simplified Model of HVDC Transmission System Connecting Offshore Wind Farm to Onshore Grid. IEEE PES PowerTech, Manchester 2017, No. 51.  
https://doi.org/10.1109/PTC.2017.7981049</mixed-citation></ref><ref id="scirp.99637-ref13"><label>13</label><mixed-citation publication-type="other" xlink:type="simple">Tada, K., Umemura, A., Takahashi, R., Tamura, J., Matsumura, Y., Yamaguchi, D., Kudo, H., Niiyama, M. and Taki, Y. (2019) Frequency Control of Power System with Renewable Power Sources by HVDC Interconnection Line Considering Energy Balancing. IEEJ Transactions on Power and Energy, 139, 163-169. (in Japanese)  
https://doi.org/10.1541/ieejpes.139.163</mixed-citation></ref></ref-list></back></article>