<?xml version="1.0" encoding="UTF-8"?><!DOCTYPE article  PUBLIC "-//NLM//DTD Journal Publishing DTD v3.0 20080202//EN" "http://dtd.nlm.nih.gov/publishing/3.0/journalpublishing3.dtd"><article xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink" dtd-version="3.0" xml:lang="en" article-type="research article"><front><journal-meta><journal-id journal-id-type="publisher-id">EPE</journal-id><journal-title-group><journal-title>Energy and Power Engineering</journal-title></journal-title-group><issn pub-type="epub">1949-243X</issn><publisher><publisher-name>Scientific Research Publishing</publisher-name></publisher></journal-meta><article-meta><article-id pub-id-type="doi">10.4236/epe.2019.112005</article-id><article-id pub-id-type="publisher-id">EPE-90712</article-id><article-categories><subj-group subj-group-type="heading"><subject>Articles</subject></subj-group><subj-group subj-group-type="Discipline-v2"><subject>Engineering</subject></subj-group></article-categories><title-group><article-title>
 
 
  Commercial Building Containing Generation Sources: A Technical and Economic Assessment and Its Potential to Participate in Demand Response Programs
 
</article-title></title-group><contrib-group><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Tesoro</surname><given-names>Elena Del Carpio-Huayllas</given-names></name><xref ref-type="aff" rid="aff1"><sup>1</sup></xref></contrib><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Dorel</surname><given-names>Soares Ramos</given-names></name><xref ref-type="aff" rid="aff1"><sup>1</sup></xref></contrib><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Ricardo</surname><given-names>Leon Vasquez-Arnez</given-names></name><xref ref-type="aff" rid="aff2"><sup>2</sup></xref></contrib></contrib-group><aff id="aff1"><addr-line>Department of Electric Power and Automation Engineering, University of S&amp;amp;atilde;o Paulo, S&amp;amp;atilde;o Paulo, Brazil</addr-line></aff><aff id="aff2"><addr-line>FDTE (Foundation for the Technological Development of the Engineering Sciences), S&amp;amp;atilde;o Paulo, Brazil</addr-line></aff><pub-date pub-type="epub"><day>20</day><month>02</month><year>2019</year></pub-date><volume>11</volume><issue>02</issue><fpage>76</fpage><lpage>91</lpage><history><date date-type="received"><day>25,</day>	<month>January</month>	<year>2019</year></date><date date-type="rev-recd"><day>22,</day>	<month>February</month>	<year>2019</year>	</date><date date-type="accepted"><day>25,</day>	<month>February</month>	<year>2019</year></date></history><permissions><copyright-statement>&#169; Copyright  2014 by authors and Scientific Research Publishing Inc. </copyright-statement><copyright-year>2014</copyright-year><license><license-p>This work is licensed under the Creative Commons Attribution International License (CC BY). http://creativecommons.org/licenses/by/4.0/</license-p></license></permissions><abstract><p>
 
 
  The interest on studying the impact of demand response is growing, especially on residential and commercial buildings which are responsible for a considerable consumption of energy worldwide. Also, it is virtually unquestionable that in most of these buildings there is a waste of energy, mainly electrical and thermal energy. In this context, the establishment of intelligent networks in these buildings, as well as the use of small or even medium-sized renewable sources of power can significantly contribute to the reduction and preservation of power. In this article, the results of the simulations carried out in a specific simulation program to evaluate the benefits brought by the installation of some local sources of power on a commercial building are presented. It is evaluated the impact on some of the economic variables linked to that system as well as compared its greenhouse gas emissions for the conditions with and without the presence of the local generation. It will also evaluate the building’s response towards the utility requirements, mainly the possibility to reduce or partially compensate the energy consumed, commonly referred to as Demand Response.
 
</p></abstract><kwd-group><kwd>Demand Response</kwd><kwd> Commercial Buildings</kwd><kwd> Cost of Energy</kwd><kwd> Net Present Cost</kwd><kwd> Small-Sized Generation Sources</kwd></kwd-group></article-meta></front><body><sec id="s1"><title>1. Introduction</title><p>Typically, demand response (DR) is referred to any program that motivates changes in the normal power consumption of the end users (consumers) in response to incentives regarding electricity prices. According to [<xref ref-type="bibr" rid="scirp.90712-ref1">1</xref>] , the main objectives of a demand response program are: reduce the periods of peak demand, fill up low-consumption periods (valleys), shift the maximum demand to another period, turn flexible the load curve, and reduce or increase the total consumption.</p><p>There are several ways of classifying DR programs. One of them depends on the objectives set [<xref ref-type="bibr" rid="scirp.90712-ref2">2</xref>] in the program; the type of market established (whole sale and retail markets) [<xref ref-type="bibr" rid="scirp.90712-ref3">3</xref>] is another way to classify DRs, and finally DRs can be classified according to the type of resources used [<xref ref-type="bibr" rid="scirp.90712-ref4">4</xref>] . Nevertheless, the two more traditional incentive DR programs are: incentive-based programs to reduce the consumption, and price-based programs [<xref ref-type="bibr" rid="scirp.90712-ref5">5</xref>] , [<xref ref-type="bibr" rid="scirp.90712-ref6">6</xref>] .</p><p>Incentive-based programs aim to reduce the end-user demand by controlling his/her major domestic loads’ associated consumption (e.g. cutting air conditioners, electric heaters, etc.). Price-based programs, in turn, strive in lowering the customer demand through the change in prices.</p><p>According to [<xref ref-type="bibr" rid="scirp.90712-ref7">7</xref>] , one of the countries that showed a high invest in demand-response projects is the USA. Other countries with substantial growth in DR programs are Australia, New Zealand, South Korea, China and Japan.</p><p>Despite the existence of a legal framework that allows the use of DR programs, only in some European countries the consumer response is commercially active [<xref ref-type="bibr" rid="scirp.90712-ref8">8</xref>] . According to a survey conducted by SEDC (Smart Energy Demand Coalition), France, Ireland, United Kingdom, Belgium, Switzerland and Finland are the countries with more active DR programs [<xref ref-type="bibr" rid="scirp.90712-ref7">7</xref>] , [<xref ref-type="bibr" rid="scirp.90712-ref9">9</xref>] . In [<xref ref-type="bibr" rid="scirp.90712-ref10">10</xref>] , some simulation tools are applied to analyse the DR of an islanded system considering some load conditions for its economic operation.</p><p>Commercial buildings have a large potential to participate in DR programs for reasons, such as, the electricity they consume today is significant, which gives them also a potential to generate onsite power. The load of these buildings is somewhat predictable operating in repeated schedules, thus, making them good candidates for DR programs. To this feature, it can be added the fact that most of them have a centralized control system, which reduces the cost for integrating them in DR programs [<xref ref-type="bibr" rid="scirp.90712-ref11">11</xref>] , [<xref ref-type="bibr" rid="scirp.90712-ref12">12</xref>] , [<xref ref-type="bibr" rid="scirp.90712-ref13">13</xref>] .</p><p>Some of the references available on the response of commercial buildings [<xref ref-type="bibr" rid="scirp.90712-ref14">14</xref>] , [<xref ref-type="bibr" rid="scirp.90712-ref15">15</xref>] , [<xref ref-type="bibr" rid="scirp.90712-ref16">16</xref>] , [<xref ref-type="bibr" rid="scirp.90712-ref17">17</xref>] suggest the use of small or medium-sized generation systems based on renewable sources. This is the case of some urban wind turbines [<xref ref-type="bibr" rid="scirp.90712-ref18">18</xref>] , which are driven by the relatively stronger winds available on top of the buildings. Solar panels are also placed on the roof of some buildings, on car parking lots as well as in some other specific areas of the building, as long as they do not interfere with the routine activities of the neighbourhood, air navigation, etc.</p><p>Today, most of the public buildings have some degree of automation, if not a high degree of intelligence. Examples of these partially automated systems are the lighting system in the corridors of a building with optical sensors that turn on/off the lights according to the users’ needs. There are also some other systems activated by infrared sensors to control and make an efficient use of water (water sinks) or to smartly operate the main doors of a building to preserve its inner temperature. Other aspects featuring a building as an intelligent one may be the maximum use of natural light instead of electric lamps, reuse of water, etc.</p><p>Automation systems such as BAS (Building Automation System), EMGI (Energy Management and Grid Interaction), and the building’s information technology system interact each other through communication protocols that may have a centralized or decentralized arrangement.</p><p>The main scope of this article is to evaluate the benefits brought by the installation of some local sources of power and observe its impact on some of the economic variables linked to a commercial building, as well as compare its greenhouse gas emissions for the conditions with and without the presence of such a local generation. It will also be evaluated the building’s response towards the utility requirements, commonly referred to as Demand Response. By applying tariffs with hourly, and/or contracts with financial incentives, the utility may induce changes in the load curve and improve operational bottlenecks.</p></sec><sec id="s2"><title>2. Description of the System</title><p>A medium-sized commercial building was considered to develop the technical and economic analysis. The power demand and consumption of such a building (2 MW and 560 MWh/month) are mainly fed by the utility. The local sources of power also contribute to complete feeding this demand. The installed sources are three wind generators of 50 kW each (which together generate approximately 54 MWh/month), a photovoltaic system containing 14 units, each with 250 Wp capacity. Both renewable sources are installed on top of the building. A 0.5 MVA diesel generator and a storage system (batteries) whose capacity is equal to 200 A-h. The latter sources are installed on the ground floor of the building (<xref ref-type="fig" rid="fig1">Figure 1</xref>). For this system, the following analyses were conducted:</p><p>− Case 1. Supply of power exclusively from the utility.</p><p>− Case 2. Power supplied by the utility and by the sources in the building.</p><p>− Case 3. Sensitivity analysis of Case 2.</p><p>The data and costs presented next were obtained from commercial catalogues and information provided by some manufacturers. The energy and demand (i.e. peak and off-peak) unit tariffs were obtained from a local utility [<xref ref-type="bibr" rid="scirp.90712-ref19">19</xref>] . The currency used here corresponds to American dollars represented by the symbol ($).</p><p>− Cost of the energy supplied by the utility during the peak period (14:00 - 22:00): 0.10 $/kWh.</p><p>− Cost of the energy supplied by the utility during the off-peak period (22:00 - 14:00): 0.067 $/kWh.</p><p>− Cost of the contracted demand from the utility during the peak period: 3.97 $/kW.</p><p>− Cost of the contracted demand from the utility during the off-peak period: 2.48 $/kW.</p><p>− Fuel cost (diesel): 0.873 $/L.</p><p>− Diesel generator cost (2018): $ 40,000 (service period: 15,000 hr).</p><p>− Wind generator cost (installation included): $ 250,000 (service period: 15 years).</p><p>− Converter cost: $ 2000 (service period: 15 years, efficiency = 90%).</p><p>− Battery bank cost: $ 60,000.</p><p>− Cost of solar panels (installation included): $ 6000.</p><p>− Average annual wind speed: 7.51 m/s (top of building).</p><p>− Average solar radiation: 4.64 kWh/m<sup>2</sup>/day.</p><p>− Building coordinates: Latitude: 23˚32' (South); Longitude: 46˚38' (West).</p><p>− Annual average temperature: 20.1˚C.</p><p>− Annual interest rate: 6%.</p></sec><sec id="s3"><title>3. Simulation of the Case under Analysis</title><p>The simulations were performed using the HOMER Legacy v2.68 beta program [<xref ref-type="bibr" rid="scirp.90712-ref20">20</xref>] , [<xref ref-type="bibr" rid="scirp.90712-ref21">21</xref>] . In Cases 1, 2 and Case 3 (sensitivity analysis) the following variables were analysed:</p><p>− Net Present Cost (NPC), which is a well-known method used to assess the viability of a certain project. Succinctly, it results of the difference between the investment value of an asset and the amount that will be redeemed at the end of the investment, brought to present value ($).</p><p>− Levelized Cost of Energy (LCOE), which refers to the unit net cost due to installation of a power source (renewable or non-renewable) divided by the energy produced over its expected life-time ($/kWh).</p><p>These variables, together with the CO<sub>2</sub> emissions of each of the alternatives analysed are indicators on the building’s viability to operate as a partially self-fed building. It will also be evaluated the energy generated by the renewable sources and the diesel generator to compute the cost that this energy represents if sold back to the grid.</p><sec id="s3_1"><title>3.1. Supply of Power Exclusively from the Utility (Case 1)</title><p>All the energy is exclusively supplied by the utility (see <xref ref-type="table" rid="table1">Table 1</xref>). The NPC value is equal to $ 4,372,648. On the other hand, the LCOE (global unit cost of energy) is equal to $ 0.100/kWh. The overall operation cost for this case is equal to $. 676,446/year.</p><p>The periods of tariff application by the utility along the day are shown in <xref ref-type="fig" rid="fig2">Figure 2</xref>. The period of peak tariff is shown in green colour whereas the off-peak period is shown in yellow colour.</p></sec><sec id="s3_2"><title>3.2. Power Supplied by the Utility and the Sources within the Building (Case 2)</title><p><xref ref-type="fig" rid="fig3">Figure 3</xref> corresponds to the simulated system presented in <xref ref-type="fig" rid="fig1">Figure 1</xref>. Note that the inclusion of the dc/dc converter linking the solar panel to the local generation (shown in <xref ref-type="fig" rid="fig1">Figure 1</xref>) is optional. In this case, it was not included.</p><table-wrap id="table1" ><label><xref ref-type="table" rid="table1">Table 1</xref></label><caption><title> Energy purchase from the grid</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Component</th><th align="center" valign="middle" >Production (kWh/yr)</th><th align="center" valign="middle" >Fraction (%)</th></tr></thead><tr><td align="center" valign="middle" >Grid purchase</td><td align="center" valign="middle" >6,789,000</td><td align="center" valign="middle" >100</td></tr></tbody></table></table-wrap><p><xref ref-type="fig" rid="fig4">Figure 4</xref> shows the daily load curve specified in the simulation tool. It should be noted that (for the sake of comparison) such a load curve will be the same used in all the three analysed cases. Thus, including the load curve of Case 1 and Case 3 would be redundant. The result of this simulation (i.e. Case 2) is shown in <xref ref-type="fig" rid="fig5">Figure 5</xref>.</p><p>Because the generation sources are relatively small in relation to the demand of the building, the utility will be supplying most of the demanded energy (blue columns). The diesel and wind generators (black and green colours respectively) contribute with less energy. The small PV solar generation (yellow colour), which practically does not appear in the graph, will also be contributing to supply power to the building.</p><p><xref ref-type="table" rid="table2">Table 2</xref> shows how the generation of the different components behaves in cumulative terms. In this case, a greater contribution of power production by the utility, followed by the wind and diesel systems, can be observed. Although the diesel generator has a higher capacity than the wind turbine, the software gives priority to the contribution of the renewable sources.</p><p>The energy produced by the local sources (E<sub>LS</sub>) will be (sum of the first three rows shown in <xref ref-type="table" rid="table2">Table 2</xref>):</p><p>E L S = ( 4149 + 688 ， 002 + 686 ， 493 ) = 1 ， 378 ， 644 ( kWh / yr ) (1)</p><p>The characteristics of each source during the power production is shown in Tables 3-6. For example, <xref ref-type="table" rid="table3">Table 3</xref> shows that the PV array has the lowest capacity factor equal to 15.8% and it also has the least energy contribution to the load (4000 kW-h/yr). This is because its rated power has only 3 kW. The wind generation (<xref ref-type="table" rid="table4">Table 4</xref>) presents a better scenario with more than 52% of capacity factor and a much greater annual production (i.e. 688,000 kW/yr), although its rated capacity, compared to the PV array, is also greater (150 kW). Due to the issues above explained, mainly the generation cost, the diesel generator presents a low capacity factor (17.4%) with only 4745 hr/yr of operation.</p><p>The first column in <xref ref-type="table" rid="table6">Table 6</xref> shows the global energy purchased from the utility, the second column represents the energy generated by the local sources which will be compensated (i.e. subtracted) from the first column. Thus, the commercial building will only pay the “net” energy purchased shown in the third column. It can also be observed the total (annual) energy and demand charges; the former calculated considering the net purchase of energy.</p><table-wrap id="table2" ><label><xref ref-type="table" rid="table2">Table 2</xref></label><caption><title> Participation of the generation components</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Component</th><th align="center" valign="middle" >Production (kWh/yr)</th><th align="center" valign="middle" >Fraction (%)</th></tr></thead><tr><td align="center" valign="middle" >PV array</td><td align="center" valign="middle" >4149</td><td align="center" valign="middle" >0</td></tr><tr><td align="center" valign="middle" >Wind turbines</td><td align="center" valign="middle" >688,002</td><td align="center" valign="middle" >10</td></tr><tr><td align="center" valign="middle" >Diesel_1</td><td align="center" valign="middle" >686,493</td><td align="center" valign="middle" >10</td></tr><tr><td align="center" valign="middle" >Grid purchase</td><td align="center" valign="middle" >5,218,002</td><td align="center" valign="middle" >79</td></tr><tr><td align="center" valign="middle" >Total</td><td align="center" valign="middle" >6,596,647</td><td align="center" valign="middle" >100</td></tr></tbody></table></table-wrap><table-wrap id="table3" ><label><xref ref-type="table" rid="table3">Table 3</xref></label><caption><title> Characteristics of the PV array</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Quantity</th><th align="center" valign="middle" >Value</th><th align="center" valign="middle" >Units</th></tr></thead><tr><td align="center" valign="middle" >Rated capacity</td><td align="center" valign="middle" >3.00</td><td align="center" valign="middle" >kW</td></tr><tr><td align="center" valign="middle" >Mean output</td><td align="center" valign="middle" >0.474</td><td align="center" valign="middle" >kW</td></tr><tr><td align="center" valign="middle" >Mean output</td><td align="center" valign="middle" >11.4</td><td align="center" valign="middle" >kWh/d</td></tr><tr><td align="center" valign="middle" >Capacity factor</td><td align="center" valign="middle" >15.8</td><td align="center" valign="middle" >%</td></tr><tr><td align="center" valign="middle" >Total production</td><td align="center" valign="middle" >4149</td><td align="center" valign="middle" >kWh/yr</td></tr></tbody></table></table-wrap><table-wrap id="table4" ><label><xref ref-type="table" rid="table4">Table 4</xref></label><caption><title> Characteristics of the wind generator</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Variable</th><th align="center" valign="middle" >Value</th><th align="center" valign="middle" >Units</th></tr></thead><tr><td align="center" valign="middle" >Total rated capacity</td><td align="center" valign="middle" >150</td><td align="center" valign="middle" >kW</td></tr><tr><td align="center" valign="middle" >Mean output</td><td align="center" valign="middle" >78.5</td><td align="center" valign="middle" >kW</td></tr><tr><td align="center" valign="middle" >Capacity factor</td><td align="center" valign="middle" >52.4</td><td align="center" valign="middle" >%</td></tr><tr><td align="center" valign="middle" >Total production</td><td align="center" valign="middle" >688,002</td><td align="center" valign="middle" >kWh/yr</td></tr></tbody></table></table-wrap><table-wrap id="table5" ><label><xref ref-type="table" rid="table5">Table 5</xref></label><caption><title> Characteristics of the diesel generator</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Quantity</th><th align="center" valign="middle" >Value</th><th align="center" valign="middle" >Units</th></tr></thead><tr><td align="center" valign="middle" >Hours of operation</td><td align="center" valign="middle" >4745</td><td align="center" valign="middle" >hr/yr</td></tr><tr><td align="center" valign="middle" >Number of starts</td><td align="center" valign="middle" >365</td><td align="center" valign="middle" >starts/yr</td></tr><tr><td align="center" valign="middle" >Operational life</td><td align="center" valign="middle" >3.16</td><td align="center" valign="middle" >yr</td></tr><tr><td align="center" valign="middle" >Capacity factor</td><td align="center" valign="middle" >17.4</td><td align="center" valign="middle" >%</td></tr><tr><td align="center" valign="middle" >Fixed generation cost</td><td align="center" valign="middle" >34.4</td><td align="center" valign="middle" >$/hr</td></tr><tr><td align="center" valign="middle" >Marginal generation cost</td><td align="center" valign="middle" >0.218</td><td align="center" valign="middle" >$/kWhyr</td></tr></tbody></table></table-wrap><table-wrap id="table6" ><label><xref ref-type="table" rid="table6">Table 6</xref></label><caption><title> Total (annual)energy purchased and sold plus the demand and energy charge</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Energy purchased (kWh)</th><th align="center" valign="middle" >Energy sold (kWh)</th><th align="center" valign="middle" >Net purchases (kWh)</th><th align="center" valign="middle" >Peak demand (kW)</th><th align="center" valign="middle" >Energy charge ($)</th><th align="center" valign="middle" >Demand charge ($)</th></tr></thead><tr><td align="center" valign="middle" >5,218,002</td><td align="center" valign="middle" >26,231</td><td align="center" valign="middle" >5,191,771</td><td align="center" valign="middle" >1400</td><td align="center" valign="middle" >430,686</td><td align="center" valign="middle" >99,466</td></tr></tbody></table></table-wrap><p>The “base case” condition is when the diesel price is equal to 0.873 US$/L and the wind speed equal to 7.51 m/s. Because these variables are global evaluation factors of the project, the NPC and LCOE variables will also be observed for these conditions.</p><p>For this (base case) condition, the NPC = $ 6,499,677; the LCOE = 0.153 $/kWh, and the cost of operation = 872,841 $/year.</p><p>In <xref ref-type="table" rid="table7">Table 7</xref>, a comparison of the main economic variables and the CO<sub>2</sub> emissions of both cases is presented. Note that Case 2 has got greater values than Case 1; this is due to the capital cost of the generation sources included to which it can be added the price of the fuel.</p></sec><sec id="s3_3"><title>3.3. Sensitivity Analysis (Case 3)</title><p>The objective to perform a sensitivity analysis is that in situations where there are hypothetical variables, or variables prone to variations, there will be certain degree of uncertainty in the system, thus, a sensitivity analysis is needed.</p><p>During the sensitivity analysis performed in the HOMER program, for any variable used it is inserted a range of values that are believed will vary. Examples of these variables can be, the energy price, fuel price, interest rate, life span of the PV array, average wind speed, average connected load, etc. Also, it is common to estimate the useful life of equipment and assume that, for example, the price of</p><table-wrap id="table7" ><label><xref ref-type="table" rid="table7">Table 7</xref></label><caption><title> Comparison of the main variables between Cases 1 and 2</title></caption><table><tbody><thead><tr><th align="center" valign="middle" ></th><th align="center" valign="middle" >NPC (US$/yr)</th><th align="center" valign="middle" >LCOE (US$/kWh)</th><th align="center" valign="middle" >Operation cost (US$/yr)</th><th align="center" valign="middle" >CO<sub>2</sub> emissions (kg/yr)</th></tr></thead><tr><td align="center" valign="middle" >Case 1</td><td align="center" valign="middle" >4,372,648</td><td align="center" valign="middle" >0.10</td><td align="center" valign="middle" >676,446</td><td align="center" valign="middle" >4,290,648</td></tr><tr><td align="center" valign="middle" >Case 2</td><td align="center" valign="middle" >6,499,677</td><td align="center" valign="middle" >0.153</td><td align="center" valign="middle" >872,841</td><td align="center" valign="middle" >4,182,966</td></tr><tr><td align="center" valign="middle" >Difference</td><td align="center" valign="middle" >2127,029</td><td align="center" valign="middle" >0.053</td><td align="center" valign="middle" >196,395</td><td align="center" valign="middle" >107,682</td></tr></tbody></table></table-wrap><p>fuel will not change over this period. There is obviously substantial uncertainty in considering this hypothesis, which might not reflect in a real manner the analysis performed and the project scenario.</p><p>The sensitivity analysis was performed for Case 2 (i.e. building fed by the utility and the local sources) for which two additional cases were considered:</p><p>− Higher wind speed and lower diesel price.</p><p>− Lower wind speed and higher diesel price.</p><sec id="s3_3_1"><title>3.3.1. Sensitivity Considering a Higher Wind Speed and Lower Diesel Price</title><p>A drop in the diesel price to 0.75 $/L and an increase in the wind speed (8.5 m/s) was in this case applied. In <xref ref-type="fig" rid="fig6">Figure 6</xref> and <xref ref-type="fig" rid="fig7">Figure 7</xref> the behaviour of the base case is represented through the crossed blue lines inside each window. It can be observed that both the NPC and LCOE are highly sensitive to the fuel price (higher slope) and to a lesser extent to the wind speed.</p><p>In <xref ref-type="table" rid="table8">Table 8</xref>, the power production of the different components is shown. Note that an increase in the wind speed makes the wind generator to produce more energy.</p><p>The total power produced by the local sources will be:</p><p>E L S = ( 4149 + 892 ， 810 + 674 ， 048 ) = 1 ， 571 ， 007 ( kWh / yr ) (2)</p><p>The quantities corresponding to the PV array did not change. This is because it has not been accounted in the sensitivity analysis. The reason is that its installed capacity is relatively small, thus, little change would produce in the whole power production.</p><p>The mean output power and the capacity factor of the wind generator are shown in <xref ref-type="table" rid="table9">Table 9</xref>. In <xref ref-type="table" rid="table1">Table 1</xref>0, the main operative characteristics of the diesel generator are shown.</p><p>The energy purchased from the utility and the net energy sold by the building, as well as the demand and energy charges are presented in <xref ref-type="table" rid="table1">Table 1</xref>1.</p><p>In this case, due to the lower fuel price the diesel generator operates at a daily basis (i.e. it is more used) operating approximately 50% (4745/8760) of the time along the year. It was not included the case when simultaneously the wind speed and the fuel price increase as the simulation toll would obviously give priority to the wind generator.</p><table-wrap id="table8" ><label><xref ref-type="table" rid="table8">Table 8</xref></label><caption><title> Power production of the various sources. Increase in the wind speed</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Component</th><th align="center" valign="middle" >Production (kWh/yr)</th><th align="center" valign="middle" >Fraction (%)</th></tr></thead><tr><td align="center" valign="middle" >PV array</td><td align="center" valign="middle" >4149</td><td align="center" valign="middle" >0%</td></tr><tr><td align="center" valign="middle" >Wind turbines</td><td align="center" valign="middle" >892,810</td><td align="center" valign="middle" >13%</td></tr><tr><td align="center" valign="middle" >Diesel_1</td><td align="center" valign="middle" >674,048</td><td align="center" valign="middle" >10%</td></tr><tr><td align="center" valign="middle" >Grid purchase</td><td align="center" valign="middle" >5,063,325</td><td align="center" valign="middle" >76%</td></tr><tr><td align="center" valign="middle" >Total</td><td align="center" valign="middle" >6,634,331</td><td align="center" valign="middle" >100%</td></tr></tbody></table></table-wrap><table-wrap id="table9" ><label><xref ref-type="table" rid="table9">Table 9</xref></label><caption><title> Characteristics of the wind generator during its operation</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Variable</th><th align="center" valign="middle" >Value</th><th align="center" valign="middle" >Units</th></tr></thead><tr><td align="center" valign="middle" >Total rated capacity</td><td align="center" valign="middle" >150</td><td align="center" valign="middle" >kW</td></tr><tr><td align="center" valign="middle" >Mean output</td><td align="center" valign="middle" >102</td><td align="center" valign="middle" >kW</td></tr><tr><td align="center" valign="middle" >Capacity factor</td><td align="center" valign="middle" >67.9</td><td align="center" valign="middle" >%</td></tr></tbody></table></table-wrap><table-wrap id="table10" ><label><xref ref-type="table" rid="table1">Table 1</xref>0</label><caption><title> Characteristics of the diesel generator during its operation</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Quantity</th><th align="center" valign="middle" >Value</th><th align="center" valign="middle" >Units</th></tr></thead><tr><td align="center" valign="middle" >Hours of operation</td><td align="center" valign="middle" >4745</td><td align="center" valign="middle" >hr/yr</td></tr><tr><td align="center" valign="middle" >Number of starts</td><td align="center" valign="middle" >365</td><td align="center" valign="middle" >starts/yr</td></tr><tr><td align="center" valign="middle" >Operational life</td><td align="center" valign="middle" >3.16</td><td align="center" valign="middle" >yr</td></tr><tr><td align="center" valign="middle" >Capacity factor</td><td align="center" valign="middle" >17.1</td><td align="center" valign="middle" >%</td></tr><tr><td align="center" valign="middle" >Fixed generation cost</td><td align="center" valign="middle" >30.0</td><td align="center" valign="middle" >$/hr</td></tr><tr><td align="center" valign="middle" >Marginal generation cost</td><td align="center" valign="middle" >0.188</td><td align="center" valign="middle" >$/kWhyr</td></tr></tbody></table></table-wrap><table-wrap id="table11" ><label><xref ref-type="table" rid="table1">Table 1</xref>1</label><caption><title> Energy purchased and sold by the local sources</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Energy purchased (kWh)</th><th align="center" valign="middle" >Energy sold (kWh)</th><th align="center" valign="middle" >Net purchases (kWh)</th><th align="center" valign="middle" >Peak demand (kW)</th><th align="center" valign="middle" >Energy charge ($)</th><th align="center" valign="middle" >Demand charge ($)</th></tr></thead><tr><td align="center" valign="middle" >5,063,325</td><td align="center" valign="middle" >63,916</td><td align="center" valign="middle" >4,999,409</td><td align="center" valign="middle" >1400</td><td align="center" valign="middle" >415,536</td><td align="center" valign="middle" >99,046</td></tr></tbody></table></table-wrap></sec><sec id="s3_3_2"><title>3.3.2. Sensitivity Considering Lower Wind Speed and Higher Diesel Price</title><p>Under this condition, a reduction of the wind speed to 6.5 m/s and an increase in the diesel price to 0.95 $/L, occurs. Analogously, the values of the NPC and LCOE relative to the best estimate are also shown in <xref ref-type="fig" rid="fig6">Figure 6</xref> and <xref ref-type="fig" rid="fig7">Figure 7</xref>.</p><p>In <xref ref-type="table" rid="table1">Table 1</xref>2, it can be observed that due to the increase in fuel price, the diesel generator reduces its power production in relation to the previous case.</p><p>The total power produced by the local sources will be (<xref ref-type="table" rid="table1">Table 1</xref>2):</p><p>E L S = ( 4149 + 468 ， 585 + 702 ， 214 ) = 1 ， 174 ， 971 ( kWh / yr ) (3)</p><p>Features like the mean output and the capacity factor of the wind generator are shown in <xref ref-type="table" rid="table1">Table 1</xref>3. In <xref ref-type="table" rid="table1">Table 1</xref>4, the main operative characteristics of the diesel generator are shown.</p><p>For this case, the energy purchased from the utility and the net energy sold by the building, as well as the demand and energy charges are presented in <xref ref-type="table" rid="table1">Table 1</xref>5.</p><p>A synthesis of the total energy produced by the local sources presented in <xref ref-type="table" rid="table2">Table 2</xref>, <xref ref-type="table" rid="table8">Table 8</xref> and <xref ref-type="table" rid="table1">Table 1</xref>2, as well as the CO<sub>2</sub> emissions, is presented in <xref ref-type="table" rid="table1">Table 1</xref>6.</p><p>The result of the sensitivity analysis considering a drop in the diesel price to 0.75 $/L and an increase in the wind speed (8.5 m/s) can also be seen in <xref ref-type="fig" rid="fig6">Figure 6</xref> and <xref ref-type="fig" rid="fig7">Figure 7</xref> (green lines). The analysis of these variations will be presented in the next section. Note that with the diesel price becoming higher (i.e. blue line shifted to the left side until it rides the red line) the value relative to the best estimate worsens (decreases) which increases the diesel NPC . A similar behaviour occurs in the case of the wind generation NPC.</p><p>Conversely, if the diesel price becomes lower (i.e. blue line is shifted to the right side until it rides the green line) the value relative to the best estimate rises  decreasing the diesel’s NPC. This behaviour also occurs in the case of the wind generation NPC.</p><p>A similar behaviour occurs in the case of the LCOE in which the “best estimate value” decreases if the diesel price increases . Conversely, this value improves if the diesel price falls .</p><table-wrap id="table12" ><label><xref ref-type="table" rid="table1">Table 1</xref>2</label><caption><title> Power production of the various sources. Increase in the diesel price</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Component</th><th align="center" valign="middle" >Production (kWh/yr)</th><th align="center" valign="middle" >Fraction (%)</th></tr></thead><tr><td align="center" valign="middle" >PV array</td><td align="center" valign="middle" >4149</td><td align="center" valign="middle" >0%</td></tr><tr><td align="center" valign="middle" >Wind turbines</td><td align="center" valign="middle" >468,585</td><td align="center" valign="middle" >7%</td></tr><tr><td align="center" valign="middle" >Diesel_1</td><td align="center" valign="middle" >702,214</td><td align="center" valign="middle" >11%</td></tr><tr><td align="center" valign="middle" >Grid purchase</td><td align="center" valign="middle" >5,399,972</td><td align="center" valign="middle" >82%</td></tr><tr><td align="center" valign="middle" >Total</td><td align="center" valign="middle" >6,574,919</td><td align="center" valign="middle" >100%</td></tr></tbody></table></table-wrap><table-wrap id="table13" ><label><xref ref-type="table" rid="table1">Table 1</xref>3</label><caption><title> Characteristics of the wind generator during its operation</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Variable</th><th align="center" valign="middle" >Value</th><th align="center" valign="middle" >Units</th></tr></thead><tr><td align="center" valign="middle" >Total rated capacity</td><td align="center" valign="middle" >150</td><td align="center" valign="middle" >kW</td></tr><tr><td align="center" valign="middle" >Mean output</td><td align="center" valign="middle" >53.5</td><td align="center" valign="middle" >kW</td></tr><tr><td align="center" valign="middle" >Capacity factor</td><td align="center" valign="middle" >35.7</td><td align="center" valign="middle" >%</td></tr></tbody></table></table-wrap><table-wrap id="table14" ><label><xref ref-type="table" rid="table1">Table 1</xref>4</label><caption><title> Characteristics of the diesel generator during its operation</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Quantity</th><th align="center" valign="middle" >Value</th><th align="center" valign="middle" >Units</th></tr></thead><tr><td align="center" valign="middle" >Hours of operation</td><td align="center" valign="middle" >4745</td><td align="center" valign="middle" >hr/yr</td></tr><tr><td align="center" valign="middle" >Number of starts</td><td align="center" valign="middle" >365</td><td align="center" valign="middle" >starts/yr</td></tr><tr><td align="center" valign="middle" >Operational life</td><td align="center" valign="middle" >3.16</td><td align="center" valign="middle" >yr</td></tr><tr><td align="center" valign="middle" >Capacity factor</td><td align="center" valign="middle" >17.8</td><td align="center" valign="middle" >%</td></tr><tr><td align="center" valign="middle" >Fixed generation cost</td><td align="center" valign="middle" >37.2</td><td align="center" valign="middle" >$/hr</td></tr><tr><td align="center" valign="middle" >Marginal generation cost</td><td align="center" valign="middle" >0.237</td><td align="center" valign="middle" >$/kWhyr</td></tr></tbody></table></table-wrap><table-wrap id="table15" ><label><xref ref-type="table" rid="table1">Table 1</xref>5</label><caption><title> Energy purchased and sold by the local sources</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Energy purchased (kWh)</th><th align="center" valign="middle" >Energy sold (kWh)</th><th align="center" valign="middle" >Net purchases (kWh)</th><th align="center" valign="middle" >Peak demand (kW)</th><th align="center" valign="middle" >Energy charge ($)</th><th align="center" valign="middle" >Demand charge ($)</th></tr></thead><tr><td align="center" valign="middle" >5,399,972</td><td align="center" valign="middle" >4503</td><td align="center" valign="middle" >5,395,468</td><td align="center" valign="middle" >1400</td><td align="center" valign="middle" >446,763</td><td align="center" valign="middle" >99,724</td></tr></tbody></table></table-wrap><table-wrap id="table16" ><label><xref ref-type="table" rid="table1">Table 1</xref>6</label><caption><title> Total energy produced by the local sources in each case (comparison)</title></caption><table><tbody><thead><tr><th align="center" valign="middle" ></th><th align="center" valign="middle" >E<sub>LS</sub> (kWh/yr)</th><th align="center" valign="middle" >CO<sub>2</sub> emissions (kg/yr)</th></tr></thead><tr><td align="center" valign="middle" >Case 2 (utility + sources)</td><td align="center" valign="middle" >1,378,644</td><td align="center" valign="middle" >4,182,966</td></tr><tr><td align="center" valign="middle" >Case 3 (sensitivity 1)</td><td align="center" valign="middle" >1,571,007</td><td align="center" valign="middle" >4,322,052</td></tr><tr><td align="center" valign="middle" >Case 3 (sensitivity 2)</td><td align="center" valign="middle" >1,174,971</td><td align="center" valign="middle" >4,053,199</td></tr></tbody></table></table-wrap></sec></sec></sec><sec id="s4"><title>4. Commercial Building Participating in Demand Response Programs</title><p>This analysis was conducted considering some hypotheses, namely:</p><p>Case 2. (Section 3.2)</p><p>If the energy generated by the local sources is injected into the grid by the battery during the period 17:00 - 21:00 (peak period), the price at which the energy is sold, according to the spot price (the ratio between the maximum spot price and the peak period price is 1.28), would be (kWh/yr taken from <xref ref-type="table" rid="table1">Table 1</xref>6):</p><p>C s e l l - b a c k = ( 1 ， 378 , 644   kWh / yr &#215; 0.1   $ / kWh &#215; 1.28 ) = 176 ， 466   $ / yr (4)</p><p>This would be the revenue value due to the local sources and could represent approximately 40% of the building’s annual cost (i.e. 176,466/430,686 = 0.40). This value is related entirely to the energy cost ($. 430,686/yr) presented in <xref ref-type="table" rid="table6">Table 6</xref>. Note that the demand cost is not being considered here.</p><p>Indeed, this condition is subject to an agreement reached between the utility and the government to encourage the contribution of end-users.</p><p>Case 3. Recall that this case explores two conditions:</p><p>1) Section 3.3.1</p><p>An increase in the wind speed and a drop in the diesel price was previously established for this case. Thus, by the same philosophy as in Case 2, the sell-back cost will be:</p><p>C s e l l - b a c k = ( 1 ， 571 ， 007   kWh / yr &#215; 0.1   $ / kWh &#215; 1.28 ) = 201 ， 089   $ / yr (5)</p><p>This sell-back value represents approximately 48.4% of compensating profit in relation to the energy charge presented in <xref ref-type="table" rid="table1">Table 1</xref>1.</p><p>2) Section 3.3.2</p><p>Analogously, in the second case of sensitivity (i.e. lower wind speed and higher diesel price) the sell-back value will be $ 150,396/yr, which represents approximately 33.66% of compensating profit in relation to the energy charge presented in <xref ref-type="table" rid="table1">Table 1</xref>5. Note that the sell-back cost is more sensitive to the wind speed than to the diesel price.</p></sec><sec id="s5"><title>5. Discussion</title><p>In the above example, the PV source is relatively small. This is because its size is limited by the available area of the building’s roof. However, its minor contribution to the analysed costs, together with the contribution of the wind generators, made the difference in relation to Case 1.</p><p>Also, since the analysed building requires a relatively high degree of power availability and reliability (i.e. it can be the case of a shopping mall) a diesel genset was included. The impact of its acquisition and operational costs was partly offset by the renewable sources that have a null fuel cost.</p><p>In some countries, the application of the microgrid technology and the smart building technology is currently leveraged by some government incentives in the electric sector. This is the case of the Brazilian ProGD (Program for the Development of Distributed Generation) whose aim is to broaden and deepen the actions to stimulate the power generation by the consumers, as long as it is based on renewable sources, especially solar power. Another similar incentive in the country is PROINFA (Program for the Incentive of Alternative Sources) that promotes the participation of alternative sources (e.g. wind power, biomass, and small hydropower plants) within the National Interconnected System. Other areas such as the construction and architecture have also some incentives for the construction of smart buildings; however, there is still a relatively long way to run before the application of this technology becomes mandatory to attain significant benefits for the environment.</p></sec><sec id="s6"><title>6. Conclusions</title><p>Moderate investments in generation sources in a building, in either renewable sources or those based on fossil fuels, may bring revenues proportional to the investment, which, in a medium term (i.e., a period less than the service life of the assets) can become significant.</p><p>The overall annual cost of the system (NPC) and LCOE is highly sensitive to the variation of the fuel price and, to a lesser degree, to wind speed variations. Hence, investment in renewable generation sources would be more advantageous for this purpose.</p><p>The article shows in a straight manner the procedures and data required (for a specific simulation program) to assess the technical and economic impact of the sources contained in a building. Some features characterizing a building as smart, are described here. Along the research conducted, it was observed the lack of some general guidelines and standards to build up new buildings, or to convert conventional ones into smart structures, this should be the next challenge for the scientific community.</p></sec><sec id="s7"><title>Acknowledgements</title><p>The authors would like to thank the Department of Energy Engineering and Electrical Automation of the University of S&#227;o Paulo for the chance to carry out this research.</p></sec><sec id="s8"><title>Conflicts of Interest</title><p>The authors declare no conflicts of interest regarding the publication of this paper.</p></sec><sec id="s9"><title>Cite this paper</title><p>Del Carpio-Huayllas, T.E., Ramos, D.S. and Vasquez-Arnez, R.L. (2019) Commercial Building Containing Generation Sources: A Technical and Economic Assessment and Its Potential to Participate in Demand Response Programs. Energy and Power Engineering, 11, 76-91. https://doi.org/10.4236/epe.2019.112005</p></sec></body><back><ref-list><title>References</title><ref id="scirp.90712-ref1"><label>1</label><mixed-citation publication-type="other" xlink:type="simple">Eid, Ch., Koliou, E., Valles, M., Reneses, J. and Hakvoort, R. (2016) Time-Based Pricing and Electricity Demand Response: Existing Barriers and Next Steps. Utilities Policy, 40, 15-25. https://doi.org/10.1016/j.jup.2016.04.001 
https://www.sciencedirect.com/science/article/pii/S0957178716300947</mixed-citation></ref><ref id="scirp.90712-ref2"><label>2</label><mixed-citation publication-type="other" xlink:type="simple">Baboli, P.T., Moghaddam, M.P. and Eghbal, M. (2011) Present Status and Future Trends in Enabling Demand Response Programs. IEEE Power and Energy Society, General Meeting, San Diego, CA, 24-29 July 2011, 1-6.  
https://doi.org/10.1109/PES.2011.6039608</mixed-citation></ref><ref id="scirp.90712-ref3"><label>3</label><mixed-citation publication-type="other" xlink:type="simple">Wang, F., Xu, H.C., Ti, Xu, T., Li, K.P., Shafie-khah, M. and Catal&amp;atilde;o, J.P.S. (2017) The Values of Market-Based Demand Response on Improving Power System Reliability under Extreme Circumstances. Applied Energy, 193, 220-231.  
https://www.sciencedirect.com/science/article/pii/S0306261917300971</mixed-citation></ref><ref id="scirp.90712-ref4"><label>4</label><mixed-citation publication-type="other" xlink:type="simple">Hopkins, A.S. and Whited, M. (2017) Best Practices in Utility Demand Response Programs. http://www.synapse-energy.com/project/best-practices-utility-demand-response-programs</mixed-citation></ref><ref id="scirp.90712-ref5"><label>5</label><mixed-citation publication-type="other" xlink:type="simple">Albadi, M.H. and E1-Saadany, E.F. (2007) Demand Response in Electricity Markets: An Overview. IEEE Power Engineering Society, General Meeting, Tampa, FL, 24-28 June 2007, 1-5. https://doi.org/10.1109/PES.2007.385728</mixed-citation></ref><ref id="scirp.90712-ref6"><label>6</label><mixed-citation publication-type="other" xlink:type="simple">Mohajeryami, S., Moghaddam, I.N., Doostan, M., Vatani, B. and Peter Schwarz, P. (2016) A Novel Economic Model for Price-Based Demand Response. Electric Power Systems Research, 135, 1-9. https://doi.org/10.1016/j.epsr.2016.03.026</mixed-citation></ref><ref id="scirp.90712-ref7"><label>7</label><mixed-citation publication-type="other" xlink:type="simple">Faria, P., Spinola, J. and Vale, Z. (2017) Identified Short and Real-Time Demand Response Opportunities in the Corresponding Requirements and Concise Systematization of the Conceived and Develop. Dram GO, Horizon 2020, European Commission. 41. http://dream-go.ipp.pt/PDF/DREAM-GO_Deliverable2.1.pdf</mixed-citation></ref><ref id="scirp.90712-ref8"><label>8</label><mixed-citation publication-type="other" xlink:type="simple">European Commission DG Energy (2016) Impact Assessment Study on Downstream Flexibility, Price Flexibility, Demand Response &amp; Smart Metering. Final Report, Belgium.  
https://ec.europa.eu/energy/en/studies/impact-assessment-study-downstream-flexibility-price-flexibility-demand-response-smart</mixed-citation></ref><ref id="scirp.90712-ref9"><label>9</label><mixed-citation publication-type="other" xlink:type="simple">Smart Energy Demand Coalition—SEDC (2017) Explicit Demand Response in Europe, Mapping the Markets 2017. Brussels, Abril.  
http://www.smarten.eu/wp-content/uploads/2017/04/SEDC-Explicit-Demand-Response-in-Europe-Mapping-the-Markets-2017.pdf</mixed-citation></ref><ref id="scirp.90712-ref10"><label>10</label><mixed-citation publication-type="other" xlink:type="simple">Neves, D., Pina, A. and Silva, C.A. (2015) Demand Response Modeling: A Comparison between Tools. Applied Energy, 146, 288-297.  
https://doi.org/10.1016/j.apenergy.2015.02.057</mixed-citation></ref><ref id="scirp.90712-ref11"><label>11</label><mixed-citation publication-type="other" xlink:type="simple">Watson, D.S., Kiliccote, S., Motegi, N.M. and Piette, M.A. (2006) Strategies for Demand Response in Commercial Buildings. Proceedings of the 2006 ACEEE Summer Study on Energy Efficiency in Buildings, Pacific Grove, CA, 13-18 August 2006, 1-14.</mixed-citation></ref><ref id="scirp.90712-ref12"><label>12</label><mixed-citation publication-type="other" xlink:type="simple">Mutule, A., Obushev, A., Grebesh, E. and Lvovs, A. (2017) Feasibility Study for Demand Response in Commercial Buildings. Proceedings of the 9th International Scientific Symposium on Electrical Power Engineering, Slovakia, StaráLesná, 12-14 Sep-tember 2017, 1-7.</mixed-citation></ref><ref id="scirp.90712-ref13"><label>13</label><mixed-citation publication-type="other" xlink:type="simple">Kjaergaard, T., Arendt, M.B., Clausen, K., Johansen, A., Jradi, A., Jorgensen, M. and Wollsen, B.N. (2016) Demand Response in Commercial Buildings with an Assessable Impact on Occupant Comfort. 2016 IEEE International Conference on Smart Grid Communications, Sydney, NSW, 6-9 November 2016, 1-6.</mixed-citation></ref><ref id="scirp.90712-ref14"><label>14</label><mixed-citation publication-type="other" xlink:type="simple">Bobrova, D. (2015) Building-Integrated Wind Turbines in the Aspect of Architectural Shaping. Procedia Engineering, 117, 404-410.  
https://doi.org/10.1016/j.proeng.2015.08.185</mixed-citation></ref><ref id="scirp.90712-ref15"><label>15</label><mixed-citation publication-type="other" xlink:type="simple">The Council on Tall Buildings and Urban Habitat, Al Bahar Towers, Abu Dhabi.  
https://freshome.com/2012/12/24/intelligent-shading-system-showcased-by-abu-dhabis-al-bahar-towers/</mixed-citation></ref><ref id="scirp.90712-ref16"><label>16</label><mixed-citation publication-type="other" xlink:type="simple">Wurtz, F. and Delinchant, B. (2017) Smart Buildings Integrated in Smart Grids: A Key Challenge for the Energy Transition by Using Physical Models and Optimization with a Human-in-the-Loop Approach. Comptes Rendus Physique, 18, 428-444.  
https://doi.org/10.1016/j.crhy.2017.09.007</mixed-citation></ref><ref id="scirp.90712-ref17"><label>17</label><mixed-citation publication-type="other" xlink:type="simple">Kaygusuz, A., Keles, C., Alagoz, B.B. and Karabiber, A. (2013) Renewable Energy Integration for Smart Sites. Journal of Energy and Buildings, 64, 456-462.  
https://doi.org/10.1016/j.enbuild.2013.05.031</mixed-citation></ref><ref id="scirp.90712-ref18"><label>18</label><mixed-citation publication-type="other" xlink:type="simple">ClimateTechWiki, Wind Energy: Building-Integrated Turbines, 2018.  
http://www.climatetechwiki.org/technology/building-integrated-wind-turbines</mixed-citation></ref><ref id="scirp.90712-ref19"><label>19</label><mixed-citation publication-type="other" xlink:type="simple">AES Eletropaulo (2018) Electric Energy Tariff. https://www.aeseletropaulo.com.br</mixed-citation></ref><ref id="scirp.90712-ref20"><label>20</label><mixed-citation publication-type="other" xlink:type="simple">HOMER Energy LLC Program, Legacy v2.68 Beta. http://www.homerenergy.com/</mixed-citation></ref><ref id="scirp.90712-ref21"><label>21</label><mixed-citation publication-type="other" xlink:type="simple">Givler, T. and Lilienthal, P. (2005) Using HOMER&lt;sup&gt;&amp;reg;&lt;/sup&gt; Software, NREL’s Micropower Optimization Model to Explore the Role of Gen-Sets in Small Solar Power Systems. Case Study: Sri Lanka. Technical Report, NREL/TP-710-36774.  
https://www.nrel.gov/docs/fy05osti/36774.pdf</mixed-citation></ref></ref-list></back></article>