<?xml version="1.0" encoding="UTF-8"?><!DOCTYPE article  PUBLIC "-//NLM//DTD Journal Publishing DTD v3.0 20080202//EN" "http://dtd.nlm.nih.gov/publishing/3.0/journalpublishing3.dtd"><article xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink" dtd-version="3.0" xml:lang="en" article-type="research article"><front><journal-meta><journal-id journal-id-type="publisher-id">CS</journal-id><journal-title-group><journal-title>Circuits and Systems</journal-title></journal-title-group><issn pub-type="epub">2153-1285</issn><publisher><publisher-name>Scientific Research Publishing</publisher-name></publisher></journal-meta><article-meta><article-id pub-id-type="doi">10.4236/cs.2016.711302</article-id><article-id pub-id-type="publisher-id">CS-70450</article-id><article-categories><subj-group subj-group-type="heading"><subject>Articles</subject></subj-group><subj-group subj-group-type="Discipline-v2"><subject>Computer Science&amp;Communications</subject><subject> Engineering</subject><subject> Physics&amp;Mathematics</subject></subj-group></article-categories><title-group><article-title>
 
 
  Optimum Simultaneous Allocation of Renewable Energy DG and Capacitor Banks in Radial Distribution Network
 
</article-title></title-group><contrib-group><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Sivasangari</surname><given-names>Rajeswaran</given-names></name><xref ref-type="aff" rid="aff1"><sup>1</sup></xref><xref ref-type="corresp" rid="cor1"><sup>*</sup></xref></contrib><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Kamaraj</surname><given-names>Nagappan</given-names></name><xref ref-type="aff" rid="aff2"><sup>2</sup></xref></contrib></contrib-group><aff id="aff2"><addr-line>Thiagarajar College of Engineering, Madurai, India</addr-line></aff><aff id="aff1"><addr-line>AAA College of Engineering and Technology, Sivakasi, India</addr-line></aff><author-notes><corresp id="cor1">* E-mail:<email>sivasangarianand@yahoo.co.in(SR)</email>;</corresp></author-notes><pub-date pub-type="epub"><day>06</day><month>09</month><year>2016</year></pub-date><volume>07</volume><issue>11</issue><fpage>3556</fpage><lpage>3564</lpage><history><date date-type="received"><day>April</day>	<month>23,</month>	<year>2016</year></date><date date-type="rev-recd"><day>Accepted:</day>	<month>May</month>	<year>20,</year>	</date><date date-type="accepted"><day>September</day>	<month>8,</month>	<year>2016</year></date></history><permissions><copyright-statement>&#169; Copyright  2014 by authors and Scientific Research Publishing Inc. </copyright-statement><copyright-year>2014</copyright-year><license><license-p>This work is licensed under the Creative Commons Attribution International License (CC BY). http://creativecommons.org/licenses/by/4.0/</license-p></license></permissions><abstract><p>
 
 
  Nowadays the optimal allocation of distributed generation (DG) in the distribution network becomes the popular research area in restructuring of power system. The capacitor banks introduced in the distribution networks for reactive power compensation also have the capacity to minimize the real and reactive power losses occurred in the system. Hence, this research integrates the allocation of renewable energy DG and capacitor banks in the radial distribution network to minimize the real power loss occurred in the system. A two
  -
  stage methodology is used for simultaneous allocation of renewable DG and capacitor banks. The optimum location of renewable energy DG and capacitor banks is determined using the distributed generation sitting index (DGSI) ranking method and the optimum sizing of DG and capacitor banks is found out for simultaneous placement using weight improved particle swarm optimization algorithm (WIPSO) and self adaptive differential evolution algorithm (SADE).
   
  This two
  -
  stage methodology reduces the burden of SADE and WIPSO algorithm, by using the DGSI index in determining the optimal location. Hence the computational time gets reduced which makes them suitable for online applications. By using the above methodology, a comprehensive performance analysis is done on IEEE 33 bus and 69 bus RDNs and the results are discussed in detail.
 
</p></abstract><kwd-group><kwd>Distributed Generation</kwd><kwd> Capacitor Banks</kwd><kwd> Real Power Loss</kwd><kwd> Radial Distribution Network</kwd><kwd> Distributed Generation Sitting Index</kwd><kwd> WIPSO</kwd><kwd> SADE</kwd></kwd-group></article-meta></front><body><sec id="s1"><title>1. Introduction</title><p>There is an increase in world economy with the increase in load demand which demands the high quality uninterrupted power supply. Due to the ruination of monopoly system and technology advancements, the small scale power generation owners have been able to enter the competitive electricity market with the on-site renewable energy based DG systems [<xref ref-type="bibr" rid="scirp.70450-ref1">1</xref>] . The distributed generation technologies generally include solar photo voltaic, fuel cells, diesel engines and gas turbines (bio mass). The integration of capacitor banks with DG provides the necessary reactive power compensation to the network thereby reducing the line losses in the network. The simultaneous allocation of DG and capacitor banks can lead to an upturn of feeder capacity, reduction in real and reactive power losses, and the voltage profile improvement in radial distribution networks. The optimal simultaneous placement of DG and capacitor is a non-convex problem and thus the attainment of the global optimum solution may be reduced by the local optimum solutions. Due to the discrete nature of the problem, a large number of alternate solutions may be attained which will claim more high computational time. To achieve the optimum allocation of DG for real power loss reduction with multiple constraints the SADE algorithm is applied by VL Huang et al. without presenting any additional parameters [<xref ref-type="bibr" rid="scirp.70450-ref2">2</xref>] . Manafi et al. applied the modified PSO and dynamic PSO as well as improved differential evolution algorithm for optimal allocation of DG in RDN [<xref ref-type="bibr" rid="scirp.70450-ref3">3</xref>] . The objective considered by them was the real power loss minimization with the minimum installed real power DG in RDN. In literature [<xref ref-type="bibr" rid="scirp.70450-ref4">4</xref>] , the results of optimal allocation of DG using PSO with the genetic algorithm were compared. The PSO gave the better characteristic results in terms of solution quality, iteration and time for computation. The PSO for line loss reduction in power system subjected to voltage constraints for optimum placement of DG was performed by Wong et al. [<xref ref-type="bibr" rid="scirp.70450-ref5">5</xref>] . Jagadeesh Gunda et al. (2011) had applied the differential evaluation algorithm (DEA) to determine the optimal location and size of shunt capacitors and DGs in RDN for minimum real power loss on Indian Electricity Board benchmark 25 bus distribution systems [<xref ref-type="bibr" rid="scirp.70450-ref6">6</xref>] . The distributed generations are mainly classified according to the main fuel used. According to the fuel used, it is categorized as renewable energy DG and non-renewable energy DG. The non-renewable DG includes diesel generator, micro turbine, gas turbine etc. The renewable energy DG consists of wind farm, solar photovoltaic system, biomass plants etc. In this paper, for real power loss minimization the solar photovoltaic (SPV) and wind energy based renewable DGs are considered for integration with capacitor banks in RDN. Based on their real and reactive power generation capacity they are modeled as follows [<xref ref-type="bibr" rid="scirp.70450-ref7">7</xref>] - [<xref ref-type="bibr" rid="scirp.70450-ref9">9</xref>] (<xref ref-type="table" rid="table1">Table 1</xref>).</p><p>In this paper two types i.e. (SPV and wind) of renewable energy DG systems are considered for optimal allocation of DG. A two-stage methodology based on distributed</p><table-wrap id="table1" ><label><xref ref-type="table" rid="table1">Table 1</xref></label><caption><title> Types of DG and their modeling</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Type of DG</th><th align="center" valign="middle" >Real power of DG P<sub>DG </sub></th><th align="center" valign="middle" >Reactive power of DG Q<sub>DG </sub></th></tr></thead><tr><td align="center" valign="middle" >Solar photo voltaic cells</td><td align="center" valign="middle" >P<sub>DGi </sub></td><td align="center" valign="middle" >0</td></tr><tr><td align="center" valign="middle" >Wind farm</td><td align="center" valign="middle" >P<sub>DGi</sub></td><td align="center" valign="middle" ><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/11-7601194x2.png" xlink:type="simple"/></inline-formula></td></tr></tbody></table></table-wrap><p>generation sitting index (DGSI) ranking is used for simultaneous allocation of DG and capacitor banks. Initially the DGSI is determined for finding the optimal location of DG. To determine the optimal sizing in the preferred location the WIPSO and SADE algorithms are applied and the obtained results are compared.</p></sec><sec id="s2"><title>2. Problem Formulation</title><p>The objective of the optimization problem is considered as</p><disp-formula id="scirp.70450-formula222"><label>. (1)</label><graphic position="anchor" xlink:href="http://html.scirp.org/file/11-7601194x3.png"  xlink:type="simple"/></disp-formula><p>P<sub>LOSS</sub> is known as</p><disp-formula id="scirp.70450-formula223"><label>. (2)</label><graphic position="anchor" xlink:href="http://html.scirp.org/file/11-7601194x4.png"  xlink:type="simple"/></disp-formula><p>In Equation (2)</p><disp-formula id="scirp.70450-formula224"><label>(3)</label><graphic position="anchor" xlink:href="http://html.scirp.org/file/11-7601194x5.png"  xlink:type="simple"/></disp-formula><disp-formula id="scirp.70450-formula225"><label>(4)</label><graphic position="anchor" xlink:href="http://html.scirp.org/file/11-7601194x6.png"  xlink:type="simple"/></disp-formula><p>P<sub>i</sub> and P<sub>j</sub> are the real power injection in bus i and bus j, respectively.</p><p>Q<sub>i</sub> and Q<sub>j</sub><sub> </sub>are the reactive power injection in bus i and j, respectively.</p><p>R<sub>ij</sub> is the resistance between with i<sup>th</sup> and j<sup>th</sup> bus.</p><p>V<sub>i</sub> and V<sub>j</sub> are the voltage profile at i<sup>th</sup> bus and j<sup>th</sup> bus, respectively.</p><p>δ<sub>i</sub> and δ<sub>j</sub> are the angle of voltage of i<sup>th</sup> bus and j<sup>th</sup> bus, correspondingly.</p><p>For DG insertion</p><disp-formula id="scirp.70450-formula226"><label>(5)</label><graphic position="anchor" xlink:href="http://html.scirp.org/file/11-7601194x7.png"  xlink:type="simple"/></disp-formula><disp-formula id="scirp.70450-formula227"><label>(6)</label><graphic position="anchor" xlink:href="http://html.scirp.org/file/11-7601194x8.png"  xlink:type="simple"/></disp-formula><p>The equality and inequality constraints are as follows.</p><p>Equality Constraints</p><disp-formula id="scirp.70450-formula228"><label>(7)</label><graphic position="anchor" xlink:href="http://html.scirp.org/file/11-7601194x9.png"  xlink:type="simple"/></disp-formula><p>Inequality constraints</p><disp-formula id="scirp.70450-formula229"><graphic  xlink:href="http://html.scirp.org/file/11-7601194x10.png"  xlink:type="simple"/></disp-formula><p>where</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/11-7601194x11.png" xlink:type="simple"/></inline-formula>and <inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/11-7601194x12.png" xlink:type="simple"/></inline-formula></p><disp-formula id="scirp.70450-formula230"><graphic  xlink:href="http://html.scirp.org/file/11-7601194x13.png"  xlink:type="simple"/></disp-formula><p>where</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/11-7601194x14.png" xlink:type="simple"/></inline-formula>and <inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/11-7601194x15.png" xlink:type="simple"/></inline-formula></p><p>Bus 2 ≤ position of DG ≤ bus n</p><p>P1 ≠ P2</p><p>where P1 and P2 are the bus location of DG and capacitor banks at position 1 and position 2 respectively.</p></sec><sec id="s3"><title>3. Methodology</title><sec id="s3_1"><title>3.1. DGSI Ranking Method</title><p>In developing countries like India, the voltages at the remote end of the distribution feeders are greatly low with decreased voltage regulation since the rural distribution feeders are too long. Therefore, the bus voltage sensitivity of the node is to be considered for the DG placement in addition to the loss reduction, to produce the optimum result with reduced DG size and increased voltage profile. The DGSI is described in [<xref ref-type="bibr" rid="scirp.70450-ref10">10</xref>] .</p><disp-formula id="scirp.70450-formula231"><label>(8)</label><graphic position="anchor" xlink:href="http://html.scirp.org/file/11-7601194x16.png"  xlink:type="simple"/></disp-formula><p>where</p><disp-formula id="scirp.70450-formula232"><label>. (9)</label><graphic position="anchor" xlink:href="http://html.scirp.org/file/11-7601194x17.png"  xlink:type="simple"/></disp-formula><p>The value of BVSI from the literature [<xref ref-type="bibr" rid="scirp.70450-ref11">11</xref>] is as follows</p><disp-formula id="scirp.70450-formula233"><label>(10)</label><graphic position="anchor" xlink:href="http://html.scirp.org/file/11-7601194x18.png"  xlink:type="simple"/></disp-formula><p>By introducing DG size of 25% of feeder capacity in a bus other than the reference bus DGSI is found out using Equation (8). Thus DGSI is determined at all locations. Then the bus with least DGSI value is selected as the location for the insertion of DG. Then the size of DG is varied such that it produces minimum real power loss. This procedure is applied to both the type of DGs to determine the optimum size and location for real power loss minimization and the results are recorded. By implementing the DGSI ranking method, the determined optimum allocation is such that it reduces the real power loss with simultaneous improvement of voltage sensitivity of the radial distribution network.</p><p>This DGSI based approach determines the optimal location of DG unit primarily then the optimum size that should be placed in that location such that the minimum real power loss occurs. If only DG placement is essential this procedure is stopped here itself. This method is repeated for allocation of capacitor banks by considering the capacitor banks as a pure reactive power generator. (i.e. P<sub>DG</sub> = 0 &amp; Q<sub>DG</sub> = Q<sub>DGi</sub>.)</p><p>Then the location is determined by altering the base system by introducing a DG with optimum DG size into the radial distribution system. After determining the location, the optimum size of capacitor bank is found out. Since the DG and capacitor banks are incorporated to the RDN one by one, the sizes found using this analytical approach are local optima not global optimum solution. Hence to determine the global optimal solution the WIPSO and SADE algorithms are used.</p></sec><sec id="s3_2"><title>3.2. SADE Algorithm</title><p>The Differential Evolution (DE) is an evolutionary computational algorithm that applies comparatively pronounced selection and less stochastic approach to solve the optimization problems [<xref ref-type="bibr" rid="scirp.70450-ref12">12</xref>] . The significant characters of DE are its simplicity in structure, fast convergence, robustness and solution quality. The DE algorithm consists of three basic genetic operations; mutation, cross over and selection. After the initialization of population, the next generation population (G + 1) is created by this three basic operations using the current generation G.</p><p>Even the differential evolution is considered as accurate, reliable and fast convergence optimisation technique, the operator is required to set the values of control parameters of DE for each problem. Such parameter tuning is a time consuming process [<xref ref-type="bibr" rid="scirp.70450-ref13">13</xref>] . Using the self-adaptive differential evolution algorithm the time complexity does not increase since the user does not need to adjust the mutation parameter, cross over parameter and number of population. Hence self adaptive differential evolution algorithm can be implemented where the parameter tuning is not required [<xref ref-type="bibr" rid="scirp.70450-ref14">14</xref>] .</p></sec><sec id="s3_3"><title>3.3. WIPSO Algorithm</title><p>The velocity equation of standard PSO is represented as the sum of three terms. The first term <inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/11-7601194x19.png" xlink:type="simple"/></inline-formula> characterizes the current velocity of the particle and can be considered as a momentum term. The second term is connected with a local search and indicates the particles best position from its current position. The third term is related with global search and indicates the global best position. The whole standard PSO process is the searching process that particle depends on its memory capability and share the information to trace the best solution. In early stage of PSO, the P<sub>best</sub> and G<sub>best</sub> vary frequently; the algorithm has the well-built global search capacity and the fast convergence characteristics. But at the end stage the P<sub>best</sub> and G<sub>best</sub> values get stabilisation and the first term nearly drops to zero value. At this instant, the updating of position goes to stagnation and the algorithm provides the local optima. It is the main disadvantage of the standard PSO.</p><p>To improve this shortcoming of PSO and produce better results, the weight improved PSO is proposed. This algorithm alters the inertia weight w value to improve the global search ability in the early stage and local search ability in the end stage.</p><disp-formula id="scirp.70450-formula234"><label>(11)</label><graphic position="anchor" xlink:href="http://html.scirp.org/file/11-7601194x20.png"  xlink:type="simple"/></disp-formula><disp-formula id="scirp.70450-formula235"><label>(12)</label><graphic position="anchor" xlink:href="http://html.scirp.org/file/11-7601194x21.png"  xlink:type="simple"/></disp-formula><p>Here k represents the current iteration and k<sub>max</sub> is the maximum of iteration.</p><p>The velocity update equation is as follows</p><disp-formula id="scirp.70450-formula236"><label>(13)</label><graphic position="anchor" xlink:href="http://html.scirp.org/file/11-7601194x22.png"  xlink:type="simple"/></disp-formula><disp-formula id="scirp.70450-formula237"><label>(14)</label><graphic position="anchor" xlink:href="http://html.scirp.org/file/11-7601194x23.png"  xlink:type="simple"/></disp-formula><p>In this paper for simultaneous optimal allocation DG and capacitor banks , the SADE and WIPSO algorithms are applied.</p></sec></sec><sec id="s4"><title>4. Results and Discussion</title><p>A two-stage methodology is followed for the simultaneous allocation of DG and capacitor banks in the RDNs. Initially the locations of DG and capacitor bank are found out using DGSI ranking method. Here the location of capacitor bank is identified after changing the base case data of RDN with the insertion of DG of optimum size at optimum location. After determining the location of DG and capacitor banks, the SADE and WIPSO algorithms are applied for the simultaneous allocation of DG and capacitor bank in RDN and the results are compared. <xref ref-type="table" rid="table2">Table 2</xref> and <xref ref-type="table" rid="table3">Table 3</xref> show the results for standalone placement of DG and capacitor bank in the IEEE 33 bus and IEEE 69 bus RDN. From <xref ref-type="table" rid="table2">Table 2</xref>, it is understood that the SPV based DG improves the percentage of real power loss and reactive power loss reduction compared to wind based DG in both the test networks. From <xref ref-type="table" rid="table3">Table 3</xref>, it is understood that the standalone placement of capacitor bank in both the test works minimizes the real and reactive power loss occurred in the network by providing the reactive power support. Hence in this paper, it is decided to combine both DG and capacitor in RDN thereby to get the additional benefits in system loss reduction. For the combined allocation of DG and capacitor bank simultaneously the SADE and WIPSO algorithms are used and the results are recorded in <xref ref-type="table" rid="table4">Table 4</xref>.</p><p><xref ref-type="fig" rid="fig1">Figure 1</xref> shows that the both the real and reactive power losses occurred in the RDN gets minimized with the insertion of both renewable energy DG i.e. SPV and wind</p><table-wrap id="table2" ><label><xref ref-type="table" rid="table2">Table 2</xref></label><caption><title> Optimum allocation results of DG alone in RDNs using DGSI ranking method</title></caption><table><tbody><thead><tr><th align="center" valign="middle"  rowspan="2"  >System</th><th align="center" valign="middle"  rowspan="2"  >Type of DG</th><th align="center" valign="middle"  rowspan="2"  >Optimum location</th><th align="center" valign="middle"  colspan="2"  >Optimal size of DG</th><th align="center" valign="middle"  rowspan="2"  >Real power loss in KW</th><th align="center" valign="middle"  rowspan="2"  >Reactive power loss in KVAR</th><th align="center" valign="middle"  rowspan="2"  >% of real power loss reduction</th><th align="center" valign="middle"  rowspan="2"  >% of reactive power loss reduction</th></tr></thead><tr><td align="center" valign="middle" >Real power of DG in MW</td><td align="center" valign="middle" >Reactive power of DG in MVAR</td></tr><tr><td align="center" valign="middle"  rowspan="3"  >IEEE 33 bus</td><td align="center" valign="middle" >Without DG</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >213.4100</td><td align="center" valign="middle" >142.3412</td><td align="center" valign="middle" >NA</td><td align="center" valign="middle" >NA</td></tr><tr><td align="center" valign="middle" >SPV</td><td align="center" valign="middle" >30</td><td align="center" valign="middle" >1.600</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >118.5938</td><td align="center" valign="middle" >83.3418</td><td align="center" valign="middle" >44.43</td><td align="center" valign="middle" >41.45</td></tr><tr><td align="center" valign="middle" >Wind farm</td><td align="center" valign="middle" >8</td><td align="center" valign="middle" >1.900</td><td align="center" valign="middle" >0.644</td><td align="center" valign="middle" >160.1534</td><td align="center" valign="middle" >110.2239</td><td align="center" valign="middle" >24.95</td><td align="center" valign="middle" >22.56</td></tr><tr><td align="center" valign="middle"  rowspan="3"  >IEEE 69 bus</td><td align="center" valign="middle" >Without DG</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >223.2913</td><td align="center" valign="middle" >101.1721</td><td align="center" valign="middle" >NA</td><td align="center" valign="middle" >NA</td></tr><tr><td align="center" valign="middle" >SPV</td><td align="center" valign="middle" >61</td><td align="center" valign="middle" >1.89</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >80.6878</td><td align="center" valign="middle" >39.0887</td><td align="center" valign="middle" >63.86</td><td align="center" valign="middle" >61.36</td></tr><tr><td align="center" valign="middle" >Wind farm</td><td align="center" valign="middle" >61</td><td align="center" valign="middle" >1.7</td><td align="center" valign="middle" >0.616</td><td align="center" valign="middle" >152.1798</td><td align="center" valign="middle" >69.4624</td><td align="center" valign="middle" >31.85</td><td align="center" valign="middle" >31.34</td></tr></tbody></table></table-wrap><table-wrap id="table3" ><label><xref ref-type="table" rid="table3">Table 3</xref></label><caption><title> Optimum allocation results of Capacitor in RDNs using DGSI ranking method</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >System</th><th align="center" valign="middle" >Optimum Location</th><th align="center" valign="middle" >Optimal size of Capacitor in MVAR</th><th align="center" valign="middle" >Real power loss in KW</th><th align="center" valign="middle" >Reactive power loss in KVAR</th><th align="center" valign="middle" >% of real power loss reduction</th><th align="center" valign="middle" >% of reactive power loss reduction</th></tr></thead><tr><td align="center" valign="middle" >IEEE 33 bus</td><td align="center" valign="middle" >30</td><td align="center" valign="middle" >1.325</td><td align="center" valign="middle" >149.4973</td><td align="center" valign="middle" >100.5821</td><td align="center" valign="middle" >29.95</td><td align="center" valign="middle" >29.34</td></tr><tr><td align="center" valign="middle" >IEEE 69 bus</td><td align="center" valign="middle" >61</td><td align="center" valign="middle" >1.37</td><td align="center" valign="middle" >149.3152</td><td align="center" valign="middle" >68.9492</td><td align="center" valign="middle" >33.13</td><td align="center" valign="middle" >31.85</td></tr></tbody></table></table-wrap><table-wrap id="table4" ><label><xref ref-type="table" rid="table4">Table 4</xref></label><caption><title> Simultaneous allocation of DG and capacitor in RDN</title></caption><table><tbody><thead><tr><th align="center" valign="middle"  rowspan="2"  >System</th><th align="center" valign="middle"  rowspan="2"  >DG location</th><th align="center" valign="middle"  rowspan="2"  >Capacitor location</th><th align="center" valign="middle"  rowspan="2"  >Type of DG</th><th align="center" valign="middle"  colspan="2"  >Optimum size of DG</th><th align="center" valign="middle" >Capacitor in MVAR</th><th align="center" valign="middle"  rowspan="2"  >P<sub>LOSS</sub> KW</th><th align="center" valign="middle"  rowspan="2"  >Q<sub>LOSS</sub> MVAR</th><th align="center" valign="middle"  rowspan="2"  >% of P<sub>LOSS </sub>reduction</th><th align="center" valign="middle"  rowspan="2"  >% of Q<sub>LOSS </sub>reduction</th></tr></thead><tr><td align="center" valign="middle" >P<sub>DG</sub> MW</td><td align="center" valign="middle" >Q<sub>DG</sub> MVAR</td><td align="center" valign="middle" >Q<sub>DG</sub> MVAR</td></tr><tr><td align="center" valign="middle"  colspan="11"  >SADE approach</td></tr><tr><td align="center" valign="middle"  rowspan="2"  >IEEE 33</td><td align="center" valign="middle" >30</td><td align="center" valign="middle" >29</td><td align="center" valign="middle" >SPV</td><td align="center" valign="middle" >1.5889</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >1.2863</td><td align="center" valign="middle" >68.206</td><td align="center" valign="middle" >50.941</td><td align="center" valign="middle" >68.03</td><td align="center" valign="middle" >64.21</td></tr><tr><td align="center" valign="middle" >8</td><td align="center" valign="middle" >30</td><td align="center" valign="middle" >WIND</td><td align="center" valign="middle" >1.5584</td><td align="center" valign="middle" >0.5971</td><td align="center" valign="middle" >1.4939</td><td align="center" valign="middle" >84.593</td><td align="center" valign="middle" >63.346</td><td align="center" valign="middle" >60.36</td><td align="center" valign="middle" >55.50</td></tr><tr><td align="center" valign="middle"  rowspan="2"  >IEEE 69</td><td align="center" valign="middle" >61</td><td align="center" valign="middle" >62</td><td align="center" valign="middle" >SPV</td><td align="center" valign="middle" >1.8409</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >1.2316</td><td align="center" valign="middle" >23.272</td><td align="center" valign="middle" >14.321</td><td align="center" valign="middle" >89.58</td><td align="center" valign="middle" >85.84</td></tr><tr><td align="center" valign="middle" >61</td><td align="center" valign="middle" >62</td><td align="center" valign="middle" >WIND</td><td align="center" valign="middle" >1.8285</td><td align="center" valign="middle" >0.6337</td><td align="center" valign="middle" >1.9417</td><td align="center" valign="middle" >24.281</td><td align="center" valign="middle" >14.789</td><td align="center" valign="middle" >89.13</td><td align="center" valign="middle" >85.38</td></tr><tr><td align="center" valign="middle"  colspan="11"  >WIPSO approach</td></tr><tr><td align="center" valign="middle"  rowspan="2"  >IEEE 33</td><td align="center" valign="middle" >30</td><td align="center" valign="middle" >29</td><td align="center" valign="middle" >SPV</td><td align="center" valign="middle" >1.5827</td><td align="center" valign="middle" ></td><td align="center" valign="middle" >1.2857</td><td align="center" valign="middle" >68.386</td><td align="center" valign="middle" >50.962</td><td align="center" valign="middle" >67.96</td><td align="center" valign="middle" >64.19</td></tr><tr><td align="center" valign="middle" >8</td><td align="center" valign="middle" >30</td><td align="center" valign="middle" >WIND</td><td align="center" valign="middle" >1.7086</td><td align="center" valign="middle" >0.6168</td><td align="center" valign="middle" >1.4682</td><td align="center" valign="middle" >84.875</td><td align="center" valign="middle" >64.172</td><td align="center" valign="middle" >60.23</td><td align="center" valign="middle" >54.92</td></tr><tr><td align="center" valign="middle"  rowspan="2"  >IEEE 69</td><td align="center" valign="middle" >61</td><td align="center" valign="middle" >62</td><td align="center" valign="middle" >SPV</td><td align="center" valign="middle" >1.8189</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >1.2883</td><td align="center" valign="middle" >23.383</td><td align="center" valign="middle" >14.365</td><td align="center" valign="middle" >89.52</td><td align="center" valign="middle" >85.8</td></tr><tr><td align="center" valign="middle" >61</td><td align="center" valign="middle" >62</td><td align="center" valign="middle" >WIND</td><td align="center" valign="middle" >2.0210</td><td align="center" valign="middle" >0.6634</td><td align="center" valign="middle" >1.9070</td><td align="center" valign="middle" >24.595</td><td align="center" valign="middle" >15.111</td><td align="center" valign="middle" >89.16</td><td align="center" valign="middle" >85.06</td></tr></tbody></table></table-wrap><fig id="fig1"  position="float"><label><xref ref-type="fig" rid="fig1">Figure 1</xref></label><caption><title> Real and Reactive power loss with the standalone placement of DG and capacitor bank</title></caption><graphic mimetype="image"   position="float"  xlink:type="simple"  xlink:href="http://html.scirp.org/file/11-7601194x24.png"/></fig><p>DG. The capacitor banks introduced in the RDN also minimize the real and reactive power losses in the system. The SPV based DG minimizes the real and reactive power losses efficiently in the system than the wind based DG since it supplies only real power to the system. The wind based DG supplies real power to the RDN and absorbs the reactive power from the network. Hence its performance in real and reactive power loss reduction is not efficient. But the capacitor banks which supply only reactive power to the RDN reduces both the real and reactive power losses to some extent. The performance of wind DG in system loss reduction can be improved by its combined placement with capacitor banks.</p><p>It is evident from <xref ref-type="table" rid="table4">Table 4</xref>, that the simultaneous allocation of DG and capacitor bank in the RDN improves both the real and reactive power loss minimization occurred in the network. The performance of wind based DG in loss reduction improves more with the combined placement of capacitor bank. In IEEE 33 bus RDN, the percentage of real power loss reduction is 24.95% with the standalone placement of wind DG which gets improved to a value of 60.36% and 60.46% with the combined placement of capacitor bank using SADE and WIPSO algorithms. Similarly in IEEE 69 bus system it is improved from 31.85% to 89.13% and 89.16% using SADE and WIPSO algorithms.</p><p>In this work, the SADE and WIPSO algorithms obtain the locations of distributed generation identified by DGSI ranking method. For the simultaneous allocation of DG and capacitor bank, these algorithms get the locations of DGs as input to find the optimum sizes of DGs such that the minimum real power losses occurred in the RDNs. The benefits of relieving the SADE and WIPSO algorithm from the calculation of position of DGs are the less computational time and the enhanced convergence characteristics. Compared to SADE algorithm, the WIPSO algorithm has the fast convergence characteristics and less computational time (22.1 seconds). Whereas the computational time of SADE algorithm is 26 seconds. But, due to the good convergence character of the SADE algorithm, it produces the better optimal solutions than the WIPSO algorithm. The above said properties of SADE algorithm and WIPSO algorithm opens the door for researchers to develop a new hybrid algorithm by using the combinations of both these algorithms.</p></sec><sec id="s5"><title>5. Conclusion</title><p>This paper is essentially concerned with the optimal allocations of DG and capacitor banks simultaneously in RDN using the SADE and WIPSO algorithms. Both the SADE and WIPSO algorithms produce the good results for real power loss minimization in the test networks. The SADE algorithm produces the good optimum solution than the WIPSO algorithm and the WIPSO algorithm has the fast convergence characteristics which makes it suitable for online applications. The results prove that the simultaneous allocation of DG and capacitor bank improves the real and reactive power loss reduction more effectively than their standalone placement. The performance of wind based DG in system loss reduction is ineffective with its standalone placement but its combined placement with capacitor banks enhances the system loss reduction. The installation of the renewable energy DG and capacitor bank at the potential locations reduces the system losses effectively. The results support the penetration of renewable energy in RDN and thereby make the power system as environmental friendly. The addition of practical constraints such as the load variation with the time period and distinct sizes of DG ratings into the proposed problem is the future work of this research.</p></sec><sec id="s6"><title>Acknowledgements</title><p>The authors would like to express their sincere and the heartfelt thanks to the Principal and Management of AAA College of Engineering and Technology and Thiagarajar College of Engineering and Technology for their Constant support and encouragement towards the success of this research work.</p></sec><sec id="s7"><title>Cite this paper</title><p>Rajeswaran, S. and Nagappan, K. (2016) Optimum Simultaneous Allocation of Renewable Energy DG and Capacitor Banks in Radial Distribution Network. Circuits and Systems, 7, 3556- 3564. http://dx.doi.org/10.4236/cs.2016.711302</p></sec></body><back><ref-list><title>References</title><ref id="scirp.70450-ref1"><label>1</label><mixed-citation publication-type="other" xlink:type="simple">Acharya, N., Mahat, P. and Mithulananthan, N. (2006) An Analytical Approach for DG Allocation in Primary Distribution Network. International Journal of Electrical Power and Energy Systems, 28, 669-678. http://dx.doi.org/10.1016/j.ijepes.2006.02.013</mixed-citation></ref><ref id="scirp.70450-ref2"><label>2</label><mixed-citation publication-type="other" xlink:type="simple">Huang, V.L., Qin, A.K. and Suganthan, P.N. (2006) Self-Adaptive Differential Evolution Algorithm for Constrained Real-Parameter Optimization. Proceedings of IEEE Congress on Evolutionary Computation, Vancouver, 16-21 July 2006, 17-24. http://dx.doi.org/10.1109/CEC.2006.1688285</mixed-citation></ref><ref id="scirp.70450-ref3"><label>3</label><mixed-citation publication-type="other" xlink:type="simple">Manafi, H., Ghadimi, M., Ojaroudi, M. and Farhadi, P. (2013) Optimal Placement of Distributed Generations in Radial Distribution Systems Using Various PSO and DE Algorithms. Elektronika IR Elektrotechnika, 19, 53-57. http://dx.doi.org/10.5755/j01.eee.19.10.1941</mixed-citation></ref><ref id="scirp.70450-ref4"><label>4</label><mixed-citation publication-type="other" xlink:type="simple">Beromi, A.Y., Sedighizadeh, M. and Sadighi, M. (2008) A Particle Swarm Optimization for Sitting and Sizing of Distributed Generation in Distribution Network to Improve Voltage Profile and Reduce THD and Losses. Proceedings of 43rd International UPEC, 1-5.</mixed-citation></ref><ref id="scirp.70450-ref5"><label>5</label><mixed-citation publication-type="other" xlink:type="simple">Wong, L.Y., Suleiman, M.H., Rafidah, S., Rahim, A. and Aleman, O. (2011) Optimal Distributed Generation Placement Using Hybrid Genetic-Particle Swarm Optimization. International Review of Electrical Engineering, 6, 1390-1397.</mixed-citation></ref><ref id="scirp.70450-ref6"><label>6</label><mixed-citation publication-type="other" xlink:type="simple">Gunda, J. and Khan, N.A. (2011) Optimal Location and Sizing of DG and Shunt Capacitors Using Differential Evolution. International Journal of Soft Computing, 6, 128-135.http://dx.doi.org/10.3923/ijscomp.2011.128.135</mixed-citation></ref><ref id="scirp.70450-ref7"><label>7</label><mixed-citation publication-type="other" xlink:type="simple">Buayai, K. (2012) Optimal Multi-Type DGs Placement in Primary Distribution System by NSGA-II. Research Journal of Applied Sciences, Engineering and Technology, 4, 3610- 3617. http://maxwellsci.com/print/rjaset/v4-3610-3617.pdf</mixed-citation></ref><ref id="scirp.70450-ref8"><label>8</label><mixed-citation publication-type="other" xlink:type="simple">Hung, D.Q. and Mithulananthan, N. (2013) Multiple Distributed Generator Placement in Primary Distribution Networks for Loss Reduction. IEEE Transactions on Industrial Electronics, 60, 1700-1708. http://dx.doi.org/10.1109/TIE.2011.2112316</mixed-citation></ref><ref id="scirp.70450-ref9"><label>9</label><mixed-citation publication-type="other" xlink:type="simple">Prommee, W. and Ongsakul, W. (2008) Optimal Multi-Distributed Generation Placement by Adaptive Weight Particle Swarm Optimization. IEEE International Conference on Control, Automation and Systems, 14-17 October 2008, 1663-1668. http://dx.doi.org/10.1109/iccas.2008.4694499</mixed-citation></ref><ref id="scirp.70450-ref10"><label>10</label><mixed-citation publication-type="other" xlink:type="simple">Sivasangari, R. and Kamaraj, N. (2016) Optimum Allocation of Renewable DG Sources and Synchronous Capacitor Simultaneously Using PSO. International Journal of Applied Engineering Research, 11, 2781-2785.</mixed-citation></ref><ref id="scirp.70450-ref11"><label>11</label><mixed-citation publication-type="other" xlink:type="simple">Singh, N., Ghosh, S. and Murari, K. (2015) Optimal Sizing and Placement of DG in a Radial Distribution Network Using Sensitivity Based Methods. International Electrical Engineering Journal (IEEJ), 6, 1727-1734.</mixed-citation></ref><ref id="scirp.70450-ref12"><label>12</label><mixed-citation publication-type="other" xlink:type="simple">Storn, R. and Price, K. (2012) Differential Evolution—A Simple and Efficient Heuristic for Global Optimization over Continuous Spaces, 341-359.</mixed-citation></ref><ref id="scirp.70450-ref13"><label>13</label><mixed-citation publication-type="other" xlink:type="simple">Omran, M.G.H., Salman, A. and Engelbrecht, A.P. (2005) Self-Adaptive Differential Evolution. Computational Intelligence and Security of the Series Lecture Notes in Computer Science, 3801, 192-199. http://dx.doi.org/10.1007/11596448_28</mixed-citation></ref><ref id="scirp.70450-ref14"><label>14</label><mixed-citation publication-type="other" xlink:type="simple">Brest, J., Greiner, S., Boskovic, B., Mernik, M. and Zumer, V. (2006) Self-Adapting Control Parameters in Differential Evolution: A Comparative Study on Numerical Benchmark Pro- blems. IEEE Transactions on Evolutionary Computing, 10, 646-657. http://dx.doi.org/10.1109/TEVC.2006.872133</mixed-citation></ref></ref-list></back></article>