<?xml version="1.0" encoding="UTF-8"?><!DOCTYPE article  PUBLIC "-//NLM//DTD Journal Publishing DTD v3.0 20080202//EN" "http://dtd.nlm.nih.gov/publishing/3.0/journalpublishing3.dtd"><article xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink" dtd-version="3.0" xml:lang="en" article-type="research article"><front><journal-meta><journal-id journal-id-type="publisher-id">CS</journal-id><journal-title-group><journal-title>Circuits and Systems</journal-title></journal-title-group><issn pub-type="epub">2153-1285</issn><publisher><publisher-name>Scientific Research Publishing</publisher-name></publisher></journal-meta><article-meta><article-id pub-id-type="doi">10.4236/cs.2016.710262</article-id><article-id pub-id-type="publisher-id">CS-69870</article-id><article-categories><subj-group subj-group-type="heading"><subject>Articles</subject></subj-group><subj-group subj-group-type="Discipline-v2"><subject>Computer Science&amp;Communications</subject><subject> Engineering</subject><subject> Physics&amp;Mathematics</subject></subj-group></article-categories><title-group><article-title>
 
 
  Firefly Algorithm in Determining Maximum Load Utilization Point and Its Enhancement through Optimal Placement of FACTS Device
 
</article-title></title-group><contrib-group><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>S.</surname><given-names>Rajasekaran</given-names></name><xref ref-type="aff" rid="aff1"><sup>1</sup></xref><xref ref-type="corresp" rid="cor1"><sup>*</sup></xref></contrib><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Dr.</surname><given-names>S. Muralidharan</given-names></name><xref ref-type="aff" rid="aff2"><sup>2</sup></xref></contrib></contrib-group><aff id="aff2"><addr-line>Department of Electrical and Electronics Engineering, Mepco Schlenk Engineering College, Sivakasi, India</addr-line></aff><aff id="aff1"><addr-line>Department of Electrical and Electronics Engineering, Thamirabharani Engineering College, Tirunelveli, India</addr-line></aff><author-notes><corresp id="cor1">* E-mail:<email>rajalakshmircit@gmail.com(SR)</email>;</corresp></author-notes><pub-date pub-type="epub"><day>02</day><month>08</month><year>2016</year></pub-date><volume>07</volume><issue>10</issue><fpage>3081</fpage><lpage>3094</lpage><history><date date-type="received"><day>1</day>	<month>May</month>	<year>2016</year></date><date date-type="rev-recd"><day>accepted</day>	<month>10</month>	<year>May</year>	</date><date date-type="accepted"><day>19</day>	<month>August</month>	<year>2016</year></date></history><permissions><copyright-statement>&#169; Copyright  2014 by authors and Scientific Research Publishing Inc. </copyright-statement><copyright-year>2014</copyright-year><license><license-p>This work is licensed under the Creative Commons Attribution International License (CC BY). http://creativecommons.org/licenses/by/4.0/</license-p></license></permissions><abstract><p>
 
 
  In a Power System, load is the most uncertain and extremely time varying unit. Hence it is important to determine the system’s supreme acceptable loadability limit called maximum loadability
   
  point to accommodate the sudden variation of load demand. Nowadays the enhancement of the
   
  maximum loadability point is essential to meet the rapid growth of load demand by improvising the system’s load utilization capacity. Flexible AC Transmission system devices (FACTS) with their speed and flexibility will play a key role in enhancing the controllability and power transfer capability of the system. Considering the theme of FACTS devices in the loadability limit enhancement,
   
  in this paper maximum loadability limit determination and its
   
  enhancement are prepared with the help of swarm intelligence based meta-heuristic Firefly Algorithm(FFA) by finding the optimal loading factor for each load and optimally placing the SVC (Shunt Compensation) and TCSC (Series
   
  Compensation) FACTS devices in the system. To illuminate the effectiveness of FACTS devices in
   
  the loadability enhancement, the line contingency scenario is also concerned
   
  in the study. The study of FACTS based maximum system load utilization acceptability point determination is demonstrated with the help of modified IEEE 30 bus, IEEE 57 Bus and IEEE 118 Bus test systems. The results of FACTS devices involvement in determining the maximum loading point enhance the load
   
  utilization point in normal state
   
  and also help to overcome the system violation in transmissionline contingency state. Also the firefly algorithm in determining
   
  the maximum loadability point provides better search capability with faster convergence rate compared to that of Particle swarm optimization (PSO) and Differential evolution algorithm.
 
</p></abstract><kwd-group><kwd>FACTS</kwd><kwd> Maximum Loadability</kwd><kwd> Firefly Algorithm (FFA)</kwd></kwd-group></article-meta></front><body><sec id="s1"><title>1. Introduction</title><p>In present days, the growing nations face the challenges of electrical power demand increasing in rocketing speed, mushrooming of ill-type load such as heaters, air conditioners and some type of motors, which have negative exponential load characteristics and sudden block out due to voltage collapse. The increasing power demand is not answered by expansion of power generating plant and transmission unit since it not only requires huge capital investment but also considers the socio-economic and environmental factors. The solution to the above problem is hidden in finding the answer of maximum loadabilty limit of the power system. The maximum loadability limit is the point where the system can able to accommodate the utmost total system loading value without violating system constraints such as voltage limit of the buses, real and reactive power limit of generator, transmission line power transfer limit. Since the control variables of the power system have a mixture of discrete and continuous variables, the maximum loadability limit determination problem has been formulated as a non- linear optimization problem. In the beginning stage of the maximum loadability point determination, mathematical iterative optimization techniques such as i) continuation power flow method (CPF); ii) sequential quadratic programming (SQP); iii) interior point method (IP); and iv) repetitive power flow solution have been utilized more. Most of the authors in their literature utilize the continuation power flow (CPF) technique proposed by Ajjarapu and Christy [<xref ref-type="bibr" rid="scirp.69870-ref1">1</xref>] . But the difficulties in the CPF method are complex mathematical formulations or convergence problems if the system is already near the maximum loading limit and fails to give the accurate result if the step length is high. The Interior Point (IP) algorithm [<xref ref-type="bibr" rid="scirp.69870-ref2">2</xref>] , Sequential Quadratic Programming (SQP) algorithm [<xref ref-type="bibr" rid="scirp.69870-ref3">3</xref>] , and repetitive power flow solution [<xref ref-type="bibr" rid="scirp.69870-ref4">4</xref>] were also used for loadability problem. These three algorithms have limitation in handling the mixture of continuous and discrete variable, large sets of equality and inequality conditions and also having limitations in starting and terminating conditions as the number of system variable increases. Hence the conventional optimization methods are not able to locate global optimum, and can only lead to a local optimum and sometimes results in divergence.</p><p>In early 2000, evolutionary/meta-heuristic computing techniques like Genetic Algorithm (GA), Particle Swarm Optimization (PSO) and Evolutionary Programming (EP) have emerged as very powerful general purpose solution tools for solving the complex power system problems. Basically, these meta-heuristics search techniques are capable of finding the optimum solution of a problem irrespective of the number of control variables and also effective in handling the mixture of continuous and discrete variables. Among the above mentioned meta-heuristic algorithm, the particle swarm optimization (PSO) technique [<xref ref-type="bibr" rid="scirp.69870-ref5">5</xref>] generates high quality solutions for the power system problem within short calculation time and has more global searching ability at the beginning of the run and a local search near the end of the run. Many researchers used hybrid PSO [<xref ref-type="bibr" rid="scirp.69870-ref6">6</xref>] [<xref ref-type="bibr" rid="scirp.69870-ref7">7</xref>] , multi-agent PSO [<xref ref-type="bibr" rid="scirp.69870-ref8">8</xref>] , CAPSO algorithm [<xref ref-type="bibr" rid="scirp.69870-ref9">9</xref>] technique to improve the efficiency in searching the optimal loading point. The above PSO algorithms have to maintain a lot of algorithmic control parameters to achieve the better search path in determining best loading point. To reduce the algorithmic control parameters handling complexity, a simple and few control parameters based Evolutionary Differential evolution algorithm [<xref ref-type="bibr" rid="scirp.69870-ref10">10</xref>] has practiced widely. Though DE provides more precise and faster convergence rate in obtaining the optimum point, the probability of getting the nearest optimal point is very less. Premature convergence is a most frequent happening in DE. Recent year’s revolutionary hybrid process of combining the advantages of two meta-heuristic algorithms in determining the optimal solution has been practised more in many applications. In literature [<xref ref-type="bibr" rid="scirp.69870-ref11">11</xref>] , the above revolutionary way of combining DE and PSO has been used in determining the maximum loadability point. Here the search capability of DE is improved by the PSO but has high complexity in algorithmic structure and in algorithmic control parameters. In the last decade due to the lot of research work in meta-heuristics algorithm, many new algorithm’s like Firefly algorithm, Bat Algorithm, Cuckoo search , Teachers Learning based optimization Algorithm etc. have been emerged and providing strong potential in solving the engineering optimization problem with limited control variables and better search capability. Among them Firefly algorithm [<xref ref-type="bibr" rid="scirp.69870-ref12">12</xref>] - [<xref ref-type="bibr" rid="scirp.69870-ref14">14</xref>] shows more efficient in handling multimodal optimization problem with their fastest search capability and also maintain better exploration balance against exploitation.</p><p>The rise of load demand in the current electricity scenario may increase the stress of transmission system which in turn may lead to the chance of the transmission line outage. The Maximum loading point determination considering the above scenario is effectively handled with the inclusion of FACTS devices in the system. FACTS devices helps in controlling the real and reactive power flow of the transmission system and voltage support in the system [<xref ref-type="bibr" rid="scirp.69870-ref15">15</xref>] which in turn enhances the maximum acceptable loading point at normal condition and also helps in regaining the system stability at line contingency state. Few researchers [<xref ref-type="bibr" rid="scirp.69870-ref16">16</xref>] - [<xref ref-type="bibr" rid="scirp.69870-ref19">19</xref>] determine the maximum loadability point of the system by optimally determining the loading value of each load and its enhancement by optimally placing and settings the FACTS devices at normal conditions.</p><p>In this paper, maximum loadability determination and its enhancement at normal and transmission line outage condition with the FACTS devices such as SVC and TCSC is experimented and the results are analyzed with the help of modified IEEE 30 Bus, IEEE 57 Bus and 118 Bus systems. Firefly Algorithm optimization tool is used to determine the maximum loading point by finding the optimal loading value of each load and also by finding the optimal placement and settings of TCSC and SVC in each Bus system without violating the system constraints.</p></sec><sec id="s2"><title>2. Maximum Loading Point Determination</title><p>Maximum loading value of the system is the boundary of the system load where all the system parameters such as Bus voltage, real and reactive power of the generator, power flow of the transmission line can be accommodated within their limits. The maximization of system load is achieved by optimizing the loading factor of each load. Hence the above is considered as an optimization problem and its mathematical problem formulation is described in below section</p><sec id="s2_1"><title>2.1. Mathematical Problem Formulation for Finding Optimal Loadability Point Determination</title><p>The main objective of our paper is to maximize the total real power load of the system without violating the system’s equality and inequality constraints such as power balance, voltage limit, generation real and reactive power limit and line flow limit. This can be mathematically formulated as below</p><disp-formula id="scirp.69870-formula379"><label>(1)</label><graphic position="anchor" xlink:href="http://html.scirp.org/file/23-7600929x6.png"  xlink:type="simple"/></disp-formula><p>where</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x7.png" xlink:type="simple"/></inline-formula>,</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x8.png" xlink:type="simple"/></inline-formula>= Total number of load connected buses,</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x9.png" xlink:type="simple"/></inline-formula>= Total number of load connected buses,</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x10.png" xlink:type="simple"/></inline-formula>= new real power load value of the i<sup>th</sup> bus in p.u,</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x11.png" xlink:type="simple"/></inline-formula>= Initial real power load value of the i<sup>th</sup> bus in p.u.</p><p>Subject to the</p><p>1. Equality constraints of Power balance Equation</p><disp-formula id="scirp.69870-formula380"><label>(2)</label><graphic position="anchor" xlink:href="http://html.scirp.org/file/23-7600929x12.png"  xlink:type="simple"/></disp-formula><disp-formula id="scirp.69870-formula381"><label>(3)</label><graphic position="anchor" xlink:href="http://html.scirp.org/file/23-7600929x13.png"  xlink:type="simple"/></disp-formula><p>where</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x14.png" xlink:type="simple"/></inline-formula>is the real power value of the i<sup>th</sup> Generator Bus in p.u,</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x15.png" xlink:type="simple"/></inline-formula>is the real power value of the i<sup>th</sup> Load Bus in p.u,</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x16.png" xlink:type="simple"/></inline-formula>is the reactive power value of the i<sup>th</sup> Generator Bus in p.u,</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x17.png" xlink:type="simple"/></inline-formula>is the reactive power value of the i<sup>th</sup> Load Bus in p.u,</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x18.png" xlink:type="simple"/></inline-formula>is the Voltage Magnitude value of the i<sup>th</sup> Bus in p.u,</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x19.png" xlink:type="simple"/></inline-formula>is the Voltage Magnitude value of the j<sup>th</sup> Bus in p.u,</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x20.png" xlink:type="simple"/></inline-formula>is the Magnitude of the admittance connected between the i<sup>th</sup> and j<sup>th</sup> Bus in p.u,</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x21.png" xlink:type="simple"/></inline-formula>is the Angle of the admittance connected between the i<sup>th</sup> and j<sup>th</sup> Bus in p.u,</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x22.png" xlink:type="simple"/></inline-formula>is the Angle of the voltage in j<sup>th</sup> Bus in p.u,</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x23.png" xlink:type="simple"/></inline-formula>is the Angle of the voltage in i<sup>th</sup> Bus in p.u,</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x24.png" xlink:type="simple"/></inline-formula>is the total number of Load Bus,</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x25.png" xlink:type="simple"/></inline-formula>is the total number of Generator Bus.</p><p>2. Inequality Constraints</p><disp-formula id="scirp.69870-formula382"><label>(4)</label><graphic position="anchor" xlink:href="http://html.scirp.org/file/23-7600929x26.png"  xlink:type="simple"/></disp-formula><disp-formula id="scirp.69870-formula383"><label>(5)</label><graphic position="anchor" xlink:href="http://html.scirp.org/file/23-7600929x27.png"  xlink:type="simple"/></disp-formula><disp-formula id="scirp.69870-formula384"><label>(6)</label><graphic position="anchor" xlink:href="http://html.scirp.org/file/23-7600929x28.png"  xlink:type="simple"/></disp-formula><disp-formula id="scirp.69870-formula385"><label>(7)</label><graphic position="anchor" xlink:href="http://html.scirp.org/file/23-7600929x29.png"  xlink:type="simple"/></disp-formula><disp-formula id="scirp.69870-formula386"><label>(8)</label><graphic position="anchor" xlink:href="http://html.scirp.org/file/23-7600929x30.png"  xlink:type="simple"/></disp-formula><p>where</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x31.png" xlink:type="simple"/></inline-formula>is the Maximum allowable power flow of the i<sup>th</sup> transmission line in p.u,</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x32.png" xlink:type="simple"/></inline-formula>is the Loading factor of i<sup>th</sup> Load,</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x33.png" xlink:type="simple"/></inline-formula>is the total Number of Loads.</p></sec><sec id="s2_2"><title>2.2. FACTS in Maximum Loading Point Determination</title><p>FACTS devices have the flexible and rapid control capability of various system parameters in a power system network [<xref ref-type="bibr" rid="scirp.69870-ref15">15</xref>] . Real and reactive power flow of the transmission system and voltage of each bus are main among the system parameters in the network .In this paper, combined contribution of FACTS devices such as thyristor control static compensator (TCSC) and Static VAR Compensator (SVC) has been utilized to achieve the Maximum loadability point enhancement at Normal and line contingency state. The TCSC has been modelled as a variable reactance inserted in a transmission line and SVC has been modelled as a reactive source added at the sending end of the transmission line. Depending upon the position and settings of TCSC and SVC, the loadability limit of the system get varied. Hence the placement and settings of FACTS devices are also considered as a control variable in determining the maximum loadability point. The above also included in the mathematical formulation of determining maximum load utilization point by randomly generating the transmission line number along with the loading factor. The settings of TCSC and SVC data are extracted from the literature [<xref ref-type="bibr" rid="scirp.69870-ref18">18</xref>] . Hence in the above mathematical formulation, Facts Devices inequality constraints are also considered for the maximum loadability limit enhancement. This can be given as follows</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x34.png" xlink:type="simple"/></inline-formula>MVAR,<inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x34.png" xlink:type="simple"/></inline-formula><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x35.png" xlink:type="simple"/></inline-formula> (9)</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x36.png" xlink:type="simple"/></inline-formula>p.u,<inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x36.png" xlink:type="simple"/></inline-formula><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x37.png" xlink:type="simple"/></inline-formula> (10)</p><p>where</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x38.png" xlink:type="simple"/></inline-formula>is the reactive power injected in the bus by Placing SVC,</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x39.png" xlink:type="simple"/></inline-formula>is the reactance added to the Transmission Line by placing TCSC,</p><p><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x40.png" xlink:type="simple"/></inline-formula>is the maximum and minimum line reactance multiplier added to the line reactance<inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x40.png" xlink:type="simple"/></inline-formula><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x41.png" xlink:type="simple"/></inline-formula>.</p></sec></sec><sec id="s3"><title>3. Firefly Algorithm (FFA) for the Maximum Loading Point Determination</title><p>Firefly algorithm was developed by Xin-She Yang [<xref ref-type="bibr" rid="scirp.69870-ref12">12</xref>] and it is based on idealized behaviour of the flashing characteristics of fireflies. Nature based algorithms are highly effective and efficient to solve difficult optimization problems. FFA is nature inspired algorithm and gaining popularity recently for solving nonlinear optimization problems technique [<xref ref-type="bibr" rid="scirp.69870-ref13">13</xref>] . For simplicity, we can summarize the flashing characteristics of the FFA as the following three rules: i) All fireflies are unisex, so that one firefly is attracted to other fireflies regardless of their sex; ii) Attractiveness is proportional to their brightness, thus for any two flashing fireflies, the less bright one will move towards the brighter one; iii) The attractiveness is proportional to the brightness and they both decrease as their distance increases. If no one is brighter than a particular firefly, it will move randomly. The brightness of a firefly is affected or determined by the landscape of the objective function to be optimized. The movement of a firefly “i” is attracted to another more attractive (brighter) firefly “j” is determined by</p><disp-formula id="scirp.69870-formula387"><label>. (11)</label><graphic position="anchor" xlink:href="http://html.scirp.org/file/23-7600929x42.png"  xlink:type="simple"/></disp-formula><p>In the Equation (11) the second term gives the attractiveness of a firefly which varies with the light intensity/brightness seen by adjacent fireflies and the distance between themselves and <inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x43.png" xlink:type="simple"/></inline-formula> is the attraction parameter when the distance is zero. The parameter <inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x43.png" xlink:type="simple"/></inline-formula><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x44.png" xlink:type="simple"/></inline-formula> which characterizes the variation of the attractiveness is the light absorption coefficient and is crucial to determine the speed of convergence of the algorithm. In theory, <inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x43.png" xlink:type="simple"/></inline-formula><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x44.png" xlink:type="simple"/></inline-formula><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x45.png" xlink:type="simple"/></inline-formula>could take any value in the set between 0 to infinity. On the other hand, if γ = 0, the attraction is constant. If β<sub>0</sub> = 0, it becomes a simple random walk. So, here the value of γ and β<sub>0</sub> was selected by conducting trail and test me-</p><p>thod. The distance between any two fireflies i and j at <inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x46.png" xlink:type="simple"/></inline-formula> and <inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x46.png" xlink:type="simple"/></inline-formula><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x47.png" xlink:type="simple"/></inline-formula> can be the Cartesian distance <inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x46.png" xlink:type="simple"/></inline-formula><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x47.png" xlink:type="simple"/></inline-formula><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x48.png" xlink:type="simple"/></inline-formula></p><p>Third term is randomization with <inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x49.png" xlink:type="simple"/></inline-formula> being the randomization parameter, and <inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x49.png" xlink:type="simple"/></inline-formula><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x50.png" xlink:type="simple"/></inline-formula> is a vector of random numbers drawn from a Gaussian distribution or uniform distribution at time t (<inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x49.png" xlink:type="simple"/></inline-formula><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x50.png" xlink:type="simple"/></inline-formula><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x51.png" xlink:type="simple"/></inline-formula>. Here α<sub>t</sub> essentially control the randomness (or, to some extent, the diversity of solutions), we can tune this parameter during iterations so that it can vary with the iteration counter t. So a good way to express α<sub>t</sub> is to use α<sub>t</sub> = α<sub>0</sub>δ<sub>t</sub>, where δ<sub>t</sub> is (0 &lt; δ &lt; 1) and δ is essentially a cooling factor. Here we use δ = 0.95 to 0.97 and α<sub>0</sub> = 0.01 L where L is the scaling parameter depend on the problem. In this work, we use L as 10. Artificial diversification is also applied in the Firefly population to avoid premature convergence, which corresponds to a local optimum. In this work, random movement of firefly is used by simple mutation method like that of used in Genetic Algorithm. In this work, it is assumed that for a given firefly x, if the dimension O<sub>k</sub> is selected, then the resulting dimension will be selected using the equation.</p><disp-formula id="scirp.69870-formula388"><label>(12)</label><graphic position="anchor" xlink:href="http://html.scirp.org/file/23-7600929x52.png"  xlink:type="simple"/></disp-formula><p>where</p><p>a<sub>k</sub> and b<sub>k</sub> are lower and upper bands of O<sub>k</sub>,</p><p>rand is a uniform random number chosen in the range of (0, 1).</p><p>Structure of Firefly Algorithm (FFA):</p><p>1. Initialize the objective function <inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x53.png" xlink:type="simple"/></inline-formula> as given in the section 2.1</p><p>2. Initialize a population of fireflies X (<inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x54.png" xlink:type="simple"/></inline-formula>) with the population size of NF &#215; N. Where NF is the Number of fireflies as 50 and N is the Dimension size depends on the number of loads available to the test systems and a FACTS device such as SVC and TCSC Location and ratings</p><p>3. The light absorption coefficient <inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x55.png" xlink:type="simple"/></inline-formula> is defined as random search between 0 to 10 and the attraction parameter <inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x55.png" xlink:type="simple"/></inline-formula><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x56.png" xlink:type="simple"/></inline-formula> value as one</p><p>4. While (t &lt;= Max Generation)</p><p>5. For I = 1:n (all n fireflies)</p><p>6. For j = 1:i</p><p>7. Light Intensity <inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x57.png" xlink:type="simple"/></inline-formula> of each firefly <inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x57.png" xlink:type="simple"/></inline-formula><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x58.png" xlink:type="simple"/></inline-formula> is determined by the objective function <inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x57.png" xlink:type="simple"/></inline-formula><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x58.png" xlink:type="simple"/></inline-formula><inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x59.png" xlink:type="simple"/></inline-formula></p><p>8. If (<inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x60.png" xlink:type="simple"/></inline-formula>)</p><p>9. Move firefly i towards j in all the dimensions as per the Equation (11)</p><p>10. Else</p><p>11. Move firefly i randomly by creating a new dimension as per the Equation (12)</p><p>12. End if</p><p>13. Evaluate newly created firefly Light Intensity and update the Light Intensity solutions</p><p>14. End for j</p><p>15. End for i</p><p>16. Rank the fireflies based on its Light Intensity</p><p>17. Extract the Local best firefly of each population</p><p>18. End While</p><p>19. Obtain the global best firefly from all the Local best firefly</p></sec><sec id="s4"><title>4. Results and Discussion</title><p>Three standard IEEE Bus systems such as modified IEEE 30 Bus system, IEEE 57 Bus and IEEE 118 Bus system [<xref ref-type="bibr" rid="scirp.69870-ref7">7</xref>] [<xref ref-type="bibr" rid="scirp.69870-ref8">8</xref>] has been used to exhibit the proposed theme of Firefly based maximum loadability enhancement. In this paper, three strategies have been adopted in sequence to achieve the proposed theme. The three Strategies are as follows:</p><p>Strategy1: Determination of maximum loadability point using Firefly Algorithm and its result comparison with the other Meta-heuristic Algorithmic results.</p><p>Strategy2: FACTS devices Involvement in the Enhancement of maximum loadability point.</p><p>Strategy3: Maximum loadability point determination in Line Contingency.</p><p>The detailed study of these three strategies has been given below. The FFA Programs were developed and tested using the MATLAB 7.0 Software Packages with the support of MATPOWER simulation software package [<xref ref-type="bibr" rid="scirp.69870-ref20">20</xref>] .</p><sec id="s4_1"><title>4.1. Strategy 1: Maximum Loading Point Determination Using FFA</title><p>The total initial (Base case) real power load of 1.892 Per Unit,12.508 Per Unit and 42.42 Per Unit has been utilized in the modified IEEE-30 bus, IEEE-57 bus and IEEE-118 bus test system respectively. In this strategy, the maximum loading point is determined by finding the optimal incremental loading factor from each initial real power load using Firefly algorithm as mentioned in the section. Here the incremental load has been assumed to be at unity power factor. This strategic implementation result of modified IEEE-30 bus, IEEE-57 bus and IEEE- 118 bus test system have been recorded and emphasized in <xref ref-type="table" rid="table1">Table 1</xref>, <xref ref-type="table" rid="table3">Table 3</xref> and <xref ref-type="table" rid="table6">Table 6</xref> respectively by comparing the results of the other literature.</p><p>In <xref ref-type="table" rid="table1">Table 1</xref>, the fourth row shows the FFA algorithm based maximum loadability point of modified IEEE 30 Bus system. The number of loading factors of this system is 20. To highlight the value of the FFA, the results has been compared with the results of DE and DE-PSO from the literature [<xref ref-type="bibr" rid="scirp.69870-ref11">11</xref>] given in the second and third row of <xref ref-type="table" rid="table1">Table 1</xref> respectively. It is inferred from <xref ref-type="table" rid="table1">Table 1</xref> that the percentage of total incremental real power load of the FFA is better compared to that of DE and DEPSO. The Critical voltage of the Bus system shows that the maximum loadability point is calculated without the violation of voltage limits. The statistical measures of meta-heuristic algorithm such as mean, best, standard deviation are recorded in <xref ref-type="table" rid="table2">Table 2</xref> by conducting 20 different trials. The low standard deviation around the high mean value of FFA shows the better quality and robustness of the FFA compared to that of DE and DE-PSO. The statistical analysis clearly depicts that FFA provides greater amount of balance between exploitation and exploration process.</p><p>To check the performance consistency of the FFA, higher order systems such as IEEE 57 Bus system having 42 loading factor and IEEE 118 Bus system having 99 loading factor has been used for implementation and the implemented results are recorded in <xref ref-type="table" rid="table3">Table 3</xref> and <xref ref-type="table" rid="table6">Table 6</xref> respectively. The IEEE 57 Bus system FFA results are compared with the PSO and HPSO algorithm results given in the literature [<xref ref-type="bibr" rid="scirp.69870-ref7">7</xref>] and the IEEE 118 results are</p><table-wrap id="table1" ><label><xref ref-type="table" rid="table1">Table 1</xref></label><caption><title> FFA based maximum loadability comparison result of IEEE 30 Bus system</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Algorithm</th><th align="center" valign="middle" >Maximum Loadability in p.u</th><th align="center" valign="middle" >Critical Voltage</th><th align="center" valign="middle" >Total Incremental System Load from Base Case in %</th><th align="center" valign="middle" >Optimal SVC Bus No.</th><th align="center" valign="middle" >Optimal TCSC Line</th><th align="center" valign="middle" >SVC in MW</th><th align="center" valign="middle" >in p.u</th></tr></thead><tr><td align="center" valign="middle" >Base Case</td><td align="center" valign="middle" >1.892</td><td align="center" valign="middle" >0.961 @ 8bus</td><td align="center" valign="middle" ></td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td></tr><tr><td align="center" valign="middle" >DE [<xref ref-type="bibr" rid="scirp.69870-ref11">11</xref>]</td><td align="center" valign="middle" >2.6709</td><td align="center" valign="middle" >Not Mentioned</td><td align="center" valign="middle" >41.16807</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td></tr><tr><td align="center" valign="middle" >DEPSO [<xref ref-type="bibr" rid="scirp.69870-ref11">11</xref>]</td><td align="center" valign="middle" >2.6974</td><td align="center" valign="middle" >0.9499 @ 8bus</td><td align="center" valign="middle" >42.5687</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td></tr><tr><td align="center" valign="middle" >FFA without FACTS</td><td align="center" valign="middle" >2.7208</td><td align="center" valign="middle" >0.9501 @ 8bus</td><td align="center" valign="middle" >43.8089</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td></tr><tr><td align="center" valign="middle" >FFA with FACTS</td><td align="center" valign="middle" >2.8461</td><td align="center" valign="middle" >0.9501 @ 8bus</td><td align="center" valign="middle" >50.42957</td><td align="center" valign="middle" >1</td><td align="center" valign="middle" >[1 3]</td><td align="center" valign="middle" >14.0863 (Inductive Mode)</td><td align="center" valign="middle" >0.073 (Capacitive Mode)</td></tr></tbody></table></table-wrap><table-wrap id="table2" ><label><xref ref-type="table" rid="table2">Table 2</xref></label><caption><title> Statistical performance comparison of FFA for IEEE 33 Bus system</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Method</th><th align="center" valign="middle" >Worst</th><th align="center" valign="middle" >Mean</th><th align="center" valign="middle" >Best</th><th align="center" valign="middle" >Standard Deviation</th><th align="center" valign="middle" >No of Iteration</th></tr></thead><tr><td align="center" valign="middle" >DE</td><td align="center" valign="middle" >2.5813</td><td align="center" valign="middle" >2.6334</td><td align="center" valign="middle" >2.6709</td><td align="center" valign="middle" >0.0234</td><td align="center" valign="middle" >15</td></tr><tr><td align="center" valign="middle" >DE-PSO</td><td align="center" valign="middle" >2.642</td><td align="center" valign="middle" >2.6759</td><td align="center" valign="middle" >2.6974</td><td align="center" valign="middle" >0.02149</td><td align="center" valign="middle" >12</td></tr><tr><td align="center" valign="middle" >FFA</td><td align="center" valign="middle" >2.710249</td><td align="center" valign="middle" >2.7198</td><td align="center" valign="middle" >2.720865439</td><td align="center" valign="middle" >0.0031</td><td align="center" valign="middle" >15</td></tr></tbody></table></table-wrap><p>compared with the DE and DEPSO algorithm results given in the literature [<xref ref-type="bibr" rid="scirp.69870-ref11">11</xref>] . From the results in <xref ref-type="table" rid="table3">Table 3</xref> and <xref ref-type="table" rid="table6">Table 6</xref> it is inferred that the FFA’s maximum loadability point and its percentage increment from the base value has better value with that of other compared algorithm. The statistical analysis results of the both system by conducting 20 independent trials are recorded in <xref ref-type="table" rid="table4">Table 4</xref> and <xref ref-type="table" rid="table5">Table 5</xref>. It is evident from the statistical tab that the FFA provides better consistency results in terms of quality and iteration convergence.</p></sec><sec id="s4_2"><title>4.2. Strategy 2: FACTS Devices Involvement in the Enhancement of Maximum Loadability Point</title><p>In this strategy, the enhancement of system’s maximum load utilization is achieved by involving the FACTS devices such as TCSC and SVC united. The combined TCSC and SVC regulates the active and reactive power control and also the voltage magnitude control by means of shunt and series compensation. Hence the optimal placement and settings of FACTS devices such as TCSC and SVC along with the optimal loading factor for each load helps to increase the systems loadability limit. The above objective has been achieved using the FFA by solving the formulation mentioned in the section 2 along with the FACTS devices setting constraints. The FFA with FACTS devices strategy has been implemented using three test systems and the results are recorded in the fifth row of <xref ref-type="table" rid="table1">Table 1</xref>, <xref ref-type="table" rid="table3">Table 3</xref> and <xref ref-type="table" rid="table6">Table 6</xref>.</p><p>In the modified IEEE 30 bus test system, the TCSC has been placed on the transmission line connected between bus no.1 and bus no.3 with the X<sub>TCSC</sub> of 0. 073 p.u added to the line. Here TCSC operates in the capacitive mode that decrease the net reactance of the line in turn increases the real power capacity of the line. Similarly the SVC is connected to the bus no.1 with the size of 14.0863 MVAR. Here SVC operates in the inductive mode to control bus reactive power within the limits to increase power transfer capacity. The above combined TCSC and SVC placement in enhancement of load value is shown in <xref ref-type="fig" rid="fig1">Figure 1</xref> by comparing the load value of</p><table-wrap id="table3" ><label><xref ref-type="table" rid="table3">Table 3</xref></label><caption><title> FFA based maximum loadability comparison result of IEEE 57 Bus system</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Algorithm</th><th align="center" valign="middle" >Maximum Loadability in p.u</th><th align="center" valign="middle" >Critical Voltage</th><th align="center" valign="middle" >Total Incremental System Load from Base Case in %</th><th align="center" valign="middle" >Optimal SVC Bus No.</th><th align="center" valign="middle" >Optimal TCSC Line</th><th align="center" valign="middle" >SVC in MVAR</th><th align="center" valign="middle" >X<sub>TCSC</sub> in p.u</th></tr></thead><tr><td align="center" valign="middle" >Base Case</td><td align="center" valign="middle" >12.508</td><td align="center" valign="middle" >0.936 @ 31bus</td><td align="center" valign="middle" ></td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td></tr><tr><td align="center" valign="middle" >PSO [<xref ref-type="bibr" rid="scirp.69870-ref7">7</xref>]</td><td align="center" valign="middle" >14.039</td><td align="center" valign="middle" >Not Mentioned</td><td align="center" valign="middle" >12.2401</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td></tr><tr><td align="center" valign="middle" >HPSO [<xref ref-type="bibr" rid="scirp.69870-ref7">7</xref>]</td><td align="center" valign="middle" >14.062</td><td align="center" valign="middle" >Not Mentioned</td><td align="center" valign="middle" >12.4240</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td></tr><tr><td align="center" valign="middle" >FFA without FACTS</td><td align="center" valign="middle" >14.134</td><td align="center" valign="middle" >0.9221 @ 31bus</td><td align="center" valign="middle" >12.9996</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td></tr><tr><td align="center" valign="middle" >FFA with FACTS</td><td align="center" valign="middle" >14.301</td><td align="center" valign="middle" >0.9340 @ 31bus</td><td align="center" valign="middle" >14.3348</td><td align="center" valign="middle" >44</td><td align="center" valign="middle" >[44 45]</td><td align="center" valign="middle" >25.715 (Capacitive Mode)</td><td align="center" valign="middle" >0.0045 (Inductive Mode)</td></tr></tbody></table></table-wrap><table-wrap id="table4" ><label><xref ref-type="table" rid="table4">Table 4</xref></label><caption><title> Statistical performance comparison of FFA for IEEE 57 Bus system</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Method</th><th align="center" valign="middle" >Worst</th><th align="center" valign="middle" >Mean</th><th align="center" valign="middle" >Best</th><th align="center" valign="middle" >Standard Deviation</th><th align="center" valign="middle" >No of Iteration</th></tr></thead><tr><td align="center" valign="middle" >PSO</td><td align="center" valign="middle" >13.8</td><td align="center" valign="middle" >14.0296</td><td align="center" valign="middle" >14.039</td><td align="center" valign="middle" >0.0278</td><td align="center" valign="middle" >39</td></tr><tr><td align="center" valign="middle" >HPSO</td><td align="center" valign="middle" >13.92</td><td align="center" valign="middle" >14.0555</td><td align="center" valign="middle" >14.062</td><td align="center" valign="middle" >0.0211</td><td align="center" valign="middle" >29</td></tr><tr><td align="center" valign="middle" >FFA</td><td align="center" valign="middle" >14.04369</td><td align="center" valign="middle" >14.1218</td><td align="center" valign="middle" >14.13427</td><td align="center" valign="middle" >0.015</td><td align="center" valign="middle" >21</td></tr></tbody></table></table-wrap><table-wrap id="table5" ><label><xref ref-type="table" rid="table5">Table 5</xref></label><caption><title> Statistical performance comparison of FFA for IEEE 118 Bus system</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Method</th><th align="center" valign="middle" >Worst</th><th align="center" valign="middle" >Mean</th><th align="center" valign="middle" >Best</th><th align="center" valign="middle" >SD</th><th align="center" valign="middle" >No of Iteration</th></tr></thead><tr><td align="center" valign="middle" >DE</td><td align="center" valign="middle" >54.4993</td><td align="center" valign="middle" >56.2432</td><td align="center" valign="middle" >56.6212</td><td align="center" valign="middle" >0.6999</td><td align="center" valign="middle" >18</td></tr><tr><td align="center" valign="middle" >DE-PSO</td><td align="center" valign="middle" >56.2189</td><td align="center" valign="middle" >56.4966</td><td align="center" valign="middle" >57.0156</td><td align="center" valign="middle" >0.27</td><td align="center" valign="middle" >15</td></tr><tr><td align="center" valign="middle" >FFA</td><td align="center" valign="middle" >56.18822</td><td align="center" valign="middle" >57.2121</td><td align="center" valign="middle" >57.32037904</td><td align="center" valign="middle" >0.1935</td><td align="center" valign="middle" >22</td></tr></tbody></table></table-wrap><fig id="fig1"  position="float"><label><xref ref-type="fig" rid="fig1">Figure 1</xref></label><caption><title> Modified IEEE 30 Bus system load value comparison</title></caption><graphic mimetype="image"   position="float"  xlink:type="simple"  xlink:href="http://html.scirp.org/file/23-7600929x61.png"/></fig><table-wrap id="table6" ><label><xref ref-type="table" rid="table6">Table 6</xref></label><caption><title> FFA based maximum loadability comparison result of IEEE 118 Bus system</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Algorithm</th><th align="center" valign="middle" >Maximum Loadability in p.u</th><th align="center" valign="middle" >Critical Voltage</th><th align="center" valign="middle" >Total Incremental System Load from Base Case in %</th><th align="center" valign="middle" >Optimal SVC Bus No.</th><th align="center" valign="middle" >Optimal TCSC Line</th><th align="center" valign="middle" >SVC in MVAR</th><th align="center" valign="middle" >X<sub>TCSC</sub> in p.u</th></tr></thead><tr><td align="center" valign="middle" >Base Case</td><td align="center" valign="middle" >42.42</td><td align="center" valign="middle" >0.946 @ 53bus</td><td align="center" valign="middle" ></td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td></tr><tr><td align="center" valign="middle" >DE [<xref ref-type="bibr" rid="scirp.69870-ref11">11</xref>]</td><td align="center" valign="middle" >56.6212</td><td align="center" valign="middle" >Not Mentioned</td><td align="center" valign="middle" >33.4776</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td></tr><tr><td align="center" valign="middle" >DEPSO [<xref ref-type="bibr" rid="scirp.69870-ref11">11</xref>]</td><td align="center" valign="middle" >57.076</td><td align="center" valign="middle" >Not Mentioned</td><td align="center" valign="middle" >34.5497</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td></tr><tr><td align="center" valign="middle" >FFA without FACTS</td><td align="center" valign="middle" >57.32</td><td align="center" valign="middle" >0.9397 @ 53bus</td><td align="center" valign="middle" >35.1249</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td><td align="center" valign="middle" >-</td></tr><tr><td align="center" valign="middle" >FFA with FACTS</td><td align="center" valign="middle" >57.57</td><td align="center" valign="middle" >0.9412 @ 53bus</td><td align="center" valign="middle" >35.7142</td><td align="center" valign="middle" >79</td><td align="center" valign="middle" >[79 80]</td><td align="center" valign="middle" >19.086 (Inductive Mode)</td><td align="center" valign="middle" >0.03930 (Capacitive Mode)</td></tr></tbody></table></table-wrap><p>FFA without FACTS and base case. By comparing fourth and fifth row of <xref ref-type="table" rid="table1">Table 1</xref> it is inferred that the FFA with maximum loading point increased with percentage of 6.6206 from the FFA without FACTS.</p><p>The Convergence Graph of FFA with FACTS and without FACTS has been shown in <xref ref-type="fig" rid="fig2">Figure 2</xref> for the Modified IEEE 30 Bus system.</p><p>In IEEE 57 Bus system, the SVC has been placed on the bus no.44 with the size of 25.715 MVAR. Here the SVC operates in capacitive mode it increases the voltage level of the Bus system which in turn increases the power flow capacity of transmission line. The above voltage level enhancement is shown in <xref ref-type="fig" rid="fig3">Figure 3</xref> by comparing the voltage level of each bus in the FFA with FACTS and without FACTS devices.</p><p>The increase in the voltage level of the bus may affect the power flow controllability of the system in turn affects the loading capacity of the load. The power flow controllability of the system is maintained by the placement of TCSC at the transmission line connected between the bus no.44 and bus no.45. <xref ref-type="fig" rid="fig4">Figure 4</xref> shows that the each load value of the system based on the FFA with FACTS devices has been compared with the FFA without FACTS and base case. From the recorded value in the fourth and fifth row of <xref ref-type="table" rid="table3">Table 3</xref> it is concluded that FFA with FACTS devices based total load value of the system has 1.3352 percentages more than the FFA without FACTS device.</p><p>The convergence graph of FFA with FACTS and without FACTS has been shown in <xref ref-type="fig" rid="fig5">Figure 5</xref> for the Modified IEEE 57 Bus system.</p><p>In the IEEE 118 Bus system, the SVC has been placed on the bus no. 79 and TCSC has been placed on the</p><fig id="fig2"  position="float"><label><xref ref-type="fig" rid="fig2">Figure 2</xref></label><caption><title> FFA convergence graph of IEEE 30 Bus system</title></caption><graphic mimetype="image"   position="float"  xlink:type="simple"  xlink:href="http://html.scirp.org/file/23-7600929x62.png"/></fig><fig id="fig3"  position="float"><label><xref ref-type="fig" rid="fig3">Figure 3</xref></label><caption><title> FFA based IEEE 57 bus voltage comparison</title></caption><graphic mimetype="image"   position="float"  xlink:type="simple"  xlink:href="http://html.scirp.org/file/23-7600929x63.png"/></fig><fig id="fig4"  position="float"><label><xref ref-type="fig" rid="fig4">Figure 4</xref></label><caption><title> IEEE 57 Bus system load value comparison</title></caption><graphic mimetype="image"   position="float"  xlink:type="simple"  xlink:href="http://html.scirp.org/file/23-7600929x64.png"/></fig><fig id="fig5"  position="float"><label><xref ref-type="fig" rid="fig5">Figure 5</xref></label><caption><title> FFA convergence graph of IEEE 57 Bus systems</title></caption><graphic mimetype="image"   position="float"  xlink:type="simple"  xlink:href="http://html.scirp.org/file/23-7600929x65.png"/></fig><p>transmission line connected between the bus no.79 and bus no.80. Here the SVC operates in inductive mode and TCSC operates in capacitive mode. Each load value of the system using FFA with FACTS has been compared with the base case and FFA without FACTS and it is shown in <xref ref-type="fig" rid="fig6">Figure 6</xref>. Total load utilization capacity of the system using FFA with FACTS is increased to 0.584 percentages than the FFA without FACTS as per inference from the fourth and fifth row of <xref ref-type="table" rid="table3">Table 3</xref>.</p><p>The Convergence Graph of FFA with FACTS and without FACTS has been shown in <xref ref-type="fig" rid="fig7">Figure 7</xref> for the Modified IEEE 118 Bus system respectively.</p></sec><sec id="s4_3"><title>4.3. Strategy3: Effectiveness of FACTS Devices in Severe Line Contingency</title><p>In a power system, the contingencies may be due to the outage of transmission lines or generators. Since in a practical power system, the possibility of transmission line outage is very high compared to that of generator outage hence it is necessary to calculate the maximum loadability point at a transmission line contingency. Considering the above subject matter, system’s maximum loadability point is determined by creating a transmission line outage for each test systems in this strategy.</p><p>Consider a transmission line connected between bus no.19 and bus no. 20 in modified IEEE 30 Bus system has been assumed to be tripped. The tripped transmission line outage decreases the voltage level to 0.9492 p.u and 0.9384 p.u at bus no. 18 and bus no. 19 respectively. The decreased voltages violate the system since the minimum system bus voltage limit is 0.95 p.u. FFA based optimal placement of SVC on bus no.15 with the size of 17.4309 MW and TCSC operates in the inductive mode with the X<sub>TCSC</sub> of 0.0123 p.u added to the transmission line connected between bus no. 15 and bus no.18 provide the solutions to determine the maximum loadability point by limiting all the bus voltage within the limits of 0.95 and 1.05 p.u. The above is illustrated in the comparison voltage graph between base case and FFA with FACTS in the contingency state shown in <xref ref-type="fig" rid="fig8">Figure 8</xref>. The maximum loading point of 2.714p.u is obtained at the assumed line outage and it is recorded in the first row of <xref ref-type="table" rid="table7">Table 7</xref>.</p><p>In IEEE 57 Bus system, a transmission line between bus no.9 and bus no.12 has been assumed to be tripped. The above line outage increases the reactive power of generator bus no. 9 to 17.4693 MVAR in the base case. Here the system gets violated since the reactive power maximum limit of generator bus no. 9 is 9MVAR.The FFA based optimal placement of SVC on bus no 24 and TCSC on the transmission line connected between bus no 24 and bus no 26 provide the solution to determine the maximum loadability point by limiting the generator bus no. 9 reactive power to 8.4413 MVAR and also the other system control variables within the limit. Here the SVC operates in capacitive mode with the size of 58.5261 MVAR and TCSC operates in inductive mode with the X<sub>TCSC</sub> of 0.0084 p.u added to the line. The maximum loading point of 14.1135 p.u is obtained at the assumed line outage and it is recorded in the second row of <xref ref-type="table" rid="table7">Table 7</xref>. The voltage graph of the IEEE 57 Bus system at</p><fig id="fig6"  position="float"><label><xref ref-type="fig" rid="fig6">Figure 6</xref></label><caption><title> IEEE 118 Bus system load value comparison</title></caption><graphic mimetype="image"   position="float"  xlink:type="simple"  xlink:href="http://html.scirp.org/file/23-7600929x66.png"/></fig><fig id="fig7"  position="float"><label><xref ref-type="fig" rid="fig7">Figure 7</xref></label><caption><title> FFA convergence graph of IEEE 118 Bus systems</title></caption><graphic mimetype="image"   position="float"  xlink:type="simple"  xlink:href="http://html.scirp.org/file/23-7600929x67.png"/></fig><fig id="fig8"  position="float"><label><xref ref-type="fig" rid="fig8">Figure 8</xref></label><caption><title> FFA based IEEE 30 bus voltage comparison in the contingency state</title></caption><graphic mimetype="image"   position="float"  xlink:type="simple"  xlink:href="http://html.scirp.org/file/23-7600929x68.png"/></fig><p>the base case line outage and the FFA with FACTS based line outage is shown in <xref ref-type="fig" rid="fig9">Figure 9</xref>. From <xref ref-type="fig" rid="fig9">Figure 9</xref> it is inferred that the optimal placement of FACTS increases the voltage profile of almost all the Bus system at the line outage.</p><p>Similar like modified IEEE 30 Bus system and IEEE 57 system, a transmission line between bus no. 69 and bus no. 75 has been assumed to be tripped in IEEE 118 Bus system. The tripped transmission line outage causes the system violation since the reactive power of the bus no.32 is increased to 17.5 MVAR compared to the maximum limit of 17 MVAR at bus no. 32. This reactive power violation has been brought into control by optimally placing the SVC at bus no.17 with the size of 29.4520MVAR and TCSC operates in the inductive mode with the <inline-formula><inline-graphic xlink:href="http://html.scirp.org/file/23-7600929x69.png" xlink:type="simple"/></inline-formula> of 0.0080 p.u added to the transmission line connected between bus no. 17 and bus no. 113 provide the solutions to determine the maximum loadability point by limiting the reactive power at bus no. 32 as 3.9 MVAR and other system limits. The maximum loading point of 54.512 p.u is obtained at the assumed line outage and it is recorded in the third row of <xref ref-type="table" rid="table7">Table 7</xref>. The voltage graph of the IEEE 118 Bus system at the base case line outage and the FFA with FACTS based line outage is shown in <xref ref-type="fig" rid="fig1">Figure 1</xref>0.</p><p>The loading value of each bus in the three test system using FFA based optimal placement of FACTS devices in the contingency state has given in <xref ref-type="fig" rid="fig1">Figure 1</xref>1.</p><fig id="fig9"  position="float"><label><xref ref-type="fig" rid="fig9">Figure 9</xref></label><caption><title> FFA based IEEE 57 bus voltage comparison in the contingency state</title></caption><graphic mimetype="image"   position="float"  xlink:type="simple"  xlink:href="http://html.scirp.org/file/23-7600929x70.png"/></fig><fig id="fig10"  position="float"><label><xref ref-type="fig" rid="fig1">Figure 1</xref>0</label><caption><title> FFA based IEEE 118 bus voltage comparison in the contingency state</title></caption><graphic mimetype="image"   position="float"  xlink:type="simple"  xlink:href="http://html.scirp.org/file/23-7600929x71.png"/></fig><fig id="fig11"  position="float"><label><xref ref-type="fig" rid="fig1">Figure 1</xref>1</label><caption><title> FFA with FACTS based load bus value of the test system in the contingency state</title></caption><graphic mimetype="image"   position="float"  xlink:type="simple"  xlink:href="http://html.scirp.org/file/23-7600929x72.png"/></fig><table-wrap id="table7" ><label><xref ref-type="table" rid="table7">Table 7</xref></label><caption><title> FFA with FACTS based maximum loading point in a line contingency state</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >FFA With SVC and TCSC at a Line Contingency State</th><th align="center" valign="middle" >Transmission Line Outage [Sending Receiving End Bus]</th><th align="center" valign="middle" >Maximum Loadability in p.u</th><th align="center" valign="middle" >Critical Voltage in p.u @ bus</th><th align="center" valign="middle" >Optimal SVC Bus No.</th><th align="center" valign="middle" >Optimal TCSC Line</th><th align="center" valign="middle" >SVC in MVAR</th><th align="center" valign="middle" >X<sub>TCSC</sub> in p.u</th></tr></thead><tr><td align="center" valign="middle" >IEEE 30 Bus System</td><td align="center" valign="middle" >[18 19]</td><td align="center" valign="middle" >2.714</td><td align="center" valign="middle" >0.9501 @ 8</td><td align="center" valign="middle" >15</td><td align="center" valign="middle" >[15 18]</td><td align="center" valign="middle" >17.4309</td><td align="center" valign="middle" >0.0123</td></tr><tr><td align="center" valign="middle" >IEEE 57 Bus System</td><td align="center" valign="middle" >[9 12]</td><td align="center" valign="middle" >14.11</td><td align="center" valign="middle" >0.9758 @ 1</td><td align="center" valign="middle" >24</td><td align="center" valign="middle" >[24 26]</td><td align="center" valign="middle" >58.5261</td><td align="center" valign="middle" >0.0084</td></tr><tr><td align="center" valign="middle" >IEEE 118 Bus System</td><td align="center" valign="middle" >[69 75]</td><td align="center" valign="middle" >54.512</td><td align="center" valign="middle" >0.9392 @ 53</td><td align="center" valign="middle" >17</td><td align="center" valign="middle" >[17 113]</td><td align="center" valign="middle" >29.4520</td><td align="center" valign="middle" >0.0080</td></tr></tbody></table></table-wrap></sec></sec><sec id="s5"><title>5. Conclusion</title><p>In this work, maximum loadability point determination using Firefly Algorithm is implemented in modified IEEE 30 Bus system, IEEE 57 Bus System and IEEE 118 Bus system. The results of Firefly algorithm provides better maximum loading point compared to the other evolutionary algorithm. It is evident from the convergence characteristics that the FFA provides better balance between the exploration and exploitation process at the faster convergence rate. The FACTS devices involvement of TCSC and SVC in determining the maximum loading point enhances the load utilization point in normal state and also helps to overcome the system violation in transmission line contingency state. Overall, the firefly algorithm in determining the maximum loadability point and its enhancement with the help of FACTS provides better search capability and also enriches the system load utilization capacity by maintaining the system security level.</p></sec><sec id="s6"><title>Cite this paper</title><p>S. Rajasekaran,Dr. S. Muralidharan, (2016) Firefly Algorithm in Determining Maximum Load Utilization Point and Its Enhancement through Optimal Placement of FACTS Device. Circuits and Systems,07,3081-3094. doi: 10.4236/cs.2016.710262</p></sec></body><back><ref-list><title>References</title><ref id="scirp.69870-ref1"><label>1</label><mixed-citation publication-type="other" xlink:type="simple">Ajjarapu, V. and Christy, C. (1992) The Continuation Power Flow: A Tool for Steady State Voltage Stability Analysis. IEEE Transactions on Power Systems, 7, 416-423. http://dx.doi.org/10.1109/59.141737</mixed-citation></ref><ref id="scirp.69870-ref2"><label>2</label><mixed-citation publication-type="other" xlink:type="simple">Irisarri, G.D., Wang, X., Tong, J. and Mokhtari, S. (1997) Maximum Loadability of Power Systems Using Interior Point Nonlinear Optimization Method. IEEE Transactions on Power Systems, 12, 162-172. http://dx.doi.org/10.1109/59.574936</mixed-citation></ref><ref id="scirp.69870-ref3"><label>3</label><mixed-citation publication-type="other" xlink:type="simple">Schlueter, R.V. (1998) A Voltage Stability Security Assessment Method. IEEE Transactions on Power Systems, 13, No. 4. http://dx.doi.org/10.1109/59.736286</mixed-citation></ref><ref id="scirp.69870-ref4"><label>4</label><mixed-citation publication-type="other" xlink:type="simple">Chiang, H.D. and Jean-Jumeau, R. (1995) A More Efficient Formulation for Computation of the Maximum Loading Points in Electric Power Systems. IEEE Transactions on Power Systems, 10, 635-646. http://dx.doi.org/10.1109/59.387898</mixed-citation></ref><ref id="scirp.69870-ref5"><label>5</label><mixed-citation publication-type="other" xlink:type="simple">Yoshida, H., Kawata, K., Fukuyama, Y., Takayama, S. and Nakanishi, Y. (2000) A Particle Swarm Optimization for Reactive Power and Voltage control Considering Voltage Security Assessment. IEEE Transactions on Power Systems, 15, 1232-1239. http://dx.doi.org/10.1109/59.898095</mixed-citation></ref><ref id="scirp.69870-ref6"><label>6</label><mixed-citation publication-type="other" xlink:type="simple">EL-Dib, A.A., Youssef, H.K.M., EL-Metwally, M.M. and Osrnan, Z. (2006) Maximum Loadability of Power Systems Using Hybrid Particle Swarm Optimization. Electric Power Systems Research, 76, 485-492. http://dx.doi.org/10.1016/j.epsr.2005.05.011</mixed-citation></ref><ref id="scirp.69870-ref7"><label>7</label><mixed-citation publication-type="other" xlink:type="simple">Shunmugalatha, A. and Mary Raja Slochanal, S. (2008) Optimum Cost of Generation for Maximum Loadability Limit of Power System Using Hybrid Particle Swarm Optimization. International Journal of Electrical Power &amp; Energy Systems, 30, 486-490. http://dx.doi.org/10.1016/j.ijepes.2008.04.001</mixed-citation></ref><ref id="scirp.69870-ref8"><label>8</label><mixed-citation publication-type="other" xlink:type="simple">Shunmugalatha, A. and Mary Raja Slochanal, S. (2008) Maximum Loadability of a Power System Using Multi Agent- Based Hybrid Particle Swarm Optimization. Electric Power Components and Systems, 36, 575-586. http://dx.doi.org/10.1080/15325000701801579</mixed-citation></ref><ref id="scirp.69870-ref9"><label>9</label><mixed-citation publication-type="other" xlink:type="simple">Arya, L.D., Choube, S.C., Shrivastava, M. and Kothari, D.P. (2010) Loadability Margin Enhancement Using Co-Ordinated Aggregation Based Particle Swarm Optimization (CAPSO). International Journal of Electrical Power &amp; Energy Systems, 32, 975-984. http://dx.doi.org/10.1016/j.ijepes.2010.02.007</mixed-citation></ref><ref id="scirp.69870-ref10"><label>10</label><mixed-citation publication-type="other" xlink:type="simple">Cai, H.R., Chung, C.Y. and Wong, K.P. (2008) Application of Differential Evolution Algorithm for Transient Stability Constrained Optimal Power Flow. IEEE Transactions on Power Systems, 23, 719-728. http://dx.doi.org/10.1109/TPWRS.2008.919241</mixed-citation></ref><ref id="scirp.69870-ref11"><label>11</label><mixed-citation publication-type="other" xlink:type="simple">Gnanambal, K. and Babulal, C.K. (2012) Maximum Loadability Limit of Power System Using Hybrid Differential Evolution with Particle Swarm Optimization. Electrical Power and Energy Systems, 43, 150-155.</mixed-citation></ref><ref id="scirp.69870-ref12"><label>12</label><mixed-citation publication-type="other" xlink:type="simple">Yang, X.S. (2008) Nature-Inspired Metaheuristic Algorithms. Luniver Press, UK.</mixed-citation></ref><ref id="scirp.69870-ref13"><label>13</label><mixed-citation publication-type="other" xlink:type="simple">Yang, X.S. (2013) Multiobjective Fire?y Algorithm for Continuous Optimization. Engineering with Computers, 29, 175-184. http://dx.doi.org/10.1007/s00366-012-0254-1 </mixed-citation></ref><ref id="scirp.69870-ref14"><label>14</label><mixed-citation publication-type="book" xlink:type="simple">Yang, X.S. (2010) Fire?y Algorithm, Levy Flights and Global Optimization. In: Bramer, M., Ellis, R. and Petridis, M., Eds., Research and Development in Intelligent Systems XXVI, Springer, London, 209-218. http://dx.doi.org/10.1007/978-1-84882-983-1_15 </mixed-citation></ref><ref id="scirp.69870-ref15"><label>15</label><mixed-citation publication-type="other" xlink:type="simple">Hingorani, N.G. (1993) Flexible AC transmission. IEEE Spectrum, 30, 40-45. http://dx.doi.org/10.1109/6.206621</mixed-citation></ref><ref id="scirp.69870-ref16"><label>16</label><mixed-citation publication-type="other" xlink:type="simple">Padhy, N.P. and Abdel Moamen, M.A. (2005) Power Flow Control and Solutions with Multiple and Multi-Type FACTS Devices. Electric Power Systems Research, 74, 341-351. http://dx.doi.org/10.1016/j.epsr.2004.10.010</mixed-citation></ref><ref id="scirp.69870-ref17"><label>17</label><mixed-citation publication-type="other" xlink:type="simple">Saravanan, M., Slochanal, S.M.R., Venkatesh, P. and Abraham, J.P.S. (2007) Application of Particle Swarm Optimization Technique for Optimal Location of FACTS Devices Considering Cost of Installation and System Loadability. Electric Power Systems Research, 77, 276-283. http://dx.doi.org/10.1016/j.epsr.2006.03.006</mixed-citation></ref><ref id="scirp.69870-ref18"><label>18</label><mixed-citation publication-type="other" xlink:type="simple">Nabavi, S.M.H., Kazemi, A. and Masoum, M.A.S. (2012) Social Welfare Maximization with Fuzzy Based Genetic Algorithm by TCSC and SSSC in Double-Sided Auction Market. Scientia Iranica, 19, 745-758.</mixed-citation></ref><ref id="scirp.69870-ref19"><label>19</label><mixed-citation publication-type="other" xlink:type="simple">Tiwari, P.K. and Sood, Y.R. (2013) An Efficient Approach for Optimal Allocation and Parameters Determination of TCSC with Investment Cost Recovery under Competitive Power Market. IEEE Transactions on Power Systems, 28, 2475-2484.</mixed-citation></ref><ref id="scirp.69870-ref20"><label>20</label><mixed-citation publication-type="other" xlink:type="simple">Zimmerman, R.D., Murillo-Sanchez, C.E. and Gan, D. (2006) MATPOWER: Matpower 6.0b1 User’s Manual, Power Systems Engineering Research Center (PSerc).</mixed-citation></ref></ref-list></back></article>