<?xml version="1.0" encoding="UTF-8"?><!DOCTYPE article  PUBLIC "-//NLM//DTD Journal Publishing DTD v3.0 20080202//EN" "http://dtd.nlm.nih.gov/publishing/3.0/journalpublishing3.dtd"><article xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink" dtd-version="3.0" xml:lang="en" article-type="research article"><front><journal-meta><journal-id journal-id-type="publisher-id">JEMAA</journal-id><journal-title-group><journal-title>Journal of Electromagnetic Analysis and Applications</journal-title></journal-title-group><issn pub-type="epub">1942-0730</issn><publisher><publisher-name>Scientific Research Publishing</publisher-name></publisher></journal-meta><article-meta><article-id pub-id-type="doi">10.4236/jemaa.2013.58050</article-id><article-id pub-id-type="publisher-id">JEMAA-35487</article-id><article-categories><subj-group subj-group-type="heading"><subject>Articles</subject></subj-group><subj-group subj-group-type="Discipline-v2"><subject>Engineering</subject><subject> Physics&amp;Mathematics</subject></subj-group></article-categories><title-group><article-title>
 
 
  Investigation of Ground Frequency Characteristics
 
</article-title></title-group><contrib-group><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>ohamed</surname><given-names>Nayel</given-names></name><xref ref-type="aff" rid="aff1"><sub>1</sub></xref><xref ref-type="corresp" rid="cor1"><sup>*</sup></xref></contrib></contrib-group><aff id="aff1"><label>1</label><addr-line>Electrical Engineering Department, Assiut University, Assiut, Egypt</addr-line></aff><author-notes><corresp id="cor1">* E-mail:<email>m_a_niel@yahoo.com</email></corresp></author-notes><pub-date pub-type="epub"><day>06</day><month>08</month><year>2013</year></pub-date><volume>05</volume><issue>08</issue><fpage>322</fpage><lpage>327</lpage><history><date date-type="received"><day>April</day>	<month>8th,</month>	<year>2013</year></date><date date-type="rev-recd"><day>May</day>	<month>15th,</month>	<year>2013</year>	</date><date date-type="accepted"><day>July</day>	<month>1st,</month>	<year>2013</year></date></history><permissions><copyright-statement>&#169; Copyright  2014 by authors and Scientific Research Publishing Inc. </copyright-statement><copyright-year>2014</copyright-year><license><license-p>This work is licensed under the Creative Commons Attribution International License (CC BY). http://creativecommons.org/licenses/by/4.0/</license-p></license></permissions><abstract><p>
 
 
   Four-electrode method is one of the well-known methods in measuring ground resistivity. But, most faults currents and lightning currents have high frequencies components. It is proposed to develop this method to study ground frequency characteristics. A step like current was injected into ground to measure the ground impedance. The ground impedance is assumed to be frequency dependent parallel resistance/capacitance. Two equations were proved to estimate ground resistivity and permittivity from four-electrode method. An analytical model was proposed to model studied cases. The four electrodes are divided to equal spheres and complex image method had been used to satisfy the boundary conditions and penetration depth effects. The calculated results show good agreement with the measured results. 
 
</p></abstract><kwd-group><kwd>Ground; Transient; Four Electrode Method; Frequency; Impedance</kwd></kwd-group></article-meta></front><body><sec id="s1"><title>1. Introduction</title><p>When designing a grounding system for a specific performance objective, it is necessary to accurately measure the ground resistivity of the site where the ground is to be installed. Grounding system design is an engineering process that removes the guesswork and “art” out of grounding. It allows grounding to be done “right, the first time”. The result is a cost savings by avoiding change orders and ground “enhancements” [<xref ref-type="bibr" rid="scirp.35487-ref1">1</xref>].</p><p>The ground impedance frequency characteristic plays an important role in understanding and designing grounding systems. To investigate this issue, samples of ground are tested in laboratories [2,3]. The characteristics of these samples will be changed due to ground excavation, temperature and humidity. There are other methods used in prediction of ground parameters and it depends on electromagnetic wave transmitted and reflected from ground or grounding system analysis [4,5].</p><p>Grounding resistivity measuring methods depend on injecting a current through the ground via the probe electrodes. The current flowing through the ground (a resistive material) develops a voltage/potential difference. There are different methods [6,7] such as, four electrode method, deep electrode method and two electrode method to measure and obtain ground resistivity. The most accurate method in practice of measuring the average resistivity of large volumes of undisturbed earth is the four-electrode method. The electrode configurations commonly used for ground resistivity measurements are the Wenner and Schlumberger, illustrated in Figures 1(a) and (b), respectively. Approximating the current electrodes by hemispheres, the apparent soil resistivity ρ<sub>app </sub>can be computed using the following Equations [<xref ref-type="bibr" rid="scirp.35487-ref1">1</xref>]:</p><p>Wenner Method:<img src="2-9801461\96ccdd64-4983-4c43-bbdd-956ce2499da4.jpg" /> &#160;&#160;&#160;&#160;&#160;&#160;&#160;&#160;&#160;&#160;(1)</p><p>Schlumberger Method:<img src="2-9801461\ccab27bf-83b5-4169-8f9d-dcb9f536f736.jpg" /> &#160;&#160;&#160;&#160;(2)</p><p>When the adjacent current and potential electrodes are close together, the measured ground resistivity is indicative of surface ground characteristics. When the electrodes are far apart, the measured ground resistivity is indicative of average deep ground characteristics throughout a much larger area.</p><p>This paper studies the frequency dependence of ground impedance by injecting a step like current in outer electrode of four electrodes method. By using successive image method, four electrodes are modeled in ground with permittivity and conductivity parameter of ground. The ground impedance by the proposed method is studied for different ground parameters and different frequencies.</p></sec><sec id="s2"><title>2. Experimental Setup</title><p>The ground resistivity and permittivity is obtained from measured voltage and current waveforms due to wave propagation in the ground to study the effect of frequency.</p><p><xref ref-type="fig" rid="fig2">Figure 2</xref>(a) illustrates an experimental setup of four electrode method for ground impedance measuring. A step-like current of 20 nsec rise time is injected from a pulse generator (PG) of 500V. The pulse generator injects the current as charge/discharge cable, so, the injected current is not equal to return current. The four electrode method needs to inject current in outer electrode and return the same current from the other side outer electrode. To overcome the unbalance of pulse generator and connection cable a balance transformer. <xref ref-type="fig" rid="fig2">Figure 2</xref>(b), is used to convert unbalance current/voltage to balance current/voltage at high frequency. The balance transformer is connected at the end of connected cable to the pulse generator as shown in <xref ref-type="fig" rid="fig2">Figure 2</xref>(a). The current is measured by a CT (Peason model 2877, bandwidth from 300 Hz to 200 MHz), and recorded by a digital oscilloscope (Tektronix TDS 3054 m, bandwidth 500 MHz). Transient voltages were measured by a voltage probe (TEKTRONIX P6139A, bandwidth 500 MHz). The field measurements were carried out in Doshisha University yard site.</p><p>The current rise time 20 ns is injected for different distances between electrodes. Four electrodes are buried in the ground, as shown in <xref ref-type="fig" rid="fig1">Figure 1</xref>(a), all at depth 0.2 m and spaced (in a straight line) at intervals 2 m between the inner electrodes and 4 m between the outer electrodes.</p></sec><sec id="s3"><title>3. Measured Results</title><p>A current, as shown in <xref ref-type="fig" rid="fig3">Figure 3</xref>, is injected in electrode (C1) and collected from the outer electrodes (C2) and the two voltages of the two inner electrodes (P1 and P2) , as shown in <xref ref-type="fig" rid="fig4">Figure 4</xref>, are recorded with the oscilloscope.</p><p>The ground impedance is obtained from the measured voltages and currents (C1, C2, P1, P2). The four electrode method at low frequency is used to obtain the grounding resistance by dividing the potential difference</p><p>between two inner electrodes by the injected current at the outer electrodes as follows:</p><disp-formula id="scirp.35487-formula67840"><label>(3)</label><graphic position="anchor" xlink:href="2-9801461\99beab53-675c-4e7c-b3c3-853ea72ad2d4.jpg"  xlink:type="simple"/></disp-formula><p>Finally, complete content and organizational editing before formatting. Please take note of the following items when proofreading spelling and grammar:</p><p>Define abbreviations and acronyms the first time they are used in the text, even after they have been defined in the abstract. Abbreviations such as IEEE, SI, MKS, CGS, sc, dc, and rms do not have to be defined. Do not use abbreviations in the title or heads unless they are unavoidable.</p><p>In the same manner the ground impedance at different frequencies Z<sub>G</sub>(f) is obtained. The current at injected points to ground (C1, C2) is distorted due to the induced voltage between ground and connection wires. The voltage waveforms at any frequency (f) at inner electrodes are reformed to be as a result of current I by multiplying them V<sub>p</sub><sub>1</sub> and V<sub>p</sub><sub>2</sub> by I/I<sub>C</sub><sub>1</sub> and I/I<sub>C</sub><sub>2</sub> as follows:</p><disp-formula id="scirp.35487-formula67841"><label>(4)</label><graphic position="anchor" xlink:href="2-9801461\1047b2cf-0647-4bdb-a326-927891b044f2.jpg"  xlink:type="simple"/></disp-formula><p>The ground impedance is assumed to be consists of parallel resistance R<sub>G</sub>(f) and capacitance C<sub>G</sub>(f). From the obtained ground impedance Z<sub>G</sub>(f) the ground resistance and capacitance are obtained. The ground resistivity is obtained for non-equal four electrode method by the following equation:</p><disp-formula id="scirp.35487-formula67842"><label>(5)</label><graphic position="anchor" xlink:href="2-9801461\fb03a40d-12b9-49d4-aa40-75d3ca1d6e54.jpg"  xlink:type="simple"/></disp-formula><p>As <img src="2-9801461\38c90d39-2f13-4882-a3b4-ba4d4f4ad96b.jpg" /> the ground permittivity can be obtained.</p><disp-formula id="scirp.35487-formula67843"><label>(6)</label><graphic position="anchor" xlink:href="2-9801461\7d04f399-dda5-4a98-83da-6da6c7c9e4cb.jpg"  xlink:type="simple"/></disp-formula><p><xref ref-type="fig" rid="fig5">Figure 5</xref> shows the calculated ground impedance obtained from the measured results by using Equation (4) and calculated impedance by proposed model in next section. It shows good agreement between measured and calculated results and the dependence of grounding impedance on frequency.</p></sec><sec id="s4"><title>4. Numerical Model</title><sec id="s4_1"><title>4.1. Penetration Depth Effect</title><p>Assume a wave travels into a conducting medium [<xref ref-type="bibr" rid="scirp.35487-ref8">8</xref>]. Equation (7) is a solution of the wave equation for a plane wave traveling in the x direction in the conducting medium.</p><disp-formula id="scirp.35487-formula67844"><label>(7)</label><graphic position="anchor" xlink:href="2-9801461\5e2f5cfd-b398-4cd3-8c58-489e894714b4.jpg"  xlink:type="simple"/></disp-formula><p>where: d = penetration depth m.</p><p>It gives the variation of E<sub>y</sub> or J<sub>y</sub> in both magnitude and phase as a fuction of x. The electric field E<sub>y</sub> or current density J<sub>y</sub> deceases to 1/e (36.8%) of its initial value, while the wave penetrates to a distance d called penetration depth [<xref ref-type="bibr" rid="scirp.35487-ref8">8</xref>].</p><disp-formula id="scirp.35487-formula67845"><label>(8)</label><graphic position="anchor" xlink:href="2-9801461\008e3a2e-a040-41b6-b0dc-bbb99a03f621.jpg"  xlink:type="simple"/></disp-formula><p>where: f = frequency Hz, &#181; = ground permeability, s = ground conductivity.</p><p><xref ref-type="fig" rid="fig6">Figure 6</xref> shows the decay of the electric field E<sub>y</sub> or currrent density J<sub>y</sub> as a function of penetration depth, based on the magnitude of Equation (7). Integrating the absolute value of Equation (7) from x = 0 to ∞ results in E<sub>0</sub>/d or J<sub>0</sub>/d. Areas under step functional and exponential curve are equal when step function width is equal to the penetration depth [<xref ref-type="bibr" rid="scirp.35487-ref8">8</xref>] as shown in <xref ref-type="fig" rid="fig6">Figure 6</xref>.</p><p>It is assumed that all of injected current pass in the area of 1/e depth and the ground resistivity below the penetration depth is proposed to be infinity [<xref ref-type="bibr" rid="scirp.35487-ref9">9</xref>]. The successive image method shown in <xref ref-type="fig" rid="fig7">Figure 7</xref> is proposed to consider the penetration depth in homogenous ground. To make sure that all current pass in the area of 1/e depth, a two layer ground is assumed with a top layer of ground resistaivity r, permitivitty e and depth equal to penetration depth d. The bottom layer is assumed with resistivity = &#165;, permitivity = 0 and extended to infinity. The reflication coefficinet between the ground and air is assumed<img src="2-9801461\392a1773-e3c1-46bd-9f54-ca35b9c4f8a9.jpg" />. The bottom layer is assumed with resistivity = &#165;, permitivity = 0 and extended to infinity and its reflication coefficient with ground is assumed unity.</p><p>The analytical method used to calculate the surface potential profile of the four electrodes and grounding resistance/capacitance assumed each electrode driven into</p><p>the ground as a sphere. As electrode length is very short, each electrode is considered as equipotential surface. The relationship between the voltage and current can be written as:</p><disp-formula id="scirp.35487-formula67846"><label>(9)</label><graphic position="anchor" xlink:href="2-9801461\4fc1a490-f9c2-4f54-aeb0-d3607f8faa88.jpg"  xlink:type="simple"/></disp-formula><p>where I<sub>j</sub> is the current of the j<sup>th</sup> electrode (j = 1; 2; 3; 4), V<sub>i</sub> is the voltage of the j<sup>th</sup> electrode, Z<sub>mn</sub> is the mutual impedance element (i.e., mutual impedance between electrode number m and electrode number n), Z<sub>nn</sub> is the self-impedance of the n<sup>th</sup> sphere.</p><p>The elements of the impedance matrix are calculated as equal to:</p><disp-formula id="scirp.35487-formula67847"><label>(10)</label><graphic position="anchor" xlink:href="2-9801461\298a613d-8a2a-4bcf-8102-45662b512104.jpg"  xlink:type="simple"/></disp-formula><disp-formula id="scirp.35487-formula67848"><label>(11)</label><graphic position="anchor" xlink:href="2-9801461\809c1ef8-51bb-419a-8623-f69095d9fd43.jpg"  xlink:type="simple"/></disp-formula><p>where r<sub>mn</sub> is the distance between m<sup>th</sup> electrode and n<sup>th</sup> electrode, r<sub>mnp</sub><sub>1,2,3,4</sub> are the distances between the m<sup>th</sup> electrode and the image of the n<sup>th</sup> sphere and equal to:</p><p><img src="2-9801461\d5d2f471-0c95-44d3-a8d0-db818d6e7196.jpg" /></p><p><xref ref-type="fig" rid="fig8">Figure 8</xref> shows the varying of apparent ground impedance for e<sub>r</sub> = 10 and 50 and (a = 1 m, r = 1000 Ω&#215;m) with frequency. The apparent ground impedace decreases more sharbly as the ground relative permittivity increases. This is due to the decrease of the capacitive part of apparent ground impedance with the increase of apparent relative permittivity.</p><p><xref ref-type="fig" rid="fig9">Figure 9</xref> shows the varying of apparent ground impedance for r = 1000 and 500 Ω&#215;m and (a = 1 m, e<sub>r</sub> = 10) with frequency. The apparent ground impedances decreases as the ground resistivity decreases. This is due to the decrease of the decrease of gound resistance.</p></sec></sec></body><back><ref-list><title>References</title><ref id="scirp.35487-ref1"><label>1</label><mixed-citation publication-type="other" xlink:type="simple">IEEE Power &amp; Energy Society, “IEEE Draft Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Grounding System,” IEEE Standards 81-1983, 2012.</mixed-citation></ref><ref id="scirp.35487-ref2"><label>2</label><mixed-citation publication-type="other" xlink:type="simple">N. M. Nor, A. Haddad and H. Griffiths, “Performance of Earthing Systems of Low Resistivity Soils,” IEEE Transactions on Power Delivery, Vol. 21, No. 4, 2006, pp. 2039-2047. doi:10.1109/TPWRD.2006.874656</mixed-citation></ref><ref id="scirp.35487-ref3"><label>3</label><mixed-citation publication-type="other" xlink:type="simple">B. Anggoro, N. I. Sinisuka and P. M. Pakpahan, “Resistivity and Dielectric Constant Characteristic of Soil If are Treated by Water, Salt and Carbon,” 8th International Conference on Properties and Applications of Dielectric Materials, Bali, June 2006, pp. 893-896.</mixed-citation></ref><ref id="scirp.35487-ref4"><label>4</label><mixed-citation publication-type="other" xlink:type="simple">S. Visacro and R. Alipio, “Frequency Dependence of Soil Parameters: Experimental Results, Predicting Formula and Influence on the Lightning Response of Grounding Electrodes,” IEEE Transactions on Power Delivery, Vol. 27, No. 2, 2012, pp. 927-935.  
doi:10.1109/TPWRD.2011.2179070</mixed-citation></ref><ref id="scirp.35487-ref5"><label>5</label><mixed-citation publication-type="other" xlink:type="simple">A. G. Pedrosa, M. A. O. Shroeder, M. M. Afonso, R. S. Alípio, S. de Castro Assis, T. A. S. Oliveira and A. R. Braga, “Transient Response of Grounding Electrodes for the Frequency-Dependence of Soil Parameters,” 2010 IEEE/PES Transmission and Distribution Conference and Exposition: Latin America (T&amp;D-LA), Sao Paulo, 8-10 November 2010, pp. 839-845.</mixed-citation></ref><ref id="scirp.35487-ref6"><label>6</label><mixed-citation publication-type="other" xlink:type="simple">I. F. Gonos, A. X. Moronis and I. A. Stathopulos, “Variation of Soil Resistivity and Ground Resistance during the Year,” 28th International Conference on Lightning Protection, Kanazawa, 17-21 September 2006, pp. 740-744.</mixed-citation></ref><ref id="scirp.35487-ref7"><label>7</label><mixed-citation publication-type="other" xlink:type="simple">IEEE Power &amp; Energy Society, “IEEE Guide for Safety in AC Substation Grounding,” ANSI/IEEE Standard 80-2000, 2000.</mixed-citation></ref><ref id="scirp.35487-ref8"><label>8</label><mixed-citation publication-type="other" xlink:type="simple">F. Kraus, “Electromagnetics with Applications,” 5th Edition, McGraw-Hill, New York, 1999.</mixed-citation></ref><ref id="scirp.35487-ref9"><label>9</label><mixed-citation publication-type="other" xlink:type="simple">M. Nayel, “Investigation of Wave Propagation Penetration Depth in Multi-Layer Ground,” IEEJ Transactions on Power and Energy, Vol. 132, No. 8, 2012, pp. 1-6.  
doi:10.1541/ieejpes.132.728</mixed-citation></ref></ref-list></back></article>