<?xml version="1.0" encoding="UTF-8"?><!DOCTYPE article PUBLIC "-//NLM//DTD Journal Publishing DTD v3.0 20080202//EN" "http://dtd.nlm.nih.gov/publishing/3.0/journalpublishing3.dtd">
<article xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink" dtd-version="3.0" xml:lang="en" article-type="research article">
 <front>
  <journal-meta>
   <journal-id journal-id-type="publisher-id">
    jpee
   </journal-id>
   <journal-title-group>
    <journal-title>
     Journal of Power and Energy Engineering
    </journal-title>
   </journal-title-group>
   <issn pub-type="epub">
    2327-588X
   </issn>
   <issn publication-format="print">
    2327-5901
   </issn>
   <publisher>
    <publisher-name>
     Scientific Research Publishing
    </publisher-name>
   </publisher>
  </journal-meta>
  <article-meta>
   <article-id pub-id-type="doi">
    10.4236/jpee.2025.139012
   </article-id>
   <article-id pub-id-type="publisher-id">
    jpee-145728
   </article-id>
   <article-categories>
    <subj-group subj-group-type="heading">
     <subject>
      Articles
     </subject>
    </subj-group>
    <subj-group subj-group-type="Discipline-v2">
     <subject>
      Engineering
     </subject>
    </subj-group>
   </article-categories>
   <title-group>
    In-Service Distribution Transformer Health Index: Insights from Field Data
   </title-group>
   <contrib-group>
    <contrib contrib-type="author" xlink:type="simple">
     <name name-style="western">
      <surname>
       Imran Sutan
      </surname>
      <given-names>
       Chairul
      </given-names>
     </name> 
     <xref ref-type="aff" rid="aff1"> 
      <sup>1</sup>
     </xref>
    </contrib>
    <contrib contrib-type="author" xlink:type="simple">
     <name name-style="western">
      <surname>
       Sharin Ab
      </surname>
      <given-names>
       Ghani
      </given-names>
     </name> 
     <xref ref-type="aff" rid="aff1"> 
      <sup>1</sup>
     </xref>
    </contrib>
    <contrib contrib-type="author" xlink:type="simple">
     <name name-style="western">
      <surname>
       Fatin Nurkamilia
      </surname>
      <given-names>
       Kamaruddin
      </given-names>
     </name> 
     <xref ref-type="aff" rid="aff1"> 
      <sup>1</sup>
     </xref>
    </contrib>
    <contrib contrib-type="author" xlink:type="simple">
     <name name-style="western">
      <surname>
       Nur Syahida Akryl
      </surname>
      <given-names>
       Azam
      </given-names>
     </name> 
     <xref ref-type="aff" rid="aff2"> 
      <sup>2</sup>
     </xref>
    </contrib>
   </contrib-group> 
   <aff id="aff1">
    <addr-line>
     aElectrical Asset Condition Monitoring Research Group (e-AMCM), Faculty of Electrical Technology and Engineering (FTKE), Universiti Teknikal Malaysia Melaka (UTeM), Melaka, Malaysia
    </addr-line> 
   </aff> 
   <aff id="aff2">
    <addr-line>
     aTNB Labs Sdn. Bhd., Kajang, Malaysia
    </addr-line> 
   </aff> 
   <pub-date pub-type="epub">
    <day>
     29
    </day> 
    <month>
     08
    </month>
    <year>
     2025
    </year>
   </pub-date> 
   <volume>
    13
   </volume> 
   <issue>
    09
   </issue>
   <fpage>
    176
   </fpage>
   <lpage>
    185
   </lpage>
   <history>
    <date date-type="received">
     <day>
      28,
     </day>
     <month>
      August
     </month>
     <year>
      2025
     </year>
    </date>
    <date date-type="published">
     <day>
      15,
     </day>
     <month>
      August
     </month>
     <year>
      2025
     </year> 
    </date> 
    <date date-type="accepted">
     <day>
      15,
     </day>
     <month>
      September
     </month>
     <year>
      2025
     </year> 
    </date>
   </history>
   <permissions>
    <copyright-statement>
     © Copyright 2014 by authors and Scientific Research Publishing Inc. 
    </copyright-statement>
    <copyright-year>
     2014
    </copyright-year>
    <license>
     <license-p>
      This work is licensed under the Creative Commons Attribution International License (CC BY). http://creativecommons.org/licenses/by/4.0/
     </license-p>
    </license>
   </permissions>
   <abstract>
    This study introduces the Transformer Health Index (THI), which is derived from the weighted scores of Dissolved Gas Analysis (DGA), Oil Quality Analysis (OQA), and Furan Fraction Analysis (FFA). The assessment methods include the Duval Triangle for DGA, the Chendong model for FFA, and the evaluation of breakdown voltage, acidity, and water content for OQA. The THI was applied to 120 in-service distribution transformers rated at 30 MVA, 33/11 kV. Results indicate that transformers classified as “Good” scored high in both DGA and FFA, while those rated “Fair” exhibited lower FFA scores relative to DGA. Conversely, transformers labeled “Poor” showed lower DGA scores compared to FFA, and those in the “Very Poor” category scored low in both DGA and FFA. The impact of service duration on THI indicates that transformer condition generally worsens with age. However, some newer transformers showed signs of rapid deterioration, while certain older units maintained a satisfactory health status.
   </abstract>
   <kwd-group> 
    <kwd>
     Dissolved Gas Analysis
    </kwd> 
    <kwd>
      Oil Quality Analysis
    </kwd> 
    <kwd>
      Furfural Analysis
    </kwd> 
    <kwd>
      Transformer Health Index
    </kwd> 
    <kwd>
      Distribution Transformers
    </kwd>
   </kwd-group>
  </article-meta>
 </front>
 <body>
  <sec id="s1">
   <title>1. Introduction</title>
   <p>Transformers are among the critical and costly assets within electrical distribution networks, with failures capable of causing widespread outages and substantial economic impact. With increasing load and power consumption, utilities have been facing much difficulty in maintaining the ageing transformer fleets. As was brought up in a study <xref ref-type="bibr" rid="scirp.145728-1">
     [1]
    </xref>, degradation patterns might lead maintenance costs to rise beyond RM 39 million by 2034. This factor alone stresses the urgency of monitoring the health condition of transformers in order to optimize maintenance schedules and increase the longevity of transformers. Traditionally, transformer monitoring involves determining the condition of the transformer parts such as cellulose materials, enameled copper windings, steel cores, and silver components of on-load tap changers that regulate the turns ratio of transformers <xref ref-type="bibr" rid="scirp.145728-2">
     [2]
    </xref>-<xref ref-type="bibr" rid="scirp.145728-5">
     [5]
    </xref>. For instance, dissolved gas analysis is utilize for determine internal faults, oil quality analysis is use to check the state of insulating oil, and furan fraction analysis is employ to determine insulating paper deterioration.</p>
   <p>These well-established diagnostics are usually applied separately, resulting in perhaps uncoordinated evaluations that might miss important interplays between each other. For example, a transformer might be declared as in good condition from a DGA results but at the same time experience a severe degraded insulating paper. In other words, no single technique can comprehensively reflect the overall condition of transformer because each technique is applied independently. Hence, this study combines all three diagnostic approaches. Each diagnostic score works in order to complement each other to produce a Transformer Health Index (THI).</p>
   <p>Keep in mind that the proposed THI incorporates only Tier 1 data, including dissolved gas analysis (DGA), oil quality analysis (OQA), and furan fraction analysis (FFA). Data from Tier 2 (Transformer Turns-Ratio, Winding Resistance, Dielectric Dissipation Factor, Excitation Current, Insulation Resistance, and Polarization Index) and Tier 3 (Frequency Response Analysis and Partial Discharge) are not included.</p>
  </sec><sec id="s2">
   <title>2. Methodology</title>
   <p>The methodology involves in this study are: (1) Duval Triangle Method (DTM) for DGA, <xref ref-type="bibr" rid="scirp.145728-6">
     [6]
    </xref> <xref ref-type="bibr" rid="scirp.145728-7">
     [7]
    </xref>, (2) breakdown voltage, acidity, and water content as OQA parameters, and (3) Chendong model for FFA, providing reliable estimates on the degree of polymerization of insulating papers <xref ref-type="bibr" rid="scirp.145728-8">
     [8]
    </xref>.</p>
   <p>DTM is user-friendly due to its graphical interpretation of gas data, allowing engineers and technicians to easily visualize fault zones. It can identify combined or mixed faults, a task that traditional ratio-based methods like the Rogers Ratio Method and IEC Ratio Method often find challenging. Additionally, DTM is recognized by IEC 60599 and widely adopted in the industry, ensuring diagnostic consistency and reliability.</p>
   <p>The Chendong model utilizes a straightforward logarithmic equation, allowing for easy integration into condition monitoring systems without the need for complex calculations. As it is based on 2-FAL (one of the most reliable chemical indicators of paper degradation), the model closely reflects actual aging behavior. Developed from both laboratory and field data, it establishes a strong correlation between 2-FAL concentration in oil and paper aging. Its reliability has been confirmed through years of use in real-world transformer evaluations.</p>
   <sec id="s2_1">
    <title>2.1. Dissolved Gas Analysis (DGA)</title>
    <p>DGA via DTM <xref ref-type="bibr" rid="scirp.145728-7">
      [7]
     </xref> applies the percentages of three critical gases, namely methane (CH<sub>4</sub>), ethylene (C<sub>2</sub>H<sub>4</sub>), and acetylene (C<sub>2</sub>H<sub>2</sub>), to determine the internal faults that occurred in a transformer. These gases are plotted on a triangular diagram, such that concentration ratios of the gases determine the location inside specified zones of the triangle, namely Partial Discharge (PD), low-energy thermal faults (T1, T2), high-energy thermal faults (T3), and electrical discharges (D1, D2), mixed thermal and electrical fault (DT) using <xref ref-type="fig" rid="fig1">
      Figure 1
     </xref>. The concentration ratios can be calculated using the following Equation (1), (2), and (3) <xref ref-type="bibr" rid="scirp.145728-7">
      [7]
     </xref>.</p>
    <fig id="fig1" position="float">
     <label>Figure 1</label>
     <caption>
      <title>
       <xref ref-type="bibr" rid="scirp.145728-"></xref>Figure 1. Coordinates and fault zones of the Duval Triangle Method <xref ref-type="bibr" rid="scirp.145728-7">
        [7]
       </xref>.</title>
     </caption>
     <graphic mimetype="image" position="float" xlink:type="simple" xlink:href="https://html.scirp.org/file/1771287-rId13.jpeg?20250918030848" />
    </fig>
    <p>
     <math xmlns="http://www.w3.org/1998/Math/MathML"> <mrow> 
       <mi>
         % 
       </mi> 
       <msub> 
        <mrow> 
         <mtext>
           CH 
         </mtext> 
        </mrow> 
        <mn>
          4 
        </mn> 
       </msub> 
       <mo>
         = 
       </mo> 
       <mfrac> 
        <mrow> 
         <msub> 
          <mrow> 
           <mtext>
             CH 
           </mtext> 
          </mrow> 
          <mn>
            4 
          </mn> 
         </msub> 
        </mrow> 
        <mrow> 
         <msub> 
          <mrow> 
           <mtext>
             CH 
           </mtext> 
          </mrow> 
          <mn>
            4 
          </mn> 
         </msub> 
         <mo>
           + 
         </mo> 
         <msub> 
          <mtext>
            C 
          </mtext> 
          <mn>
            2 
          </mn> 
         </msub> 
         <msub> 
          <mtext>
            H 
          </mtext> 
          <mn>
            4 
          </mn> 
         </msub> 
         <mo>
           + 
         </mo> 
         <msub> 
          <mtext>
            C 
          </mtext> 
          <mtext>
            2 
          </mtext> 
         </msub> 
         <msub> 
          <mtext>
            H 
          </mtext> 
          <mn>
            2 
          </mn> 
         </msub> 
        </mrow> 
       </mfrac> 
       <mo>
         × 
       </mo> 
       <mn>
         100 
       </mn> 
      </mrow> 
     </math> (1)</p>
    <p>
     <math display="inline" xmlns="http://www.w3.org/1998/Math/MathML"> <mrow> 
       <mi>
         % 
       </mi> 
       <msub> 
        <mtext>
          C 
        </mtext> 
        <mtext>
          2 
        </mtext> 
       </msub> 
       <msub> 
        <mtext>
          H 
        </mtext> 
        <mn>
          4 
        </mn> 
       </msub> 
       <mo>
         = 
       </mo> 
       <mfrac> 
        <mrow> 
         <msub> 
          <mtext>
            C 
          </mtext> 
          <mtext>
            2 
          </mtext> 
         </msub> 
         <msub> 
          <mtext>
            H 
          </mtext> 
          <mn>
            4 
          </mn> 
         </msub> 
        </mrow> 
        <mrow> 
         <msub> 
          <mrow> 
           <mtext>
             CH 
           </mtext> 
          </mrow> 
          <mn>
            4 
          </mn> 
         </msub> 
         <mo>
           + 
         </mo> 
         <msub> 
          <mtext>
            C 
          </mtext> 
          <mtext>
            2 
          </mtext> 
         </msub> 
         <msub> 
          <mtext>
            H 
          </mtext> 
          <mn>
            4 
          </mn> 
         </msub> 
         <mo>
           + 
         </mo> 
         <msub> 
          <mtext>
            C 
          </mtext> 
          <mtext>
            2 
          </mtext> 
         </msub> 
         <msub> 
          <mtext>
            H 
          </mtext> 
          <mn>
            2 
          </mn> 
         </msub> 
        </mrow> 
       </mfrac> 
       <mo>
         × 
       </mo> 
       <mn>
         100 
       </mn> 
      </mrow> 
     </math> (2)</p>
    <p>
     <math xmlns="http://www.w3.org/1998/Math/MathML"> <mrow> 
       <mi>
         % 
       </mi> 
       <msub> 
        <mtext>
          C 
        </mtext> 
        <mtext>
          2 
        </mtext> 
       </msub> 
       <msub> 
        <mtext>
          H 
        </mtext> 
        <mtext>
          2 
        </mtext> 
       </msub> 
       <mo>
         = 
       </mo> 
       <mfrac> 
        <mrow> 
         <msub> 
          <mtext>
            C 
          </mtext> 
          <mtext>
            2 
          </mtext> 
         </msub> 
         <msub> 
          <mtext>
            H 
          </mtext> 
          <mtext>
            2 
          </mtext> 
         </msub> 
        </mrow> 
        <mrow> 
         <msub> 
          <mrow> 
           <mtext>
             CH 
           </mtext> 
          </mrow> 
          <mn>
            4 
          </mn> 
         </msub> 
         <mo>
           + 
         </mo> 
         <msub> 
          <mtext>
            C 
          </mtext> 
          <mtext>
            2 
          </mtext> 
         </msub> 
         <msub> 
          <mtext>
            H 
          </mtext> 
          <mn>
            4 
          </mn> 
         </msub> 
         <mo>
           + 
         </mo> 
         <msub> 
          <mtext>
            C 
          </mtext> 
          <mtext>
            2 
          </mtext> 
         </msub> 
         <msub> 
          <mtext>
            H 
          </mtext> 
          <mn>
            2 
          </mn> 
         </msub> 
        </mrow> 
       </mfrac> 
       <mo>
         × 
       </mo> 
       <mn>
         100 
       </mn> 
      </mrow> 
     </math> (3)</p>
    <p>DGA severity, that assess the condition of transformers by classifying their internal fault types through DGA is shown in <xref ref-type="table" rid="table1">
      Table 1
     </xref>. Each fault type (PD, T1, T2, T3, D1, D2, DT) identified via the DTM is assigned a numerical severity between 0.1 and 1.0.</p>
    <p>The severity represent the risk level associated with each fault, where higher severity corresponds to less critical faults, and lower severity indicate more critical internal fault conditions.</p>
    <table-wrap id="table1">
     <label>
      <xref ref-type="table" rid="table1">
       Table 1
      </xref></label>
     <caption>
      <title>
       <xref ref-type="bibr" rid="scirp.145728-"></xref>Table 1. DGA severity <xref ref-type="bibr" rid="scirp.145728-9">
        [9]
       </xref> <xref ref-type="bibr" rid="scirp.145728-10">
        [10]
       </xref>.</title>
     </caption>
     <table class="MsoTableGrid custom-table" border="0" cellspacing="0" cellpadding="0"> 
      <tr> 
       <td class="custom-bottom-td acenter" width="37.60%"><p style="text-align:center">Internal fault type</p></td> 
       <td class="custom-bottom-td acenter" width="37.62%"><p style="text-align:center">Risk level</p></td> 
       <td class="custom-bottom-td acenter" width="37.62%"><p style="text-align:center">DGA severity</p></td> 
      </tr> 
      <tr> 
       <td class="custom-top-td acenter" width="37.60%"><p style="text-align:center">None</p></td> 
       <td class="custom-top-td acenter" width="37.62%"><p style="text-align:center">Very low</p></td> 
       <td class="custom-top-td acenter" width="37.62%"><p style="text-align:center">1.0</p></td> 
      </tr> 
      <tr> 
       <td class="acenter" width="37.60%"><p style="text-align:center">PD</p></td> 
       <td class="acenter" width="37.62%"><p style="text-align:center">Low</p></td> 
       <td class="acenter" width="37.62%"><p style="text-align:center">0.8 - 0.9</p></td> 
      </tr> 
      <tr> 
       <td class="acenter" width="37.60%"><p style="text-align:center">T1</p></td> 
       <td class="acenter" width="37.62%"><p style="text-align:center">Medium-low</p></td> 
       <td class="acenter" width="37.62%"><p style="text-align:center">0.6 - 0.8</p></td> 
      </tr> 
      <tr> 
       <td class="acenter" width="37.60%"><p style="text-align:center">T2</p></td> 
       <td class="acenter" width="37.62%"><p style="text-align:center">Medium</p></td> 
       <td class="acenter" width="37.62%"><p style="text-align:center">0.5 - 0.6</p></td> 
      </tr> 
      <tr> 
       <td class="acenter" width="37.60%"><p style="text-align:center">T3</p></td> 
       <td class="acenter" width="37.62%"><p style="text-align:center">Medium</p></td> 
       <td class="acenter" width="37.62%"><p style="text-align:center">0.4 - 0.5</p></td> 
      </tr> 
      <tr> 
       <td class="acenter" width="37.60%"><p style="text-align:center">D1</p></td> 
       <td class="acenter" width="37.62%"><p style="text-align:center">High</p></td> 
       <td class="acenter" width="37.62%"><p style="text-align:center">0.3 - 0.4</p></td> 
      </tr> 
      <tr> 
       <td class="acenter" width="37.60%"><p style="text-align:center">D2</p></td> 
       <td class="acenter" width="37.62%"><p style="text-align:center">Critical</p></td> 
       <td class="acenter" width="37.62%"><p style="text-align:center">0.2 - 0.3</p></td> 
      </tr> 
      <tr> 
       <td class="acenter" width="37.60%"><p style="text-align:center">DT</p></td> 
       <td class="acenter" width="37.62%"><p style="text-align:center">Very critical</p></td> 
       <td class="acenter" width="37.62%"><p style="text-align:center">0.1 - 0.2</p></td> 
      </tr> 
     </table>
    </table-wrap>
    <p>For example, a PD fault might receive a severity of 0.85 due to its relatively minor impact, while a D2 fault, linked to high-energy discharges causing major damage, could be scored at 0.25. By translating fault categories into severity-based rating, <xref ref-type="table" rid="table1">
      Table 1
     </xref> assists converting qualitative fault type data into a quantitative format suitable for integration into the overall THI model.</p>
   </sec>
   <sec id="s2_2">
    <title>2.2. Oil Quality Analysis (OQA)</title>
    <p>OQA is employed to evaluate the condition of transformer insulating oil, which is essential for both cooling and insulating of the transformer. Three parameters were utilized: breakdown voltage, acidity, and water content. Breakdown voltage indicates the oil’s ability to withstand electrical stress; a low breakdown voltage suggests possible contamination or degradation. Acidity measures the chemical ageing of the oil, with higher acidity pointing to the presence of by-products that can accelerate insulation deterioration. Water content is also essential, as even small amounts of water can impair the insulating properties of the oil and hasten the deterioration of insulating paper. Collectively, these parameters offer insights into the overall condition of the transformer oil. <xref ref-type="table" rid="table2">
      Table 2
     </xref> shows the severity of OQA parameters (breakdown voltage, acidity and water content).</p>
    <table-wrap id="table2">
     <label>
      <xref ref-type="table" rid="table2">
       Table 2
      </xref></label>
     <caption>
      <title>
       <xref ref-type="bibr" rid="scirp.145728-"></xref>Table 2. Severity of OQA parameters <xref ref-type="bibr" rid="scirp.145728-11">
        [11]
       </xref>.</title>
     </caption>
     <table class="MsoTableGrid custom-table" border="0" cellspacing="0" cellpadding="0"> 
      <tr> 
       <td rowspan="2" class="acenter" width="35.78%"><p style="text-align:center">Parameter</p></td> 
       <td class="custom-bottom-td acenter" width="75.43%" colspan="4"><p style="text-align:center">Risk level</p></td> 
      </tr> 
      <tr> 
       <td class="custom-bottom-td custom-top-td acenter" width="17.24%"><p style="text-align:center">Good</p></td> 
       <td class="custom-bottom-td custom-top-td acenter" width="21.56%"><p style="text-align:center">Fair</p></td> 
       <td class="custom-bottom-td custom-top-td acenter" width="19.39%"><p style="text-align:center">Poor</p></td> 
       <td class="custom-bottom-td custom-top-td acenter" width="17.24%"><p style="text-align:center">Critical</p></td> 
      </tr> 
      <tr> 
       <td class="custom-top-td acenter" width="35.78%"><p style="text-align:center">Breakdown voltage (kV)</p></td> 
       <td class="custom-top-td acenter" width="17.24%"><p style="text-align:center">&gt;50</p></td> 
       <td class="custom-top-td acenter" width="21.56%"><p style="text-align:center">45 - 50</p></td> 
       <td class="custom-top-td acenter" width="19.39%"><p style="text-align:center">40 - 45</p></td> 
       <td class="custom-top-td acenter" width="17.24%"><p style="text-align:center">&lt;40</p></td> 
      </tr> 
      <tr> 
       <td class="acenter" width="35.78%"><p style="text-align:center">Acidity (mg KOH/g)</p></td> 
       <td class="acenter" width="17.24%"><p style="text-align:center">&lt;0.10</p></td> 
       <td class="acenter" width="21.56%"><p style="text-align:center">0.10 - 0.15</p></td> 
       <td class="acenter" width="19.39%"><p style="text-align:center">0.15 - 0.20</p></td> 
       <td class="acenter" width="17.24%"><p style="text-align:center">&gt;0.20</p></td> 
      </tr> 
      <tr> 
       <td class="acenter" width="35.78%"><p style="text-align:center">Water content (ppm)</p></td> 
       <td class="acenter" width="17.24%"><p style="text-align:center">10 - 20</p></td> 
       <td class="acenter" width="21.56%"><p style="text-align:center">20 - 25</p></td> 
       <td class="acenter" width="19.39%"><p style="text-align:center">25 - 30</p></td> 
       <td class="acenter" width="17.24%"><p style="text-align:center">&gt;30</p></td> 
      </tr> 
      <tr> 
       <td class="acenter" width="35.78%"><p style="text-align:center">Severity</p></td> 
       <td class="acenter" width="17.24%"><p style="text-align:center">0.70 - 1.0</p></td> 
       <td class="acenter" width="21.56%"><p style="text-align:center">0.50 - 0.70</p></td> 
       <td class="acenter" width="19.39%"><p style="text-align:center">0.30 - 0.5</p></td> 
       <td class="acenter" width="17.24%"><p style="text-align:center">0.10 - 0.30</p></td> 
      </tr> 
     </table>
    </table-wrap>
    <p>The OQA severity is calculated via Equation (4)</p>
    <p>
     <math xmlns="http://www.w3.org/1998/Math/MathML"> <mrow> 
       <mtext>
         OQA 
       </mtext> 
       <mtext>
           
       </mtext> 
       <mtext>
         severity 
       </mtext> 
       <mo>
         = 
       </mo> 
       <mfrac> 
        <mrow> 
         <mrow> 
          <mo>
            ( 
          </mo> 
          <mrow> 
           <mi>
             x 
           </mi> 
           <mo>
             × 
           </mo> 
           <mn>
             0.169 
           </mn> 
          </mrow> 
          <mo>
            ) 
          </mo> 
         </mrow> 
         <mo>
           + 
         </mo> 
         <mrow> 
          <mo>
            ( 
          </mo> 
          <mrow> 
           <mi>
             y 
           </mi> 
           <mo>
             × 
           </mo> 
           <mn>
             0.139 
           </mn> 
          </mrow> 
          <mo>
            ) 
          </mo> 
         </mrow> 
         <mo>
           + 
         </mo> 
         <mrow> 
          <mo>
            ( 
          </mo> 
          <mrow> 
           <mi>
             z 
           </mi> 
           <mo>
             × 
           </mo> 
           <mn>
             0.108 
           </mn> 
          </mrow> 
          <mo>
            ) 
          </mo> 
         </mrow> 
        </mrow> 
        <mrow> 
         <mn>
           0.169 
         </mn> 
         <mo>
           + 
         </mo> 
         <mn>
           0.139 
         </mn> 
         <mo>
           + 
         </mo> 
         <mn>
           0.108 
         </mn> 
        </mrow> 
       </mfrac> 
      </mrow> 
     </math> (4)</p>
    <p>
     <xref ref-type="bibr" rid="scirp.145728-"></xref>where x = breakdown voltage’s severity, y = Acidity’s severity × 0.139, and z = water content’s severity.</p>
    <p>Each parameter applied a severity from 0.1 to 1.0, where a higher severity means better oil condition. For instance, a high breakdown voltage accompanied by low amounts of acidity or water content will almost have a severity of 0.9, suggesting that it is healthy insulating oil. Conversely, lower breakdown voltage or higher quantities of water content or acidity mean deterioration and lessen the severity. These severity account for the quality of the oil and are further aggregated with their respective weighted score <xref ref-type="bibr" rid="scirp.145728-11">
      [11]
     </xref> (i.e., 0.169, 0.139, and 0.108 for breakdown voltage, acidity, and water content respectively) to find the OQA severity, which contributes to the overall THI model.</p>
   </sec>
   <sec id="s2_3">
    <title>2.3. Furan Fraction Analysis (FFA)</title>
    <p>FFA is used to evaluate the condition of insulating paper of transformer, which naturally deteriorates over time due to heat, chemical reactions, and electrical stress. As the paper ages, it produces chemical by-products called furans, which dissolve into the insulating oil. By measuring these furans, FFA provides an estimate of how damaged the insulating paper has become. A critical metric in this assessment is called Degree of Polymerization (DP), which reflects the strength of the cellulose fibres within the paper. A high DP indicates healthy, well-preserved insulation, while a low DP signals ageing insulation.</p>
    <p>However, directly determining DP involves removing and testing the insulation, which is impractical for active transformers. Instead, FFA estimates DP indirectly through models such as the Chendong model, which translates furan concentrations into approximate DP values as in Equation (5).</p>
    <p>
     <math xmlns="http://www.w3.org/1998/Math/MathML"> <mrow> 
       <mtext>
         DP 
       </mtext> 
       <mo>
         = 
       </mo> 
       <mfrac> 
        <mrow> 
         <mn>
           1.51 
         </mn> 
         <mo>
           − 
         </mo> 
         <mi>
           log 
         </mi> 
         <mn>
           2 
         </mn> 
         <mtext>
           FAL 
         </mtext> 
        </mrow> 
        <mrow> 
         <mn>
           0.0035 
         </mn> 
        </mrow> 
       </mfrac> 
      </mrow> 
     </math> (5)</p>
    <p>The Chendong model’s ability for providing non-invasive, precise estimations of insulating paper’s condition makes it a valuable instrument in transformer diagnostics. FFA severity is listed in <xref ref-type="table" rid="table3">
      Table 3
     </xref>.</p>
    <table-wrap id="table3">
     <label>
      <xref ref-type="table" rid="table3">
       Table 3
      </xref></label>
     <caption>
      <title>
       <xref ref-type="bibr" rid="scirp.145728-"></xref>Table 3. FFA score <xref ref-type="bibr" rid="scirp.145728-8">
        [8]
       </xref> <xref ref-type="bibr" rid="scirp.145728-12">
        [12]
       </xref>.</title>
     </caption>
     <table class="MsoTableGrid custom-table" border="0" cellspacing="0" cellpadding="0"> 
      <tr> 
       <td class="custom-bottom-td acenter" width="19.99%"><p style="text-align:center">DP value</p></td> 
       <td class="custom-bottom-td acenter" width="19.99%"><p style="text-align:center">&gt;800</p></td> 
       <td class="custom-bottom-td acenter" width="20.01%"><p style="text-align:center">600 - 800</p></td> 
       <td class="custom-bottom-td acenter" width="19.99%"><p style="text-align:center">450 - 600</p></td> 
       <td class="custom-bottom-td acenter" width="20.01%"><p style="text-align:center">&lt;450</p></td> 
      </tr> 
      <tr> 
       <td class="custom-top-td acenter" width="19.99%"><p style="text-align:center">FFA severity</p></td> 
       <td class="custom-top-td acenter" width="19.99%"><p style="text-align:center">0.7 - 1.0</p></td> 
       <td class="custom-top-td acenter" width="20.01%"><p style="text-align:center">0.5 - 0.7</p></td> 
       <td class="custom-top-td acenter" width="19.99%"><p style="text-align:center">0.3 - 0.5</p></td> 
       <td class="custom-top-td acenter" width="20.01%"><p style="text-align:center">0.1 - 0.3</p></td> 
      </tr> 
     </table>
    </table-wrap>
    <p>The FFA severity is from 0.1 to 1.0, where better DP values receiving higher rating, indicating healthier insulation. This scoring permits furan statistics to be translated into a measurable health indicator, contributing substantially to the overall THI model.</p>
   </sec>
   <sec id="s2_4">
    <title>2.4. Transformer Health Index (THI)</title>
    <p>The combination of DGA, OQA, and FFA weighted scores gives a complete THI. Each analysis offers independent information about the transformer’s insulation system. Yet, while combined, yields an assessment of the transformer’s health. THI is calculated by combining the weighted scores of DGA, OQA, and FFA (see <xref ref-type="table" rid="table4">
      Table 4
     </xref>) using Equation (6).</p>
    <p>
     <math display="inline" xmlns="http://www.w3.org/1998/Math/MathML"> <mrow> 
       <mtext>
         THI 
       </mtext> 
       <mo>
         , 
       </mo> 
       <mi>
         % 
       </mi> 
       <mo>
         = 
       </mo> 
       <mrow> 
        <mo>
          ( 
        </mo> 
        <mrow> 
         <mi>
           a 
         </mi> 
         <mo>
           + 
         </mo> 
         <mi>
           b 
         </mi> 
         <mo>
           + 
         </mo> 
         <mi>
           c 
         </mi> 
        </mrow> 
        <mo>
          ) 
        </mo> 
       </mrow> 
       <mo>
         × 
       </mo> 
       <mn>
         100 
       </mn> 
      </mrow> 
     </math> (6)</p>
    <table-wrap id="table4">
     <label>
      <xref ref-type="table" rid="table4">
       Table 4
      </xref></label>
     <caption>
      <title>
       <xref ref-type="bibr" rid="scirp.145728-"></xref>Table 4. Weight factor of the transformer health index parameters <xref ref-type="bibr" rid="scirp.145728-11">
        [11]
       </xref>.</title>
     </caption>
     <table class="MsoTableGrid custom-table" border="0" cellspacing="0" cellpadding="0"> 
      <tr> 
       <td class="custom-bottom-td acenter" width="19.40%"><p style="text-align:center">Factor</p></td> 
       <td class="custom-bottom-td acenter" width="26.87%"><p style="text-align:center">a</p></td> 
       <td class="custom-bottom-td acenter" width="26.87%"><p style="text-align:center">b</p></td> 
       <td class="custom-bottom-td acenter" width="26.87%"><p style="text-align:center">c</p></td> 
      </tr> 
      <tr> 
       <td class="custom-top-td acenter" width="19.40%"><p style="text-align:center">Weighted score</p></td> 
       <td class="custom-top-td acenter" width="26.87%"><p style="text-align:center">DGA severity × 0.348</p></td> 
       <td class="custom-top-td acenter" width="26.87%"><p style="text-align:center">OQA severity × 0.216</p></td> 
       <td class="custom-top-td acenter" width="26.87%"><p style="text-align:center">FFA severity × 0.436</p></td> 
      </tr> 
     </table>
    </table-wrap>
    <p>
     <xref ref-type="table" rid="table4">
      Table 4
     </xref> shows how DGA, OQA, and FFA contributes to the health index of a transformer: DGA (34.8%), OQA (21.6%), and FFA (43.6%). FFA having the very highest weight because insulating paper degradation is irreversible.</p>
    <p>The THI (Equation (6)) is then compared with <xref ref-type="table" rid="table5">
      Table 5
     </xref>, which classify the transformer’s condition as Good, Fair, Poor, or Very Poor.</p>
    <table-wrap id="table5">
     <label>
      <xref ref-type="table" rid="table5">
       Table 5
      </xref></label>
     <caption>
      <title>
       <xref ref-type="bibr" rid="scirp.145728-"></xref>Table 5. Transdormer health index (THI).</title>
     </caption>
     <table class="MsoTableGrid custom-table" border="0" cellspacing="0" cellpadding="0"> 
      <tr> 
       <td class="custom-bottom-td acenter" width="22.99%"><p style="text-align:center">THI</p></td> 
       <td class="custom-bottom-td acenter" width="22.67%"><p style="text-align:center">70 - 100</p></td> 
       <td class="custom-bottom-td acenter" width="22.18%"><p style="text-align:center">50 - 70</p></td> 
       <td class="custom-bottom-td acenter" width="22.50%"><p style="text-align:center">30 - 50</p></td> 
       <td class="custom-bottom-td acenter" width="22.49%"><p style="text-align:center">0 - 30</p></td> 
      </tr> 
      <tr> 
       <td class="custom-top-td acenter" width="22.99%"><p style="text-align:center">Grade</p></td> 
       <td class="custom-top-td acenter" width="22.67%"><p style="text-align:center">Good</p></td> 
       <td class="custom-top-td acenter" width="22.18%"><p style="text-align:center">Fair</p></td> 
       <td class="custom-top-td acenter" width="22.50%"><p style="text-align:center">Poor</p></td> 
       <td class="custom-top-td acenter" width="22.49%"><p style="text-align:center">Very poor</p></td> 
      </tr> 
     </table>
    </table-wrap>
    <p>Based on the THI classification, the suggested actions are as follows: for a “Good” rating, continue data collection at a 1-year interval; for “Fair,” adjust the data collection frequency to every 6 months; for “Poor,” decrease the transformer loading; and for “Very Poor,” plan for significant repair, upgrade, or replacement.</p>
   </sec>
  </sec><sec id="s3">
   <title>3. Results and Discussion</title>
   <p>
    <xref ref-type="table" rid="table6">
     Table 6
    </xref> shows sample data: 10 out of the 120 units of in-service transformers. Data of dissolved gases, namely methane (CH<sub>4</sub>), ethylene (C<sub>2</sub>H<sub>4</sub>), and acetylene (C<sub>2</sub>H<sub>2</sub>), breakdown voltage (BDV), acidity, water content, and 2-Furaldehyde (2FAL) were collected from 120 units of 30MVA, 33/11 kV in-service distribution transformers in Peninsular Malaysia.</p>
   <table-wrap id="table6">
    <label>
     <xref ref-type="table" rid="table6">
      Table 6
     </xref></label>
    <caption>
     <title>
      <xref ref-type="bibr" rid="scirp.145728-"></xref>Table 6. Data of 10 units of in-service transformers.</title>
    </caption>
    <table class="MsoTableGrid custom-table" border="0" cellspacing="0" cellpadding="0"> 
     <tr> 
      <td class="custom-bottom-td acenter" width="6.48%"><p style="text-align:center">ID</p></td> 
      <td class="custom-bottom-td acenter" width="10.34%"><p style="text-align:center">Age</p><p style="text-align:center">(years)</p></td> 
      <td class="custom-bottom-td acenter" width="10.34%"><p style="text-align:center">CH<sub>4</sub></p><p style="text-align:center">(ppm)</p></td> 
      <td class="custom-bottom-td acenter" width="10.35%"><p style="text-align:center">C<sub>2</sub>H<sub>4</sub></p><p style="text-align:center">(ppm)</p></td> 
      <td class="custom-bottom-td acenter" width="10.34%"><p style="text-align:center">C<sub>2</sub>H<sub>2</sub></p><p style="text-align:center">(ppm)</p></td> 
      <td class="custom-bottom-td acenter" width="10.35%"><p style="text-align:center">BDV</p><p style="text-align:center">(kV)</p></td> 
      <td class="custom-bottom-td acenter" width="15.08%"><p style="text-align:center">Acidity</p><p style="text-align:center">(mg KOH/g)</p></td> 
      <td class="custom-bottom-td acenter" width="17.24%"><p style="text-align:center">Water content (ppm)</p></td> 
      <td class="custom-bottom-td acenter" width="9.47%"><p style="text-align:center">2FAL</p><p style="text-align:center">(ppb)</p></td> 
     </tr> 
     <tr> 
      <td class="custom-top-td acenter" width="6.48%"><p style="text-align:center">1</p></td> 
      <td class="custom-top-td acenter" width="10.34%"><p style="text-align:center">50</p></td> 
      <td class="custom-top-td acenter" width="10.34%"><p style="text-align:center">0</p></td> 
      <td class="custom-top-td acenter" width="10.35%"><p style="text-align:center">12</p></td> 
      <td class="custom-top-td acenter" width="10.34%"><p style="text-align:center">6</p></td> 
      <td class="custom-top-td acenter" width="10.35%"><p style="text-align:center">58</p></td> 
      <td class="custom-top-td acenter" width="15.08%"><p style="text-align:center">0.08</p></td> 
      <td class="custom-top-td acenter" width="17.24%"><p style="text-align:center">137</p></td> 
      <td class="custom-top-td acenter" width="9.47%"><p style="text-align:center">15641</p></td> 
     </tr> 
     <tr> 
      <td class="acenter" width="6.48%"><p style="text-align:center">2</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">36</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">4</p></td> 
      <td class="acenter" width="10.35%"><p style="text-align:center">1</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">0</p></td> 
      <td class="acenter" width="10.35%"><p style="text-align:center">56</p></td> 
      <td class="acenter" width="15.08%"><p style="text-align:center">0.01</p></td> 
      <td class="acenter" width="17.24%"><p style="text-align:center">13</p></td> 
      <td class="acenter" width="9.47%"><p style="text-align:center">115</p></td> 
     </tr> 
     <tr> 
      <td class="acenter" width="6.48%"><p style="text-align:center">3</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">27</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">0</p></td> 
      <td class="acenter" width="10.35%"><p style="text-align:center">7</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">7</p></td> 
      <td class="acenter" width="10.35%"><p style="text-align:center">42</p></td> 
      <td class="acenter" width="15.08%"><p style="text-align:center">0.02</p></td> 
      <td class="acenter" width="17.24%"><p style="text-align:center">17</p></td> 
      <td class="acenter" width="9.47%"><p style="text-align:center">145</p></td> 
     </tr> 
     <tr> 
      <td class="acenter" width="6.48%"><p style="text-align:center">4</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">30</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">15</p></td> 
      <td class="acenter" width="10.35%"><p style="text-align:center">10</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">11</p></td> 
      <td class="acenter" width="10.35%"><p style="text-align:center">31</p></td> 
      <td class="acenter" width="15.08%"><p style="text-align:center">0.19</p></td> 
      <td class="acenter" width="17.24%"><p style="text-align:center">41</p></td> 
      <td class="acenter" width="9.47%"><p style="text-align:center">115</p></td> 
     </tr> 
     <tr> 
      <td class="acenter" width="6.48%"><p style="text-align:center">5</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">29</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">5</p></td> 
      <td class="acenter" width="10.35%"><p style="text-align:center">7</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">0</p></td> 
      <td class="acenter" width="10.35%"><p style="text-align:center">66</p></td> 
      <td class="acenter" width="15.08%"><p style="text-align:center">0.09</p></td> 
      <td class="acenter" width="17.24%"><p style="text-align:center">14</p></td> 
      <td class="acenter" width="9.47%"><p style="text-align:center">396</p></td> 
     </tr> 
     <tr> 
      <td class="acenter" width="6.48%"><p style="text-align:center">6</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">41</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">4</p></td> 
      <td class="acenter" width="10.35%"><p style="text-align:center">2</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">8</p></td> 
      <td class="acenter" width="10.35%"><p style="text-align:center">28</p></td> 
      <td class="acenter" width="15.08%"><p style="text-align:center">0.22</p></td> 
      <td class="acenter" width="17.24%"><p style="text-align:center">60</p></td> 
      <td class="acenter" width="9.47%"><p style="text-align:center">2756</p></td> 
     </tr> 
     <tr> 
      <td class="acenter" width="6.48%"><p style="text-align:center">7</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">40</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">3</p></td> 
      <td class="acenter" width="10.35%"><p style="text-align:center">0</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">0</p></td> 
      <td class="acenter" width="10.35%"><p style="text-align:center">38</p></td> 
      <td class="acenter" width="15.08%"><p style="text-align:center">0.03</p></td> 
      <td class="acenter" width="17.24%"><p style="text-align:center">32</p></td> 
      <td class="acenter" width="9.47%"><p style="text-align:center">757</p></td> 
     </tr> 
     <tr> 
      <td class="acenter" width="6.48%"><p style="text-align:center">8</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">61</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">11</p></td> 
      <td class="acenter" width="10.35%"><p style="text-align:center">19</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">0</p></td> 
      <td class="acenter" width="10.35%"><p style="text-align:center">47</p></td> 
      <td class="acenter" width="15.08%"><p style="text-align:center">0.02</p></td> 
      <td class="acenter" width="17.24%"><p style="text-align:center">34</p></td> 
      <td class="acenter" width="9.47%"><p style="text-align:center">1112</p></td> 
     </tr> 
     <tr> 
      <td class="acenter" width="6.48%"><p style="text-align:center">9</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">30</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">35</p></td> 
      <td class="acenter" width="10.35%"><p style="text-align:center">141</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">343</p></td> 
      <td class="acenter" width="10.35%"><p style="text-align:center">60</p></td> 
      <td class="acenter" width="15.08%"><p style="text-align:center">0.03</p></td> 
      <td class="acenter" width="17.24%"><p style="text-align:center">23</p></td> 
      <td class="acenter" width="9.47%"><p style="text-align:center">293</p></td> 
     </tr> 
     <tr> 
      <td class="acenter" width="6.48%"><p style="text-align:center">10</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">30</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">199</p></td> 
      <td class="acenter" width="10.35%"><p style="text-align:center">50</p></td> 
      <td class="acenter" width="10.34%"><p style="text-align:center">0</p></td> 
      <td class="acenter" width="10.35%"><p style="text-align:center">22</p></td> 
      <td class="acenter" width="15.08%"><p style="text-align:center">0.04</p></td> 
      <td class="acenter" width="17.24%"><p style="text-align:center">35</p></td> 
      <td class="acenter" width="9.47%"><p style="text-align:center">7</p></td> 
     </tr> 
    </table>
   </table-wrap>
   <p>The dissolved gases were determined via Gas Chromatography. Breakdown voltage, acidity, and water content were measured according to ASTM D1816, ASTM D664, and ASTM D1533 respectively. Data of 2FAL were collected through High Performance Liquid Chromatography (HPLC) technique, executed according to ASTM D5857.</p>
   <p>
    <xref ref-type="table" rid="table7">
     Table 7
    </xref> shows results of DGA, OQA, and FFA severity, as well as THI of the 10 transformer sample under consideration.</p>
   <table-wrap id="table7">
    <label>
     <xref ref-type="table" rid="table7">
      Table 7
     </xref></label>
    <caption>
     <title>
      <xref ref-type="bibr" rid="scirp.145728-"></xref>Table 7. Severity (DGA, OQA, FFA), THI and Grade of 10 units of in-service transformers.</title>
    </caption>
    <table class="MsoTableGrid custom-table" border="0" cellspacing="0" cellpadding="0"> 
     <tr> 
      <td class="custom-bottom-td acenter" width="15.31%"><p style="text-align:center">ID</p></td> 
      <td class="custom-bottom-td acenter" width="16.04%"><p style="text-align:center">Age</p><p style="text-align:center">(years)</p></td> 
      <td class="custom-bottom-td acenter" width="16.06%"><p style="text-align:center">DGA</p><p style="text-align:center">severity</p></td> 
      <td class="custom-bottom-td acenter" width="16.06%"><p style="text-align:center">OQA</p><p style="text-align:center">severity</p></td> 
      <td class="custom-bottom-td acenter" width="16.06%"><p style="text-align:center">FFA</p><p style="text-align:center">severity</p></td> 
      <td class="custom-bottom-td acenter" width="16.00%"><p style="text-align:center">THI</p><p style="text-align:center">(%)</p></td> 
      <td class="custom-bottom-td acenter" width="16.03%"><p style="text-align:center">Grade</p></td> 
     </tr> 
     <tr> 
      <td class="custom-top-td acenter" width="15.31%"><p style="text-align:center">1</p></td> 
      <td class="custom-top-td acenter" width="16.04%"><p style="text-align:center">50</p></td> 
      <td class="custom-top-td acenter" width="16.06%"><p style="text-align:center">1.00</p></td> 
      <td class="custom-top-td acenter" width="16.06%"><p style="text-align:center">0.72</p></td> 
      <td class="custom-top-td acenter" width="16.06%"><p style="text-align:center">0.20</p></td> 
      <td class="custom-top-td acenter" width="16.00%"><p style="text-align:center">58.20</p></td> 
      <td class="custom-top-td acenter" width="16.03%"><p style="text-align:center">Fair</p></td> 
     </tr> 
     <tr> 
      <td class="acenter" width="15.31%"><p style="text-align:center">2</p></td> 
      <td class="acenter" width="16.04%"><p style="text-align:center">36</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.70</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.90</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.60</p></td> 
      <td class="acenter" width="16.00%"><p style="text-align:center">69.96</p></td> 
      <td class="acenter" width="16.03%"><p style="text-align:center">Fair</p></td> 
     </tr> 
     <tr> 
      <td class="acenter" width="15.31%"><p style="text-align:center">3</p></td> 
      <td class="acenter" width="16.04%"><p style="text-align:center">27</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">1.00</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.70</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.60</p></td> 
      <td class="acenter" width="16.00%"><p style="text-align:center">75.37</p></td> 
      <td class="acenter" width="16.03%"><p style="text-align:center">Good</p></td> 
     </tr> 
     <tr> 
      <td class="acenter" width="15.31%"><p style="text-align:center">4</p></td> 
      <td class="acenter" width="16.04%"><p style="text-align:center">30</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.25</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.27</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.60</p></td> 
      <td class="acenter" width="16.00%"><p style="text-align:center">40.62</p></td> 
      <td class="acenter" width="16.03%"><p style="text-align:center">Poor</p></td> 
     </tr> 
     <tr> 
      <td class="acenter" width="15.31%"><p style="text-align:center">5</p></td> 
      <td class="acenter" width="16.04%"><p style="text-align:center">29</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.45</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.90</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.40</p></td> 
      <td class="acenter" width="16.00%"><p style="text-align:center">52.24</p></td> 
      <td class="acenter" width="16.03%"><p style="text-align:center">Fair</p></td> 
     </tr> 
     <tr> 
      <td class="acenter" width="15.31%"><p style="text-align:center">6</p></td> 
      <td class="acenter" width="16.04%"><p style="text-align:center">41</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.35</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.20</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.20</p></td> 
      <td class="acenter" width="16.00%"><p style="text-align:center">25.22</p></td> 
      <td class="acenter" width="16.03%"><p style="text-align:center">Very poor</p></td> 
     </tr> 
     <tr> 
      <td class="acenter" width="15.31%"><p style="text-align:center">7</p></td> 
      <td class="acenter" width="16.04%"><p style="text-align:center">40</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.90</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.43</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.40</p></td> 
      <td class="acenter" width="16.00%"><p style="text-align:center">58.13</p></td> 
      <td class="acenter" width="16.03%"><p style="text-align:center">Fair</p></td> 
     </tr> 
     <tr> 
      <td class="acenter" width="15.31%"><p style="text-align:center">8</p></td> 
      <td class="acenter" width="16.04%"><p style="text-align:center">61</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.35</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.60</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.20</p></td> 
      <td class="acenter" width="16.00%"><p style="text-align:center">33.78</p></td> 
      <td class="acenter" width="16.03%"><p style="text-align:center">Poor</p></td> 
     </tr> 
     <tr> 
      <td class="acenter" width="15.31%"><p style="text-align:center">9</p></td> 
      <td class="acenter" width="16.04%"><p style="text-align:center">30</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.25</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.82</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.40</p></td> 
      <td class="acenter" width="16.00%"><p style="text-align:center">43.90</p></td> 
      <td class="acenter" width="16.03%"><p style="text-align:center">Poor</p></td> 
     </tr> 
     <tr> 
      <td class="acenter" width="15.31%"><p style="text-align:center">10</p></td> 
      <td class="acenter" width="16.04%"><p style="text-align:center">30</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.70</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.43</p></td> 
      <td class="acenter" width="16.06%"><p style="text-align:center">0.90</p></td> 
      <td class="acenter" width="16.00%"><p style="text-align:center">72.97</p></td> 
      <td class="acenter" width="16.03%"><p style="text-align:center">Good</p></td> 
     </tr> 
    </table>
   </table-wrap>
   <p>
    <xref ref-type="fig" rid="fig2">
     Figure 2
    </xref> shows weighted scores of DGA, OQA, and FFA throughout the 10 transformers, alongside their corresponding THI grades. By combining these 3 weighted scores into a THI (expressed in percentage), a complete assessment of the transformer overall condition is classified into four grades (i.e., good, fair, poor, and very poor).</p>
   <fig id="fig2" position="float">
    <label>Figure 2</label>
    <caption>
     <title>
      <xref ref-type="bibr" rid="scirp.145728-"></xref>Figure 2. Weighted scores (DGA, OQA, FFA) of 10 units of in-service transformers.</title>
    </caption>
    <graphic mimetype="image" position="float" xlink:type="simple" xlink:href="https://html.scirp.org/file/1771287-rId26.jpeg?20250918030848" />
   </fig>
   <p>
    <xref ref-type="fig" rid="fig2">
     Figure 2
    </xref> reveals several key patterns: transformers labelled as “Good” (Transformer 3 and 10) show high DGA and FFA score. In comparison, Transformer 6, rated “Very Poor”, shows a critically low score in all categories, with its FFA score being poor, indicating extreme paper insulation degradation. The “Fair” and “Poor” rated transformers showcase blended styles, some hold slight OQA and DGA scores despite lower FFA score (e.g., Transformer 7), at the same time as others display balanced but suboptimal performance throughout all metrics (e.g., Transformer 5). Notably, the FFA score appears to be the large differentiator among THI, underscoring its dominant role inside the THI assessment. <xref ref-type="fig" rid="fig3">
     Figure 3
    </xref> shows the grade of 120 units of in-service transformers by their age group.</p>
   <fig id="fig3" position="float">
    <label>Figure 3</label>
    <caption>
     <title>
      <xref ref-type="bibr" rid="scirp.145728-"></xref>Figure 3. Grade of in-service transformers by their in-service period (years) group.</title>
    </caption>
    <graphic mimetype="image" position="float" xlink:type="simple" xlink:href="https://html.scirp.org/file/1771287-rId27.jpeg?20250918030848" />
   </fig>
   <p>The 30 - 39 age group includes the most transformers, where most of them fall into “Good” and “Fair” health categories. The units in this age group show signs of ageing yet most remain operational, indicating the health condition of transformers deteriorates as their age increases. The 40 - 49 age group demonstrates a shift toward “Fair”, “Poor”, and “Very Poor” conditions which indicates the progressive breakdown of insulation and internal components. Most units in the 50 - 59 and 60 - 69 age groups receive “Fair” or “Poor” ratings while “Good” condition units remain scarce. The observed trend shows the natural degradation which occurs in ageing transformers. Some units in older age groups show acceptable health status, may result from proper maintenance practices and reduced operational stress. The 20 - 29 age group contains transformers with “Good” and “Fair” grades but only a few units have “Poor” condition. The data shows that most recent transformers function properly yet some units from this group may already display early signs of ageing.</p>
   <p>Regarding limitations, the proposed THI models may not consider variations in transformer designs (such as power transformers), loading conditions, or environmental factors. Rather than representing the actual operational risk, the THI serves as a predictive tool to support asset management strategies.</p>
  </sec><sec id="s4">
   <title>4. Conclusion</title>
   <p>The proposed Transformer Health Index (THI), formulated through weighted integration of Dissolved Gas Analysis (DGA), Oil Quality Analysis (OQA), and Furan Fraction Analysis (FFA), offers a framework for assessing transformer condition. Diagnostic methods utilized include the Duval Triangle for internal fault classification, the Chendong model for Degree of Polymerization (DP), and key OQA parameters (breakdown voltage, acidity, and moisture content). Application of the THI to a dataset of 120 in-services 30 MVA, 33/11 kV distribution transformers demonstrated clear differentiation across health categories. “Good” units presented consistently high DGA and FFA scores, while deviations between these parameters in “Fair” and “Poor” categories indicated varied degradation modes. “Very Poor” units exhibited uniformly low DGA and FFA scores. Furthermore, the analysis established a general correlation between operational age and declining THI values. Nonetheless, exceptions such as accelerated deterioration in relatively newer units and sustained performance in some older transformers, highlight the need for condition-based maintenance strategies over age-based assessments alone.</p>
  </sec><sec id="s5">
   <title>Acknowledgements</title>
   <p>The authors gratefully acknowledge the Center for Research and Innovation Management (CRIM), Universiti Teknikal Malaysia Melaka (UTeM), for publication fee.</p>
  </sec>
 </body><back>
  <ref-list>
   <title>References</title>
   <ref id="scirp.145728-ref1">
    <label>1</label>
    <mixed-citation publication-type="other" xlink:type="simple">
     Yahaya, M.S., Azis, N., Mohd Selva, A., Ab Kadir, M.Z.A., Jasni, J., Kadim, E.J., et al. (2018) A Maintenance Cost Study of Transformers Based on Markov Model Utilizing Frequency of Transition Approach. Energies, 11, Article No. 2006. &gt;https://doi.org/10.3390/en11082006
    </mixed-citation>
   </ref>
   <ref id="scirp.145728-ref2">
    <label>2</label>
    <mixed-citation publication-type="other" xlink:type="simple">
     Khiar, M.S.A., Md Thayoob, Y.H., Ghazali, Y.Z.Y., Ab Ghani, S. and Chairul, I.S. (2012) Condition Assessment of OLTC Using Duval Triangle and Static Winding Resistance Test. 2012 IEEE International Power Engineering and Optimization Conference, Melaka, 6-7 June 2012, 432-435. &gt;https://doi.org/10.1109/peoco.2012.6230903
    </mixed-citation>
   </ref>
   <ref id="scirp.145728-ref3">
    <label>3</label>
    <mixed-citation publication-type="other" xlink:type="simple">
     Sutan Chairul, I., Ab Ghani, S., Ahmad Khiar, M.S., Md Thayoob, Y.H. and Yang Ghazali, Y.Z. (2012) Kraft Paper Insulation’s Life Assessment and Effects of Oxygen and Moisture to Paper Insulation’s Deterioration Rate. 2012 IEEE International Conference on Power and Energy (PECon), Kota Kinabalu, 2-5 December 2012, 728-731. &gt;https://doi.org/10.1109/pecon.2012.6450311
    </mixed-citation>
   </ref>
   <ref id="scirp.145728-ref4">
    <label>4</label>
    <mixed-citation publication-type="other" xlink:type="simple">
     Ghani, S.A., Thayoob, Y.H.M., Ghazali, Y.Z.Y., Khiar, M.S.A. and Chairul, I.S. (2013) Condition Monitoring of Distribution Transformer’s Mechanical Parts Using Sweep Frequency Response Analysis (SFRA). Procedia Engineering, 68, 469-476. &gt;https://doi.org/10.1016/j.proeng.2013.12.208
    </mixed-citation>
   </ref>
   <ref id="scirp.145728-ref5">
    <label>5</label>
    <mixed-citation publication-type="other" xlink:type="simple">
     Khiar, M.S.A., Thayoob, Y.H.M., Ghazali, Y.Z.Y., Ghani, S.A. and Chairul, I.S. (2013) Diagnosis of OLTC via Duval Triangle Method and Dynamic Current Measurement. Procedia Engineering, 68, 477-483. &gt;https://doi.org/10.1016/j.proeng.2013.12.209
    </mixed-citation>
   </ref>
   <ref id="scirp.145728-ref6">
    <label>6</label>
    <mixed-citation publication-type="other" xlink:type="simple">
     Manisha, Kaur, K., Sharma, N.K., Singh, J. and Bhalla, D. (2022) Performance Assessment of IEEE/IEC Method and Duval Triangle Technique for Transformer Incipient Fault Diagnosis. IOP Conference Series: Materials Science and Engineering, 1228, Article ID: 012027. &gt;https://doi.org/10.1088/1757-899x/1228/1/012027
    </mixed-citation>
   </ref>
   <ref id="scirp.145728-ref7">
    <label>7</label>
    <mixed-citation publication-type="other" xlink:type="simple">
     Duval, M. (2002) A Review of Faults Detectable by Gas-in-Oil Analysis in Transformers. IEEE Electrical Insulation Magazine, 18, 8-17. &gt;https://doi.org/10.1109/mei.2002.1014963
    </mixed-citation>
   </ref>
   <ref id="scirp.145728-ref8">
    <label>8</label>
    <mixed-citation publication-type="other" xlink:type="simple">
     Kanumuri, D., Sharma, V. and Rahi, O.P. (2019) Analysis Using Various Approaches for Residual Life Estimation of Power Transformers. International Journal on Electrical Engineering and Informatics, 11, 389-407. &gt;https://doi.org/10.15676/ijeei.2019.11.2.11
    </mixed-citation>
   </ref>
   <ref id="scirp.145728-ref9">
    <label>9</label>
    <mixed-citation publication-type="other" xlink:type="simple">
     Wani, S.A., Farooque, M.U., Khan, S.A., Gupta, D. and Khan, M.A. (2015) Fault Severity Determination in Transformers Using Dissolved Gas Analysis (DGA). IEEE International Conference Electronics, Energy, Environment, Communication, Computer, Control (INDICON), New Delhi, 17-20 December 2015, 1-6. &gt;https://doi.org/10.1109/indicon.2015.7443362
    </mixed-citation>
   </ref>
   <ref id="scirp.145728-ref10">
    <label>10</label>
    <mixed-citation publication-type="other" xlink:type="simple">
     Mharakurwa, E.T., Nyakoe, G.N. and Akumu, A.O. (2019) Power Transformer Fault Severity Estimation Based on Dissolved Gas Analysis and Energy of Fault Formation Technique. Journal of Electrical and Computer Engineering, 2019, Article ID: 9674054. &gt;https://doi.org/10.1155/2019/9674054
    </mixed-citation>
   </ref>
   <ref id="scirp.145728-ref11">
    <label>11</label>
    <mixed-citation publication-type="other" xlink:type="simple">
     Tamma, W.R., Prasojo, R.A. and Suwarno, (2021) High Voltage Power Transformer Condition Assessment Considering the Health Index Value and Its Decreasing Rate. High Voltage, 6, 314-327. &gt;https://doi.org/10.1049/hve2.12074
    </mixed-citation>
   </ref>
   <ref id="scirp.145728-ref12">
    <label>12</label>
    <mixed-citation publication-type="other" xlink:type="simple">
     Hernanda, I.G.N.S., Mulyana, A.C., Asfani, D.A., Negara, I.M.Y. and Fahmi, D. (2014) Application of Health Index Method for Transformer Condition Assessment. TENCON 2014-2014 IEEE Region 10 Conference, Bangkok, 22-25 October 2014, 1-6. &gt;https://doi.org/10.1109/tencon.2014.7022433
    </mixed-citation>
   </ref>
  </ref-list>
 </back>
</article>