<?xml version="1.0" encoding="UTF-8"?><!DOCTYPE article  PUBLIC "-//NLM//DTD Journal Publishing DTD v3.0 20080202//EN" "http://dtd.nlm.nih.gov/publishing/3.0/journalpublishing3.dtd"><article xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink" dtd-version="3.0" xml:lang="en" article-type="research article"><front><journal-meta><journal-id journal-id-type="publisher-id">WJET</journal-id><journal-title-group><journal-title>World Journal of Engineering and Technology</journal-title></journal-title-group><issn pub-type="epub">2331-4222</issn><publisher><publisher-name>Scientific Research Publishing</publisher-name></publisher></journal-meta><article-meta><article-id pub-id-type="doi">10.4236/wjet.2022.104047</article-id><article-id pub-id-type="publisher-id">WJET-120193</article-id><article-categories><subj-group subj-group-type="heading"><subject>Articles</subject></subj-group><subj-group subj-group-type="Discipline-v2"><subject>Chemistry&amp;Materials Science</subject><subject> Engineering</subject></subj-group></article-categories><title-group><article-title>
 
 
  Performance Survey of PVC Insulation of LC/Gecamines Electrical Cables Subjected to Ageing and Its Life Span Evaluation
 
</article-title></title-group><contrib-group><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Chungu</surname><given-names>Mwana Mwamba Yannick</given-names></name><xref ref-type="aff" rid="aff1"><sup>1</sup></xref></contrib><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Michael</surname><given-names>Kabangu Ngoie</given-names></name><xref ref-type="aff" rid="aff1"><sup>1</sup></xref><xref ref-type="corresp" rid="cor1"><sup>*</sup></xref></contrib><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Muliangala</surname><given-names>Mbalaba Francis</given-names></name><xref ref-type="aff" rid="aff1"><sup>1</sup></xref></contrib><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Kasambay</surname><given-names>Mutangala Francis</given-names></name><xref ref-type="aff" rid="aff1"><sup>1</sup></xref></contrib><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Katamea</surname><given-names>Mwanvua Mavé</given-names></name><xref ref-type="aff" rid="aff1"><sup>1</sup></xref></contrib><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Twite</surname><given-names>Kabamba Edmond</given-names></name><xref ref-type="aff" rid="aff1"><sup>1</sup></xref></contrib><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Lukozi</surname><given-names>Mufaume Donatien</given-names></name><xref ref-type="aff" rid="aff2"><sup>2</sup></xref></contrib></contrib-group><aff id="aff2"><addr-line>Independent Researcher, Faculty of Polytechnics, University of Lubumbashi, Lubumbashi, Democratic Republic of the Congo</addr-line></aff><aff id="aff1"><addr-line>Metallurgy and Materials Department, Faculty of Polytechnics, University of Lubumbashi, Lubumbashi, Democratic Republic of the Congo</addr-line></aff><pub-date pub-type="epub"><day>08</day><month>09</month><year>2022</year></pub-date><volume>10</volume><issue>04</issue><fpage>728</fpage><lpage>737</lpage><history><date date-type="received"><day>12,</day>	<month>February</month>	<year>2022</year></date><date date-type="rev-recd"><day>26,</day>	<month>September</month>	<year>2022</year>	</date><date date-type="accepted"><day>29,</day>	<month>September</month>	<year>2022</year></date></history><permissions><copyright-statement>&#169; Copyright  2014 by authors and Scientific Research Publishing Inc. </copyright-statement><copyright-year>2014</copyright-year><license><license-p>This work is licensed under the Creative Commons Attribution International License (CC BY). http://creativecommons.org/licenses/by/4.0/</license-p></license></permissions><abstract><p>
 
 
  Considering the insulators ageing in a mixture of PVC and dye, set following operating conditions and time to ensure proper operation and perfect safety of industrial installations using insulated conductors. The results showed that the insulation carried out by the L.C main office was 
  a 
  good quality (on thermal aspect), because the resistance of the insulation is so high (i.e. 3940 Mega Ohms under normal conditions). The results showed a lifespan of 50 years at a temperature of 40&#176;C (close to ambient temperature), plus minus 33 years at a temperature of 70&#176;C; plus minus 22 years at a temperature of 100&#176;C and 12 years at a temperature of 160&#176;C. Furthermore, information on chemical attack
  , the
   result
  s
   showed that PVC cables have poor resistance to sulfuric acid attack (having a pH of 1.5 and a density of 1.84 g/cm<sup>3</sup>). LC/Gecamines is able to produce locally a good quality of electrical cables.
 
</p></abstract><kwd-group><kwd>PVC</kwd><kwd> Performance</kwd><kwd> Thermal Ageing</kwd><kwd> Chemical Resistance</kwd><kwd> Cable Life Span</kwd></kwd-group></article-meta></front><body><sec id="s1"><title>1. Introduction</title><p>The factory of rolling and cable mills L.C acronym, was created in the middle of the Second World War during the occupation of Belgium by the German Nazis. The purpose was to mitigate the importation and production difficulties of the manufactured products in steels (cables, flats, tubes) by Belgium. Since 1975, the factory has been annexed to the Congolese mining giant GECAMINES under the name of “Rolling mills and cable factories main office” [<xref ref-type="bibr" rid="scirp.120193-ref1">1</xref>]. Previously, about 95% of companies in RDC used the insulated electrical cables from L.C/Gecamines for their internal installations. The cables are insulating with various types of polymers [<xref ref-type="bibr" rid="scirp.120193-ref2">2</xref>]. The insulation can age; it can suffer from defects due to operating conditions, and at the same time cause invaluable damage at the industry [<xref ref-type="bibr" rid="scirp.120193-ref3">3</xref>]. Therefore, the accurate prediction of the service life and operating conditions of electrical cables is obviously becoming an economic, safety and strategic issue for the industry [<xref ref-type="bibr" rid="scirp.120193-ref4">4</xref>]. However, the life span and operating conditions of electrical cables are mainly relating to the life span of their insulation.</p><p>Indeed, the insulating tape is the direct element in contact with the external environment. Therefore, the insulating tape is the first defect element exposed to chemical, thermal (external) and mechanical deterioration [<xref ref-type="bibr" rid="scirp.120193-ref5">5</xref>]. The material used by L.C/Gecamines for the insulation of this external insulating tape is polyvinyl chloride (PVC).</p><p>Each electrical wire in a factory must be carefully covered with some type of electrical insulating tape (PVC in the case of this study). The wire itself is usually made of copper or aluminum, which are known to be good conductors of electrical power. The insulation must be opposite from the conductor; meaning, it must resist to electrical power and keep the latter in a path along with a conductor [<xref ref-type="bibr" rid="scirp.120193-ref6">6</xref>]. Insulated material can age, it can fail due to operating conditions, and it can cause inestimable damage to the plant.</p><p>The study gap is to evaluate the performance and life span of L.C/Gecamines cables subjected to a thermal force ageing to characterize their resistance to chemical attacks.</p></sec><sec id="s2"><title>2. Materials and Methods</title><sec id="s2_1"><title>2.1. The Sample and LC/Gecamines Presentation</title><p>The L.C/Gecamines main office is a production entity of Gecamines Company in the Democratic Republic of Congo, engaged in the processing of non-ferrous metals (<xref ref-type="fig" rid="fig1">Figure 1</xref> &amp; <xref ref-type="fig" rid="fig2">Figure 2</xref>).</p><p>The insulated wire produced by L.C/Gecamines main office, was mainly composed of 99.73% copper and some other impurities at acceptable levels (<xref ref-type="table" rid="table1">Table 1</xref>). The wire-bars received by the headquarters from Shituru mining plant, had a deformation of &#177;2%. These wire bars were recycled in a FRITZ furnace at 400˚C - 450˚C for 3 hours of heating time, half an hour of holding and 18 hours of cooling. This operation resulted in new characteristic as shown in <xref ref-type="table" rid="table2">Table 2</xref>. The plastic materials in the form of pellets (PVC) had a density of 1.52 g/cm<sup>3</sup>; a low tensile strength of 13.6 MPa (15 MPa - 18 MPa for the supplier); an elongation at 200% breakage (280% for the supplier) and a continuous operating temperature of 70˚C to −5˚C for the L.C/Gecamines main office (<xref ref-type="table" rid="table3">Table 3</xref>). Noted that all these values (for plastic) from the supplier were define according to IEC 60,250 and SABS Methods 503/4/7.</p><table-wrap id="table1" ><label><xref ref-type="table" rid="table1">Table 1</xref></label><caption><title> Chemical composition according to the content of different metals in the conductor sample</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Elements present in the sample</th><th align="center" valign="middle" >Copper (Cu)</th><th align="center" valign="middle" >Cobalt (Co)</th><th align="center" valign="middle" >Iron (Fe)</th><th align="center" valign="middle" >Lead (Pb)</th><th align="center" valign="middle" >Selenium (Se)</th></tr></thead><tr><td align="center" valign="middle" >Proportion in % of total</td><td align="center" valign="middle" >99.73</td><td align="center" valign="middle" >4 ppm</td><td align="center" valign="middle" >39.6 ppm</td><td align="center" valign="middle" >74.6 ppm</td><td align="center" valign="middle" >&lt;0.01 ppm</td></tr></tbody></table></table-wrap></sec><sec id="s2_2"><title>2.2. Studies Materials</title><p>BALTEAU apparatus were use in this study; it is a generator of medium voltage from zero to 10 kV, used for tests of dielectric rigidity of the insulator (<xref ref-type="fig" rid="fig3">Figure 3</xref>). The objective within was to determine the lifetime of cables based on the resistance of the insulation. A good insulation was defined as the insulation resistance that has a great value or equal to 1/100 of the applied voltage [<xref ref-type="bibr" rid="scirp.120193-ref7">7</xref>].</p><p>This lifetime is a function of the insulator’s resistance. The insulator must resist to the current, and maintain the latest in its trajectory along with the conductor.</p></sec><sec id="s2_3"><title>2.3. Methods and Experimental Setup</title><p>In order to determine the resistance of the insulation, five samples (for each temperature) of 60 cm length and 9.075 mm<sup>2</sup> cross-section were prepared and stripped at both ends; the central part of the sample was attach in the water bath (<xref ref-type="fig" rid="fig3">Figure 3</xref>(b)). The two ends were not in contact with the water (setup shown in <xref ref-type="fig" rid="fig4">Figure 4</xref>). The phase of the device was connect to the first stripped end of the</p><table-wrap id="table2" ><label><xref ref-type="table" rid="table2">Table 2</xref></label><caption><title> Physical properties of annealed copper conductor</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Physical properties</th><th align="center" valign="middle" >Density in g/cm <sup>3</sup></th><th align="center" valign="middle" >Breaking load in N/mm <sup>2</sup></th><th align="center" valign="middle" >Elongation in % of length</th><th align="center" valign="middle" >Resistivity in ohm mm<sup>2</sup>/m</th></tr></thead><tr><td align="center" valign="middle" >Value of the copper sample</td><td align="center" valign="middle" >8.93</td><td align="center" valign="middle" >21.8</td><td align="center" valign="middle" >34.8</td><td align="center" valign="middle" >0.017</td></tr></tbody></table></table-wrap><table-wrap id="table3" ><label><xref ref-type="table" rid="table3">Table 3</xref></label><caption><title> Characteristic of the PVC insulation of L.C/Gecamines cables</title></caption><table><tbody><thead><tr><th align="center" valign="middle"  colspan="2"  >Characteristics of PVC</th></tr></thead><tr><td align="center" valign="middle" >Size</td><td align="center" valign="middle" >Values</td></tr><tr><td align="center" valign="middle" >Density in g/cm<sup>3</sup></td><td align="center" valign="middle" >1.52</td></tr><tr><td align="center" valign="middle" >breaking load MPa</td><td align="center" valign="middle" >13.6</td></tr><tr><td align="center" valign="middle" >Extrusion temperature in ˚C</td><td align="center" valign="middle" >155 - 175</td></tr><tr><td align="center" valign="middle" >Elongation at break in %</td><td align="center" valign="middle" >200</td></tr><tr><td align="center" valign="middle" >Continuous temperature in ˚C (6)</td><td align="center" valign="middle" >70 - 5</td></tr></tbody></table></table-wrap><p>cable and the neutral was immerse in the water bath. A voltage of 8 kV (8000 V) was sent through the cable (the time depends on the test to be performed).</p><p>During the study, the applied method was to determine the leakage current of the insulating tape than based on Ohm’s law, deduced the resistance of the insulating tape:</p><p>U = R ⋅ I l e a k i n g (1)</p><p>In order to evaluate the chemical attacks resistance, the used of a round bottom flask of 11, a principal solution, distilled water for dilution, a volumetric pipette, sulfuric acid, two beakers and a stopwatch. After the samples and the sulfuric acid solution’s preparation, these samples were immerse in an acid solution for 48 hours and then dried after 24 hours in an oven at 150˚C until a constant mass was obtain.</p></sec></sec><sec id="s3"><title>3. Results</title><sec id="s3_1"><title>3.1. Results Presentation on the Total Resistance of the Cable</title><p>The table shows 3940.88 Mega Ohms characterizes the resistance of PVC insulation. However, it should be noted that there is no such thing as perfect insulation (i.e., no insulation has infinite resistance); from that, a certain quantity of electricity always flows along or through the insulation to the outside environment. A good insulation essentially means a relatively high resistance to current. In order to describe an insulating material, a good insulation also means “the ability to maintain a high resistance” [<xref ref-type="bibr" rid="scirp.120193-ref8">8</xref>].</p><p>Having a look at the results obtained in <xref ref-type="table" rid="table4">Table 4</xref>, a confirmation come out that the isolation performed at L.C/Gecamines main office is good quality. Furthermore, if measured at regular time intervals, it is possible to monitor it degradation’s trends.</p><p><xref ref-type="table" rid="table5">Table 5</xref> shows the decrease in insulation resistance over time at 40˚C (near ambient temperature), 70˚C, 100˚C and 160˚C.</p></sec><sec id="s3_2"><title>3.2. Estimated Lifetime of Insulating Tape in PVC</title><p><xref ref-type="table" rid="table4">Table 4</xref> below presented a highlighted lifetime of the insulation according to the different test temperature. Started from the graphical representation of each case, and then conducted through Excel, the trend line resulted to an equation of decrease’s evolution of the resistance according to time (Graphic 1).</p><p>Starting from the trend of the insulation resistance loss (plasticizer loss), R e s = − 0.0091 t + 3940 (with R 2 = 0.9992 : Determination graphical coefficient) where R e s = 8 Mega Ohms;</p><p>The lifetime would then be equal to:</p><p>t = 3940 − 8 0.0091 → t = 432 , 087.9121 Life hours corresponded to &#177; 50 years.</p><table-wrap id="table4" ><label><xref ref-type="table" rid="table4">Table 4</xref></label><caption><title> Estimated total strength of the PVC insulation after the test</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Size</th><th align="center" valign="middle" >Voltage in V</th><th align="center" valign="middle" >Current I (micro A)</th><th align="center" valign="middle" >Insulation resistance (Ohms)</th></tr></thead><tr><td align="center" valign="middle" >values obtained</td><td align="center" valign="middle" >8000</td><td align="center" valign="middle" >2.03</td><td align="center" valign="middle" >3940.88</td></tr></tbody></table></table-wrap><table-wrap id="table5" ><label><xref ref-type="table" rid="table5">Table 5</xref></label><caption><title> Insulation resistance of the cable at different temperatures according to a time interval</title></caption><table><tbody><thead><tr><th align="center" valign="middle"  rowspan="2"  >Cable insulation resistance</th><th align="center" valign="middle"  rowspan="2"  >Initial</th><th align="center" valign="middle"  colspan="4"  >Study time (t) in Hours</th></tr></thead><tr><td align="center" valign="middle" >1 Hour</td><td align="center" valign="middle" >3 Hours</td><td align="center" valign="middle" >5 Hours</td><td align="center" valign="middle" >8 Hours</td></tr><tr><td align="center" valign="middle" >Insulation resistance at 40˚C (Mega Ohms)</td><td align="center" valign="middle" >3940</td><td align="center" valign="middle" >3939.9907</td><td align="center" valign="middle" >3939.9729</td><td align="center" valign="middle" >3939.953</td><td align="center" valign="middle" >3939.928</td></tr><tr><td align="center" valign="middle" >Insulation resistance at 70˚C (Mega Ohms)</td><td align="center" valign="middle" >3940</td><td align="center" valign="middle" >3939.985</td><td align="center" valign="middle" >3939.956</td><td align="center" valign="middle" >3939.93</td><td align="center" valign="middle" >3939.8895</td></tr><tr><td align="center" valign="middle" >Insulation resistance at 100˚C (Mega Ohms)</td><td align="center" valign="middle" >3940</td><td align="center" valign="middle" >3939.978</td><td align="center" valign="middle" >3939.933</td><td align="center" valign="middle" >3939.8898</td><td align="center" valign="middle" >3939.837</td></tr><tr><td align="center" valign="middle" >Insulation resistance at 160˚C (Mega Ohms)</td><td align="center" valign="middle" >3940</td><td align="center" valign="middle" >3939.962</td><td align="center" valign="middle" >3939.8906</td><td align="center" valign="middle" >3939.801</td><td align="center" valign="middle" >3939.6868</td></tr></tbody></table></table-wrap><disp-formula id="scirp.120193-formula1"><graphic  xlink:href="//html.scirp.org/file/4-1561166x11.png?20220928171031644"  xlink:type="simple"/></disp-formula><p>Graphic 1. Progress of PVC strength as a test time’s function at 40˚C.</p><p>According to this theory, the lifetime seems to be long because the main way of PVC insulation deterioration at this temperature consists in the evaporation of the plasticizer, the deshychloration is so low and even negligible. The Brebu’s work [<xref ref-type="bibr" rid="scirp.120193-ref9">9</xref>], who studied waste medium voltage cables (6 - 10 kV) after 18 years of operation, concludes that the PVC’s deshycloration is very low under service conditions. Indeed, according Hishler [<xref ref-type="bibr" rid="scirp.120193-ref8">8</xref>], it would take at least 2 billion years to have a release of 1% by mass of HCl at 40˚C. clearly, this estimate has no physical significance since the material itself will not survive that many years, but it does confirm that deshychloration of PVC is a negligible phenomenon at low, near ambient temperatures.</p><p>Graphic 2 shows the pattern of insulation resistance loss as a function of time, this pattern translates into the straight line R e s = − 0.0138 t + 3940 (with R 2 = 0.9996 : coefficient of graphical determination).</p><p>From this line, a lifetime of &#177;33 years is obtained. This loss of strength is largely due to the loss of plasticizer at 70˚C. However, in the case of PVC, the loss of plasticizer mass, as shown in the previous point, is mainly due to evaporation [<xref ref-type="bibr" rid="scirp.120193-ref5">5</xref>], Ekelund [<xref ref-type="bibr" rid="scirp.120193-ref10">10</xref>] studied the thermal ageing of a PVC electrical cable insulation. The results showed:</p><p>&#183; The plasticizer (DEHP) loss process is controlled by evaporation below 100˚C;</p><p>&#183; The evaporation rate of the plasticizer is constant in the studied time interval (150 days), looking at the strength loss curve, the trend of the line is almost linear, so its rate is constant also during 8 hours of research.</p><p>The trend of straight line of the decrease of the insulation resistance R e s = − 0.0205 t + 3940 ( R 2 = 0.9968 : coefficient of graphical determination), inducted to a lifetime of 22 years (Graphic 3).</p><p>If the temperature is at 70˚C, the only mode of plasticizer loss was evaporation;</p><disp-formula id="scirp.120193-formula2"><graphic  xlink:href="//html.scirp.org/file/4-1561166x16.png?20220928171031644"  xlink:type="simple"/></disp-formula><p>Graphic 2. Progress of the strength of PVC as a test time’s function at a temperature of 70˚C.</p><p>however, at 100˚C, this loss is largely due to evaporation of the plasticizer but also to a slight deshychloration. The Hishler’s work [<xref ref-type="bibr" rid="scirp.120193-ref8">8</xref>] shows a very low release off HCl below 105˚C (close to 100˚C) (Graphic 4).</p><p>The PVC insulation decrease resistance is show by the straight line R e s = − 0.0394 t + 3940 (with R 2 = 0.999 : coefficient of graphical determination), this inducted a lifetime of &#177; 12 years.</p><p>This low lifetime obtained is justified by different aspects: at 160˚C, out from the loss of plasticizer (which is generally known), the PVC itself undergoes deterioration due to deshychloration as shown by the Ekelund’s work, between 120˚C and 180˚C, the deterioration of PVC in electrical cables consists mainly to a deshychloration. The latter is a bad phenomenon because it propagates by sequential removal of HCl molecules along the chain. Each removal creates a</p><disp-formula id="scirp.120193-formula3"><graphic  xlink:href="//html.scirp.org/file/4-1561166x19.png?20220928171031644"  xlink:type="simple"/></disp-formula><p>Graphic 3. Progress of the strength of PVC as a test time’s function at a temperature of 100˚C.</p><disp-formula id="scirp.120193-formula4"><graphic  xlink:href="//html.scirp.org/file/4-1561166x20.png?20220928171031644"  xlink:type="simple"/></disp-formula><p>Graphic 4. Progress of PVC insulations resistance as a test time’s function at a temperature of 160˚C.</p><p>structural irregularity (double bond) that destabilizes the next monomer unit. Several deshychloration acts created polyene sequences along the chain that ultimately caused material’s yellowing and its thermal, optical and electrical properties changes [<xref ref-type="bibr" rid="scirp.120193-ref11">11</xref>].</p></sec><sec id="s3_3"><title>3.3. Resistance to Acid Attacks</title><p>Each insulating tape’s presence constituents particularly affects the acid resistance value of the cables. <xref ref-type="table" rid="table6">Table 6</xref> shows the change in mass of the samples after 48 hours test.</p><p>The above table shows that after 48 hours of immersion in sulfuric acid (pH 1.5 and density 1.84 g/cm<sup>3</sup>), a mass loss of 0.2470 g was observed, i.e. a rate of 2.027% per day. Thus, at a pH of 1.5; L.C cables have very poor resistance to acid attack. These results coincide with those proven by IPEX [<xref ref-type="bibr" rid="scirp.120193-ref12">12</xref>], performing a similar operation on PVC at 23˚C and 60˚C; the results showed that the PVC cable is non-resistant to 98% sulfuric acid attack but it states that it resists to sulfuric acid attack with a mass percentage of less than 80%. On the other hand, the commercial company Alfa Flex [<xref ref-type="bibr" rid="scirp.120193-ref13">13</xref>] proposes a good resistance of standard PVC from 10% to 50% mass of sulfuric acid, and a worst resistance for a higher massive percentage evaluated at 50% in acid. These operations were carried out at temperatures of 20˚C and 60˚C.</p></sec></sec><sec id="s4"><title>4. Conclusions</title><p>The present work is divided in two parts, the evaluation of the performance and the life span of LC/Gecamines cables subjected to a force thermal ageing and the characterization of their resistance to chemical attacks. The sample of the cable produced and insulated at LC/Gecamines has characteristics such as:</p><p>&#183; The PVC: density is 1.52 g/cm<sup>3</sup>, a low tensile strength of 13.6 Mpa (between 15 Mpa - 18 Mpa indicated by supplier) and an elongation at break of 200% (200% - 280% indicated by supplier).</p><p>&#183; Copper: a strain of 34.8%, a breaking load of 21.8 kg/mm<sup>2</sup> (annealed material); a resistivity of 0.017 ohm mm<sup>2</sup>/m and a density of 8.93 g/cm<sup>3</sup>.</p><p>Therefore, the study of its performance and the accurate prediction of its lifetime remain economic, safety and strategic issues for the industries. Focusing on safety perspective, this work inscribed the objective to put LC cables in forced ageing in order to evaluate their performance and their life span in precarious conditions. This study used samples coming from cables produced and insulated in PVC at the main office of Gecamines Rolling Mills and Cable Factory. The results showed that the insulation carried out by the L.C/Gecamines main office is a great quality because the insulation resistances are high (i.e. 3940 Mega Ohms</p><table-wrap id="table6" ><label><xref ref-type="table" rid="table6">Table 6</xref></label><caption><title> Results of the chemical attack test</title></caption><table><tbody><thead><tr><th align="center" valign="middle" >Designation</th><th align="center" valign="middle" >Front weight (g)</th><th align="center" valign="middle" >Mass taken after (g)</th><th align="center" valign="middle" >Losses (g)</th></tr></thead><tr><td align="center" valign="middle" >Weight gain</td><td align="center" valign="middle" >6.0918</td><td align="center" valign="middle" >5.8448</td><td align="center" valign="middle" >0.247</td></tr></tbody></table></table-wrap><p>under normal conditions). The results showed a lifetime of more than 50 years at a temperature of 40˚C (close to an ambient temperature), &#177; 33 years at a temperature of 70˚C, 22 years at a temperature of 100˚C and &#177; 12 years at a temperature of 160˚C. For chemical attacks, the results showed that PVC cables have a poor resistance to sulfuric acid attack (having a pH of 1.5 and a density of 1.84 g/cm<sup>3</sup>). These results allow L.C/Gecamines’s customers to realize that is possible to order insulated electrical cables that can work in such extreme temperature conditions but also on short scale into higher acidic environment.</p></sec><sec id="s5"><title>Conflicts of Interest</title><p>The authors declare no conflicts of interest regarding the publication of this paper.</p></sec><sec id="s6"><title>Cite this paper</title><p>Yannick, C.M.M., Ngoie, M.K., Francis, M.M., Francis, K.M., Mav&#233;, K.M., Edmond, T.K. and Donatien, L.M. (2022) Performance Survey of PVC Insulation of LC/Gecamines Electrical Cables Subjected to Ageing and Its Life Span Evaluation. World Journal of Engineering and Technology, 10, 728-737. https://doi.org/10.4236/wjet.2022.104047</p></sec></body><back><ref-list><title>References</title><ref id="scirp.120193-ref1"><label>1</label><mixed-citation publication-type="other" xlink:type="simple">Gécamines SA Website (2020) https://www.gecamines.cd/</mixed-citation></ref><ref id="scirp.120193-ref2"><label>2</label><mixed-citation publication-type="other" xlink:type="simple">A. Lapp (2020) Lapp Cable Guide.  
http://www.elecsa-tn.com/tn/en/telechargements/</mixed-citation></ref><ref id="scirp.120193-ref3"><label>3</label><mixed-citation publication-type="other" xlink:type="simple">Carrega, M., et al. (2007) Polymeric Materials, 2 Edition, Dunod, Paris, 5-180.</mixed-citation></ref><ref id="scirp.120193-ref4"><label>4</label><mixed-citation publication-type="other" xlink:type="simple">Augustin, M.K. (2019) Lecture Notes of Health and Safety in Industry, Bac 3, Polytechnics, University of Lubumbashi.</mixed-citation></ref><ref id="scirp.120193-ref5"><label>5</label><mixed-citation publication-type="other" xlink:type="simple">Mkacher, I. (2012) Thermal Aging of PE and PVC Sheet of Electrical Cables. ENAM, Paris.</mixed-citation></ref><ref id="scirp.120193-ref6"><label>6</label><mixed-citation publication-type="other" xlink:type="simple">Megger (2006) A Comprehensive Guide to Electrical Insulation Testing. 68. 
https://www.instrumart.com/assets/Megger-Guide-to-Insulation-Testing.pdf</mixed-citation></ref><ref id="scirp.120193-ref7"><label>7</label><mixed-citation publication-type="other" xlink:type="simple">Vergnes, B. (1993) Tribology and Polymer Shaping. Materials &amp; Techniques, 32, 33-36.  
https://doi.org/10.1051/mattech/199381010033</mixed-citation></ref><ref id="scirp.120193-ref8"><label>8</label><mixed-citation publication-type="other" xlink:type="simple">Hirschler, M. (2005) Hydrogen Chloride Evolution from the Heating of Poly (vinyl Chloride) Compounds. Fire and Materials, 29, 367-382.  
https://doi.org/10.1002/fam.893</mixed-citation></ref><ref id="scirp.120193-ref9"><label>9</label><mixed-citation publication-type="other" xlink:type="simple">Brebu, M., et al. (2000) Study of the Natural Ageing of PVC in Salution for Electrical Cables. Polymer Degradation and Stability, 67, 209-221.  
https://doi.org/10.1016/S0141-3910(99)00114-7</mixed-citation></ref><ref id="scirp.120193-ref10"><label>10</label><mixed-citation publication-type="other" xlink:type="simple">Ekelund, M., Edin, H. and Gedde, U.W. (2007) Long-Term Performance of Poly (Vinyl Chloride) Cables. Mechanical and Electrical Performances, 92, 617-629.  
https://doi.org/10.1016/j.polymdegradstab.2007.01.005</mixed-citation></ref><ref id="scirp.120193-ref11"><label>11</label><mixed-citation publication-type="other" xlink:type="simple">Carette, L. (1992) Stabilizant. Techniques de L’ingénieur, Paris.</mixed-citation></ref><ref id="scirp.120193-ref12"><label>12</label><mixed-citation publication-type="other" xlink:type="simple">Ipex (2013) PVC: Chemical Resistance Guide. Ontario, 14.  
https://docplayer.net/227573498-Pvc-chemical-resistance-guide.html</mixed-citation></ref><ref id="scirp.120193-ref13"><label>13</label><mixed-citation publication-type="other" xlink:type="simple">Alfaflex (2019) Chemical Resistance of PVC Cables.</mixed-citation></ref></ref-list></back></article>