<?xml version="1.0" encoding="UTF-8"?><!DOCTYPE article  PUBLIC "-//NLM//DTD Journal Publishing DTD v3.0 20080202//EN" "http://dtd.nlm.nih.gov/publishing/3.0/journalpublishing3.dtd"><article xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink" dtd-version="3.0" xml:lang="en" article-type="research article"><front><journal-meta><journal-id journal-id-type="publisher-id">JPEE</journal-id><journal-title-group><journal-title>Journal of Power and Energy Engineering</journal-title></journal-title-group><issn pub-type="epub">2327-588X</issn><publisher><publisher-name>Scientific Research Publishing</publisher-name></publisher></journal-meta><article-meta><article-id pub-id-type="doi">10.4236/jpee.2020.811002</article-id><article-id pub-id-type="publisher-id">JPEE-104392</article-id><article-categories><subj-group subj-group-type="heading"><subject>Articles</subject></subj-group><subj-group subj-group-type="Discipline-v2"><subject>Engineering</subject></subj-group></article-categories><title-group><article-title>
 
 
  Parameters Calculation of Underground Cables Using MATLAB
 
</article-title></title-group><contrib-group><contrib contrib-type="author" xlink:type="simple"><name name-style="western"><surname>Bin</surname><given-names>Sun</given-names></name><xref ref-type="aff" rid="aff1"><sub>1</sub></xref><xref ref-type="corresp" rid="cor1"><sup>*</sup></xref></contrib></contrib-group><aff id="aff1"><label>1</label><addr-line>Hitachi ABB Power Grids, Raleigh, USA</addr-line></aff><pub-date pub-type="epub"><day>26</day><month>11</month><year>2022</year></pub-date><volume>08</volume><issue>11</issue><fpage>12</fpage><lpage>20</lpage><history><date date-type="received"><day>14,</day>	<month>October</month>	<year>2020</year></date><date date-type="rev-recd"><day>23,</day>	<month>November</month>	<year>2020</year>	</date><date date-type="accepted"><day>26,</day>	<month>November</month>	<year>2020</year></date></history><permissions><copyright-statement>&#169; Copyright  2014 by authors and Scientific Research Publishing Inc. </copyright-statement><copyright-year>2014</copyright-year><license><license-p>This work is licensed under the Creative Commons Attribution International License (CC BY). http://creativecommons.org/licenses/by/4.0/</license-p></license></permissions><abstract><p>
 
 
  With the development of technology, more and more options are available for insulated cables in power systems. Different cable construction types have different impedance, voltage drop and power losses. In order to efficiently design these cable systems and adequately model them for system analysis, 
  engineers should be able to calculate the parameters of different types of cables. 
  Although the methods of parameters calculation are very mature, few types of software are used to calculate all these parameters for different cables
  .
   
  The objective of this paper is to build a user-friendly software to calculate these parameters with greater flexibility even if the users are not familiar with the methods of estimating the parameters of different types of cables. A program that is used to calculate the parameters of different cross-sections of cables is built by combining the method of estimating these parameters with the graphical user interface (GUI). Using this program, users can input or choose any type of cables, and calculate the parameters they need. In the future, more functions can be added to the program and the code could be switched to python or C# and develop a better GUI (Graphical User Interface).
 
</p></abstract><kwd-group><kwd>Carson Line Method</kwd><kwd> Tape Shield Cable</kwd><kwd> Concentric Neutral Cable</kwd></kwd-group></article-meta></front><body><sec id="s1"><title>1. Introduction</title><p>Nowadays, more and more cables are used in power systems. To efficiently design these cable systems, engineers should be able to calculate the parameters of different types of cables. Although the methods, which include calculations of impedance matrix, power losses, and voltage drop, are very mature [<xref ref-type="bibr" rid="scirp.104392-ref1">1</xref>] [<xref ref-type="bibr" rid="scirp.104392-ref2">2</xref>], few types of software are used to calculate all these parameters for different cables [<xref ref-type="bibr" rid="scirp.104392-ref3">3</xref>]. There are some other cable data calculators [<xref ref-type="bibr" rid="scirp.104392-ref4">4</xref>] [<xref ref-type="bibr" rid="scirp.104392-ref5">5</xref>], but it’s difficult for users to specify cables’ cross-sections. The objective of this paper is to build a user-friendly software to calculate these parameters with greater flexibility even if the users are not familiar with the methods of estimating the parameters of different types of cables. To complete the program, it’s necessary to know that two different types of cables are commonly used in the distribution system: concentric neutral cable and tape shield cable [<xref ref-type="bibr" rid="scirp.104392-ref1">1</xref>]. Before calculating the parameters of a cable, the composition of cables must be studied first. Generally, there are five levels of different materials. They are a copper conductor, EPR for fixation, insulation EPR, neutral copper conductors, and a jacket for physical protection as shown in <xref ref-type="fig" rid="fig1">Figure 1</xref>. However, for different types of cables, there are different conductor configurations.</p><p>For a common concentric neutral cable, the layer arrangement is shown in <xref ref-type="fig" rid="fig2">Figure 2</xref>. The inner layer is normally an aluminum conductor and the second layer is the EPR insulation. The circles around the insulation layer are several symmetrical copper conductors named neutral line. The outermost layer is a rubber jacket for physical protection. When the conductors are connected with a voltage source, the voltage distribution is shown in <xref ref-type="fig" rid="fig3">Figure 3</xref>.</p><p>For a standard tape shield cable, the layer arrangement is shown in <xref ref-type="fig" rid="fig4">Figure 4</xref>. The inner layer is a copper conductor and the second layer is the EPR insulation. The thin layer around the insulation layer is a copper shield that is normally grounded. The outermost layer is a rubber jacket for physical protection. When the conductors are connected with a voltage source, the voltage distribution is shown in <xref ref-type="fig" rid="fig5">Figure 5</xref>.</p></sec><sec id="s2"><title>2. Method</title><p>Carson line method is used to estimate the impedance matrix and calculate the parameters of these two types of cables [<xref ref-type="bibr" rid="scirp.104392-ref1">1</xref>]. For a concentric neutral cable, Equations (1)-(6) below are used to estimate the parameters [<xref ref-type="bibr" rid="scirp.104392-ref1">1</xref>].</p><p>Z a a = ( r a + r d ) + j ω k ln ( D e / D s a ) / mile (1)</p><p>Z a b = r d + j ω k ln ( D e / D a b ) / mile (2)</p><p>GMR = GMR s ∗ K ∗ R K − 1 K f t (3)</p><p>R = ( d o d − d s ) / 2 = ( d o d − d s ) / 2 ∗ 12 f t (4)</p><p>r c n = r s / K Ω / mile (5)</p><p>D i j 3 = D n m K − R K K (6)</p><p>where D<sub>sa</sub> is the conductor GMR in ft; D<sub>e</sub> is the earth GMR constant = 2790 ft for average earth; ωk = 0.12134; r<sub>a</sub> is the resistance of the conductor in Ω/unit length; r<sub>d</sub> = 0.09528 Ω/mile, is the resistance of Carson line; d<sub>od</sub> is the nominal diameter of the cable in inches; d<sub>s</sub> is the diameter of the neutral conductor in inches; GMR<sub>s</sub> is the geometric mean radius of the neutral conductor in ft; r<sub>s</sub> is the resistance of neutral conductor in Ω/mile; r<sub>d</sub> is the earth constant resistance coefficient; K is the number of concentric neutral strands; R is the radius of a circle passing through the center of the concentric neutral strands; r<sub>cn</sub> is the equivalent resistance of the concentric neutral. These parameters are shown in <xref ref-type="fig" rid="fig6">Figure 6</xref>. Equation (1) and (2) are used to calculate self-impedance and mutual impedance separately.</p><p>For a tape shield cable, the parameters are shown in <xref ref-type="fig" rid="fig7">Figure 7</xref>. All equations are the same except Equations (3) and (5) [<xref ref-type="bibr" rid="scirp.104392-ref1">1</xref>].</p><p>GMR shield = ( d s − T / 1000 ) / 2 ∗ 12   in f t (7)</p><p>r shield = 7.9385 ∗ 10 8 P ( Ω ∗ m ) d s ( inch ) * T ( m .inch ) (8)</p><p>Using the above equations combined with some other basic electrical equations, the impedance matrix of any cross-sections can be calculated. For example, the cross-section is shown in <xref ref-type="fig" rid="fig8">Figure 8</xref>.</p><p>Using Equation (1) and (2), a 13 &#215; 13 impedance matrix could be developed with the corresponding conductor positions.</p><p>In order to simplify, number all the conductors:</p><p>Top Row: A1 = “1”, C1 = “2”, B1 = “3”, B2 = “4”, C2 = “5”, A2 = “6”.</p><p>Bottom Row: A1 = “7”, C1 = “8”, B1 = “9”, B2 = “10”, C2 = “11”, A2 = “12”.</p><p>Ground: G = “13”.</p><p>The output impedance matrix is as follows:</p><p>Z a b c g = [ z 1 , 1 ⋯ z 1 , 12 z 1 , 13 ⋮ ⋱ ⋮ ⋮ z 12 , 1 ⋯ z 12 , 12 z 12 , 13 z 13 , 1 ⋯ z 13 , 12 z 13 , 13 ] 13 &#215; 13 (9)</p><p>Because the 13th row and 13th column correspond to the ground conductor, the ground conductor can be eliminated by the equation:</p><p>Z abc = [ z 1 , 1 ⋯ z 1 , 12 ⋮ ⋱ ⋮ z 12 , 1 ⋯ z 12 , 12 ] 12 &#215; 12 − [ z 1 , 13 ⋮ z 12 , 13 ] 1 z 13 , 13 [ z 13 , 1 ⋯ z 13 , 12 ] (10)</p><p>This equation is also called Kron Reduction [<xref ref-type="bibr" rid="scirp.104392-ref2">2</xref>].</p><p>Now the impedance matrix of the line is calculated. But the loads on the bus that is connected with the ground should be considered too. So the Z<sub>abc</sub> matrix for the cable bus plus the load is calculated using</p><p>Z abc,total = [ z 1 , 1 ⋯ z 1 , 12 ⋮ ⋱ ⋮ z 12 , 1 ⋯ z 12 , 12 ] 12 &#215; 12 + [ Z load,1 ⋯ 0 ⋮ ⋱ ⋮ 0 ⋯ Z load,12 ] (11)</p><p>Using the total impedance matrix established, the current flowing through the conductors can be calculated using Equation (11).</p><p>V input = Z abc,total ⋅ I (12)</p><p>where the current vector (I) has 12 &#215; 1 complex numbers for the 12 conductors. Therefore, the input voltage vector (V<sub>input</sub>), total impedance matrix, and the current vector can be calculated as</p><p>I = Z abc,total − 1 ⋅ V i n p u t (13)</p><p>where the input voltages are described in Equation (14) if the system is balanced:</p><p>V A 1 = V A 2 = V A 3 = V A 4 = V r a t e d 3 ∠ 0 ∘ V B 1 = V B 2 = V B 3 = V B 4 = V r a t e d 3 ∠ − 120 ∘ V C 1 = V C 2 = V C 3 = V C 4 = V r a t e d 3 ∠ 120 ∘ V input = [ V A 1 V C 1 V B 1 V B 2 V C 2 V A 2 V A 3 V C 3 V B 3 V B 4 V C 4 V A 4 ] (14)</p><p>If there are multiple neutral lines, the conventional method is to reduce them into one equivalent neutral line, which follows Equation (15).</p><p>D s = ( D a a D a b ⋯ D a n ) ( D b a D b b ⋯ D b n ) ⋯ ( D n a D n b ⋯ D n n ) n 2 (15)</p><p>where D<sub>ij</sub> is the distance between neutral i and neutral j. If i = j, D<sub>ij</sub> means GMR; n means n-strand bundle neutral.</p></sec><sec id="s3"><title>3. Results</title><p>Using Carson line method, a software that is used to calculate the parameters of two types of cables for different cross-sections was developed. Using this program, users can input or choose some initial values, and calculate the parameters they need, such as impedance matrix, voltage drop and power loss.</p><p>In this program, there are 26 preloaded cross-sections that are ready to be used. If they are not enough, this program allows the user to specify the locations of all individual cables. When the user inputs the line to line voltage, current, power factor of the load, ambient temperature, conductor type, cable bus length, cable’s outer diameter, conductor size, diameter of ground, size of ground and specified cross-section, the program will look up standard tables of different cables and obtain related parameters, such as conductor resistance and its diameter. Then it will use the Carson line method and cable equations to calculate the final impedance matrix to be used for power losses and voltage drop calculations. The main process of the MATLAB code is shown in <xref ref-type="fig" rid="fig9">Figure 9</xref>.</p><p>Based on the MATLAB impedance matrix calculation code, the graphical user interface (GUI) of this program was built, and the sample calculation results were displayed, as shown in <xref ref-type="fig" rid="fig1">Figure 1</xref>0. Using this GUI, users can choose and input initial values before easily calculating the impedance matrix to be used for different calculations.</p></sec><sec id="s4"><title>4. Conclusion</title><p>In recent years, more and more electrical utilities are using cables to distribute electric power to their customers. However, few types of software are developed</p><p>to calculate parameters for different cables. In this paper, a MATLAB-based program is built to calculate parameters of different types of cables including impedance matrix, power losses, and voltage drop. Users can input and select some initial values and easily calculate the parameters they need using the developed user-friendly software. With these parameters, power utilities can realize the conditions of cables and predict their voltage drop and power losses, and select the best type of cables they need.</p></sec><sec id="s5"><title>Conflicts of Interest</title><p>The author declares no conflicts of interest regarding the publication of this paper.</p></sec><sec id="s6"><title>Cite this paper</title><p>Sun, B. (2020) Parameters Calculation of Underground Cables Using MATLAB. Journal of Power and Energy Engineering, 8, 12-20. https://doi.org/10.4236/jpee.2020.811002</p></sec></body><back><ref-list><title>References</title><ref id="scirp.104392-ref1"><label>1</label><mixed-citation publication-type="other" xlink:type="simple">Gonen, T. (2013) Electric Power Distribution Engineering. Third Edition, CRC Press, Boca Raton.</mixed-citation></ref><ref id="scirp.104392-ref2"><label>2</label><mixed-citation publication-type="other" xlink:type="simple">Grainger, J.J. and Stevenson, W.D. (1994) Power System Analysis. McGraw-Hill Book Co., New York.</mixed-citation></ref><ref id="scirp.104392-ref3"><label>3</label><mixed-citation publication-type="other" xlink:type="simple">CYME International—CYMCAP. http://www.cyme.com/software/cymcap/</mixed-citation></ref><ref id="scirp.104392-ref4"><label>4</label><mixed-citation publication-type="other" xlink:type="simple">Calculation of Cable Data. http://nepsi.com/resources/calculators/calculation-of-cable-data.htm</mixed-citation></ref><ref id="scirp.104392-ref5"><label>5</label><mixed-citation publication-type="other" xlink:type="simple">General Cable Tools. https://www.generalcable.com/eu/en/information-center/tools-applications/gc-app-low-voltage</mixed-citation></ref></ref-list></back></article>